![Mercury SR-10K User Manual Download Page 18](http://html1.mh-extra.com/html/mercury/sr-10k/sr-10k_user-manual_1773642018.webp)
Doc. 10107-0007 Rev 1.04
Page 18
Mercury Security Corporation,
©
2005
SR-10K
1.4 [36]
2.
9
[
74]
3.25 [83]
2 X Ø0.18 [4.5]
HOLES
2.0 [50]
5.
5 [
140]
1.3 [33]
3.3
[
84]
2.
6
[
6
6
]
Reader and Interface Dimensions
Reader to Interface Connection:
Connect the Reader to the Interface
Module using the straight 6-conductor
modular cable. DO NOT use cross-
over cable. Maximum distance
between reader and interface is 500
feet using 22AWG wires.
6-COND. STRAIGHT
Typical Wiring Configuration
Communication Wiring:
Maximum total cable length - 4,000 ft [1,200 m], 24 AWG
JUMPER SETTING
Set each interface to unique address. Install RS-485 termination jumper, J4, on the first and last units only.
SR−10K
SR−10K
PRINTER INTERFACE
TO ADDITIONAL
SR−10K
(DISCONTINUED)
Exit Request
Door Contact
Strike
Forced Open,
Held Open
Alarm Buzzer
I1
I1
I2
I2
GND
+
12V
C
NC
NO
NO
C
NC
K1
K2
J2 Jumpers