MC³ 90.10.EX O&M Manual
- 26 -
Date/Time
For setting the date and time parameters, follow the direction given the Entering New Values
section found on page 21.
Analog Input
The analog inputs can be mapped to Analog Setpoint or Panel Meter functions. Two analog
inputs are available when there are two PCIO boards installed into the controller. Once the inputs
are mapped, you should adjust the high, low and scaling values. The Analog I/O Diagnostics
(page 34) displays the active counts for the analog inputs and can be used to determine the high
and low values.
Analog Setpoint
When you intend to use an analog signal for the setpoint, an Analog Input Source must be set for
this input. The analog input selected is used for the setpoint when the Setpoint method is
Remote Analog Input.
Panel Meter
This selection is used to display a value of an analog input to be used for display purposes only.
The value is scaled to a user-defined value. The value can be set in the numeric parameter
selection (see below).
Analog Input Source Settings
The source used is analog input number 1 on PCIO board number 1.
The source used is analog input number 2, which is located on the PCIO board
number 2.
The value that is used for the function selected is always 0.
The value used is controlled through a register using the serial port.
Analog Input Numeric
Low Values
This value is the counts representing the zero level of the incoming signal. When the input signal
is set to 4-20mA (2-10V) input then this value should be 200,000 counts. If the input is set to 0-
20mA (0-10V) then the zero level should be close to 0 counts. Limits are minimum of 0 and a
maximum of 1,040,000.
High Values
This value is the representation of the 100% value of the incoming signal. Normally this value will
be 1,000,000 counts representing 100% (20mA or 10V) of the incoming signal. Limits are
minimum of 1 and a maximum of 1,040,000.
Maximum Scale Values
This is the value representing the full-scale value used for scaling the input. This value should be
associated with the analog input counts it is to represent