CIPHER CODES Related Commands

 (Commands 15 through 17)

Up to 10 cipher codes may be defined (user slots 0 through 9). Each cipher code may be from 1 to
6 digits long. Cipher codes shorter than 6 digits are terminated with the "#" key. Just like cards can
produce different results when read "upward", cipher codes can be entered in the "reverse" direction.
For example, cipher code "123" entered as "3", "2", "1", "#" will produce the action specified for
"reverse" entry of a user having the User Level assigned to cipher code "123".

Command 20 - Add a card (activate a user)

*

2 0

- select Command 20

1-3

- select the user level (1, 2, or 3)

0-1

0-9

0-9

0-9

- enter the user slot to activate (0000 through 1599)

Command 21 - Delete a card (deactivate a user)

* 2 1

- select Command 21

0-1

0-9      0-9

0-9

- enter the user slot to deactivate (0000 through 1599)

Command 22 - Add a range of cards (block activate)

* 2 2

- select Command 22

1-3

- select the user level (1-3)

0-1

0-9

0-9

0-9

- enter the first user slot to activate (0000 through 1599)

0-1

0-9

0-9

0-9

- enter the last user slot to activate (0000 through 1599)

Command 23 - Delete a range of cards (block deactivate)

* 2 3

- select Command 23

0-1     0-9      0-9       0-9

- enter the first user slot to delete (0000 through 1599)

0-1     0-9      0-9       0-9

- enter the last user slot to delete (0000 through 1599)

Command 15 - Add Cipher Code(s)

* 1 5

- select Command 15

1-3

- select the user level: 1, 2, or 3

0-9

- select the user number: 0 to 9

0-9 

 (

0-9 

)

#

- enter a 1 to 6 digit cipher code, end with '#'

(

0-9,

0-9

#

- additional codes will be added into successive slots 

)

* #

- any other action quits the 'add loop'

Command 16 - Delete a cipher code

* 1 6

- select Command 16

0-9

- select the user number to delete: 0 to 9

Command 17 - Delete a range of cipher codes

* 1 7

- select Command 17

0-9

- select the first user number to delete: 0 to 9

0-9

- select the last user number to delete: 0 to 9

BLOCK Database Mode Commands

 (Commands 20 through 23)

Use these commands to manage the card holders if the BLOCK database mode was selected
(Command 93 set to mode "1"). The block number is set by Command 94.

Summary of Contents for SR-10K

Page 1: ...Doc 10107 0007 Rev 1 04 Page 1 Mercury Security Corporation 2005 SR 10K SR 10K Mag Stripe Access System Users Guide...

Page 2: ...ode 6 Two Door Access Control 14 Mode 7 Access Control with Door Bell Feature 15 Mode 8 Dual Output Toggle on Valid Access 15 Installation 16 Maintenance 17 Specifications 17 Dimensions and Typical Co...

Page 3: ...p to 100 users factory default This mode allows the use of any magnetic stripe card with standard track 2 encod ing such as the MS SR10CC25 pre encoded packs of 25 cards or cards from many other acces...

Page 4: ...isplay the status of an exter nal device connected to an input such as an alarm panel s armed disarmed indicator An Operating Mode is a collection of these functions intended for a specific applicatio...

Page 5: ...etermines the installation wiring details and User Level assignment Lost Master Card Follow the steps outlined below to set a new Master Card in case the current Master Card is lost remove power from...

Page 6: ...on Command 12 Delete a card using the card 1 2 select Command 12 user card read the card to be deleted from that slot Command 13 Delete a range of cards 1 3 select Command 13 0 9 0 9 select the first...

Page 7: ...mmand 22 1 3 select the user level 1 3 0 1 0 9 0 9 0 9 enter the first user slot to activate 0000 through 1599 0 1 0 9 0 9 0 9 enter the last user slot to activate 0000 through 1599 Command 23 Delete...

Page 8: ...s to indicate transfer in progress The transfer of the entire block mode card database 1 600 users may take up to 1 minute The completion of a succesful transfer is indicated with the long beep A tran...

Page 9: ...with the Block Database Mode 4 The Block Number Command 94 must be set for Block Database Mode operation 5 In Facility Code Database Mode the digit count specifies the the number of card digits to rea...

Page 10: ...rd read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configuration Inputassignments Input I1 is connected to a...

Page 11: ...the status of Input I2 User Level 2 and 3 A downward read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configur...

Page 12: ...rd pulses Output K2 allowing the momentary closure to simulate a key switch input to an alarm panel User Level Specifications User Level 1 Both downward and upward read will pulse Output K1 User Level...

Page 13: ...etosimulate a key switch input to an alarm panel User Level Specifications UserLevel1 CardshavingthisUserLevelarerejectedifthecontactonInputI2isopen IfthecontactonInput I2 is closed Both downward and...

Page 14: ...t to Output K2 and functions as the access control input User Level 1 users are valid only when a closed contact is presented to this input UpperLEDassignment The upper LED follows Input I2 displaying...

Page 15: ...th Door Buzzer Control Description This mode is intended for applications where the outputs need to be toggled instead of the standard momentary pulse operation Both outputs are toggled Level 1 users...

Page 16: ...l off moisture for outdoor mounting To avoid having ESD electrostatic discharge interfering with the operation of the reader the reader casing shall be grounded This can be accomplished be tying the m...

Page 17: ...g nominal Interface Dimension 3 25 83mm W x 2 9 74mm L x 1 4 36mm H Weight 4 oz 120 g nominal Environmental Temperature 55 to 85 degrees C storage 40 to 75 degrees C operating Humidity Reader 100 RHN...

Page 18: ...ss over cable Maximum distance between reader and interface is 500 feet using 22AWG wires 6 COND STRAIGHT Typical Wiring Configuration Communication Wiring Maximum total cable length 4 000 ft 1 200 m...

Page 19: ...nap track The new module dimension is 4 25 x 2 75 inches Connection to the card reader is also changed from modular jack to a screw terminals for more convenient termination GND BLK BZR ORG LED BRN CL...

Reviews: