13. Specifications: 

The interface is for use in low voltage, Class 2 circuits only. 

The installation of this device must comply with all local fire and electrical codes.

 

Primary Power: 

PoE (12.95 W), compliant to IEEE 802.3af 
or 
PoE+ (25 W), compliant to IEEE 802.3at  
or 
12 Vdc 



10 %, 1.8 A maximum 

Power Output: 

PoE: 12 Vdc @ 625 mA including reader and Auxiliary Power output * 

Power Output: 

PoE+ or external 12 Vdc: 12 Vdc @ 1.25 A including reader and Auxiliary 
Power output * 

Micro USB Port: 

5 Vdc maximum (deduct 270 mA from reader and Auxiliary Power output) 

* Excluding micro USB port 

 

PoE power is to be supplied by a Listed ITE or Access Control System Unit (ALVY), power limited, PoE+ 
injector or PoE+ Ethernet switch providing 42.5 

– 57 Vdc, 25.5W for maximum output. 

SRAM Backup Battery: 

Rechargeable battery 

microSD Card 

Format: microSD or microSDHC; 2GB to 8GB. 

Host Communication: 

Ethernet: 10-BaseT/100Base-TX and Micro USB port (2.0) with optional 
adapter: pluggable model USB2-OTGE100 

Inputs: 

Two unsupervised/supervised, Programmable End of Line resistors, 1k/1k 
ohm, 1 %, ¼ watt standard 
One unsupervised input dedicated for cabinet tamper 

Outputs: 

Two relays: Form-C contacts: 2 A @ 30 Vdc, resistive 

Reader Interface: 

Power: 

12 Vdc 

 10 %: PoE, PoE+ or local power supply, 300 mA maximum 

Data Inputs: 

Reader port 1: TTL compatible, F/2F or 2-wire RS-485 
Reader port 2: TTL compatible or F/2F 

LED Output: 

TTL compatible, high > 3 V, low < 0.5 V, 5 mA source/sink maximum 

Buzzer Output: 

Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum 

Cable Requirements: 

Power: 

1 twisted pair, 18 AWG (when using local 12 Vdc power supply) 

Ethernet: 

CAT-5, minimum  

Reader data (TTL): 

6-conductor, 18 AWG, 500 ft. (152 m) maximum 

Reader data (F/2F): 

4-conductor, 18 AWG, 500 ft. (152 m) maximum 

Reader data (RS-485):  1 twisted pair, shielded.  24 AWG, 120 ohm impedance, 

2000 ft. (610 m) maximum 

Alarm Input: 

1 twisted pair per input, 30 ohm maximum 

Outputs: 

As required for the load 

Environmental: 

Temperature: 

Storage 

-55 to +85 °C 

Operating 

0 to +70 °C 

Summary of Contents for LP1501

Page 1: ...TTL D1 D0 Clock Data or F 2F signaling also provides tri state LED control and buzzer control one wire LED mode only Two Form C contact relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 2 A 30 Vdc dry contact configuration Two inputs are provided that may be used for monitoring the door contact exit push button or alarm contact Input circuits can ...

Page 2: ...2 GND Auxiliary Power Output Ground TB4 3 VIN Input Power 12 Vdc from local power supply TB4 4 GND Input Power Ground TB5 1 NO Relay K1 Normally Open Contact TB5 2 1 C Relay K1 Common Contact TB5 3 NC Relay K1 Normally Closed Contact TB5 4 NO Relay K2 Normally Open Contact TB5 5 2 C Relay K2 Common Contact TB5 6 NC Relay K2 Normally Closed Contact Note 1 Terms A B are from the RS 485 standard Jump...

Page 3: ...unication address 0 Alternate Host Port Disabled 4 Bulk Erase Configuration Memory The bulk erase function can be used for the following purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing LP1501 board to continuously reboot If clearing the memory does not correct the initiali...

Page 4: ...ote serial I O devices using MSP1 protocol or up to two OSDP devices If two OSDP devices are used reader port 2 will not support a third reader If only one OSDP device is configured then reader port 2 is available for a second reader The maximum cable length is 2000 ft 610 m Do not terminate any RS 485 devices connected to reader port 1 When powering remote device s from the LP1501 be cautious not...

Page 5: ...AL I O MODULE MR16in MR16out FOR EXAMPLE MR62e MR50 MR52 GND GND 12 Vdc TR TR MR62e FOR EXAMPLE MR50 MR16out MR16in MR52 GND TR 12 Vdc GND TR TR TR FIRST READER PORT REFER TO THE APPROPRIATE REMOTE SERIAL I O DEVICE INSTALLATION MANUAL FOR ADDRESS AND BAUD RATE SETTINGS DO NOT TERMINATE ANY OF THE DEVICES ON THE RS 485 MULTI DROP COMMUNICATION BUS EACH REMOTE SERIAL I O DEVICE MUST BE CONFIGURED W...

Page 6: ... a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for proper egress door installation Door lock mechanisms can generate E...

Page 7: ...ne 80 ON 2 Host Communication Activity 3 Readers combined Clock Data or D1 D0 Mode Flashes when Data is Received Either Input RS 485 Mode Flashes when Transmitting Data F 2F Mode Flashes when Data Acknowledgment is Received 4 Input IN1 Status OFF Inactive ON Active Flash Fault See Note 1 5 Input IN2 Status OFF Inactive ON Active Flash Fault See Note 1 6 Cabinet Tamper 7 Reserved for Future Use D9 ...

Page 8: ...nication Ethernet 10 BaseT 100Base TX and Micro USB port 2 0 with optional adapter pluggable model USB2 OTGE100 Inputs Two unsupervised supervised Programmable End of Line resistors 1k 1k ohm 1 watt standard One unsupervised input dedicated for cabinet tamper Outputs Two relays Form C contacts 2 A 30 Vdc resistive Reader Interface Power 12 Vdc 10 PoE PoE or local power supply 300 mA maximum Data I...

Page 9: ...Levels Feature Level Standby Power I Endurance IV Line Security I Destructive Attack I These specifications are subject to change without notice 14 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 FIELD WIRING LP1501 WITH IN...

Page 10: ...ied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an alternative method for exit is available This prod...

Reviews: