* Inputs on supervised F/2F readers may be unsupervised or supervised (supervised shown). 
 

 

 

Reader Port 1 

Typical Supervised F/2F Reader

 

Reader Port 2 

Typical Supervised F/2F Reader

 

 

Jumper D1 and LED on supervised F/2F readers

 

 

 

Reader Port 1 - Remote Serial I/O Devices using MSP1 Protocol (2-Wire RS485)

 

 

Reader Port 1 - OSDP Protocol Devices (2-Wire RS-485)

 

1

TB2

VO (12 Vdc)

GND

LED

BZR

CLK/D1
DAT/D0

+12 Vdc

D1

GROUND

DO (GREEN LED)

F/2F Reader

NORMALLY CLOSED CONTACT *

DOOR MONITOR SWITCH

REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *

1K,1%

1K,1%

1K,1%

1K,1%

FIRST READER PORT

1

BZR

DAT/D0

CLK/D1

LED

1

GND

VIN

GND

VO

+12 Vdc

D1

GROUND

DO (GREEN LED)

F/2F Reader

1K,1%

1K,1%

1K,1%

1K,1%

SECOND READER PORT

TB3

TB4

DOOR MONITOR SWITCH

NORMALLY CLOSED CONTACT *

REQUEST TO EXIT SWITCH

NORMALLY OPEN CONTACT *

FIRST READER PORT

1

BZR

VO

DAT/D0

CLK/D1

LED

GND

VIN

GND

TB4

TB3

1

VO (12 Vdc)

CLK

LED

BZR

GND

DAT

TB2

1

REMOTE SERIAL I/O MODULE

REMOTE SERIAL I/O MODULE

MR16in
MR16out

FOR EXAMPLE:

MR62e

MR50
MR52

GND

GND

12

 V

dc

TR+

TR-

MR62e

FOR EXAMPLE:
MR50

MR16out

MR16in

MR52

GND

TR+

12

 V

dc

GND

TR-

TR+

TR-

FIRST READER PORT

REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR ADDRESS

AND BAUD RATE SETTINGS.  DO NOT TERMINATE ANY OF THE DEVICES ON THE RS-485 MULTI-DROP
COMMUNICATION BUS.  EACH REMOTE SERIAL I/O DEVICE MUST BE CONFIGURED WITH AN UNIQUE
COMMUNICATION ADDRESS.  A MAXIMUM OF EIGHT REMOTE SERIAL I/O DEVICES MAY BE
CONNECTED TO READER PORT 1.  CABLE SHIELD: ONLY GROUND ONE END.

GND

MRDT

MRDT

VO (12 Vdc)

GND

DAT

CLK

1

OSDP PROTOCOL DEVICE

9600 BAUD

ADDRESS 0

BZR

1

GND

GND

VIN

VO

DAT/D0

CLK/D1

1

LED

LED

BZR

OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD

REFER TO THE APPROPRIATE OSDP DEVICE INSTALLATION MANUAL FOR ADDRESS AND BAUD RATE

SETTINGS.  DO NOT TERMINATE ANY OF THE DEVICES ON THE RS-485 MULTI-DROP COMMUNICATION

BUS.  EACH OSDP DEVICE MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS.  A
MAXIMUM OF TWO OSDP DEVICES MAY BE CONNECTED TO READER PORT 1.  CABLE SHIELD: ONLY
GROUND ONE END.

(DEFAULT)

(DEFAULT)

TB4

TB3

TB2

FIRST READER PORT

GND

GND

12

 V

dc

TR+

TR-

GND

TR+

12

 V

dc

GND

TR-

TR+

TR-

FIRST READER PORT

GND

Summary of Contents for LP1501

Page 1: ...TTL D1 D0 Clock Data or F 2F signaling also provides tri state LED control and buzzer control one wire LED mode only Two Form C contact relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 2 A 30 Vdc dry contact configuration Two inputs are provided that may be used for monitoring the door contact exit push button or alarm contact Input circuits can ...

Page 2: ...2 GND Auxiliary Power Output Ground TB4 3 VIN Input Power 12 Vdc from local power supply TB4 4 GND Input Power Ground TB5 1 NO Relay K1 Normally Open Contact TB5 2 1 C Relay K1 Common Contact TB5 3 NC Relay K1 Normally Closed Contact TB5 4 NO Relay K2 Normally Open Contact TB5 5 2 C Relay K2 Common Contact TB5 6 NC Relay K2 Normally Closed Contact Note 1 Terms A B are from the RS 485 standard Jump...

Page 3: ...unication address 0 Alternate Host Port Disabled 4 Bulk Erase Configuration Memory The bulk erase function can be used for the following purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing LP1501 board to continuously reboot If clearing the memory does not correct the initiali...

Page 4: ...ote serial I O devices using MSP1 protocol or up to two OSDP devices If two OSDP devices are used reader port 2 will not support a third reader If only one OSDP device is configured then reader port 2 is available for a second reader The maximum cable length is 2000 ft 610 m Do not terminate any RS 485 devices connected to reader port 1 When powering remote device s from the LP1501 be cautious not...

Page 5: ...AL I O MODULE MR16in MR16out FOR EXAMPLE MR62e MR50 MR52 GND GND 12 Vdc TR TR MR62e FOR EXAMPLE MR50 MR16out MR16in MR52 GND TR 12 Vdc GND TR TR TR FIRST READER PORT REFER TO THE APPROPRIATE REMOTE SERIAL I O DEVICE INSTALLATION MANUAL FOR ADDRESS AND BAUD RATE SETTINGS DO NOT TERMINATE ANY OF THE DEVICES ON THE RS 485 MULTI DROP COMMUNICATION BUS EACH REMOTE SERIAL I O DEVICE MUST BE CONFIGURED W...

Page 6: ... a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for proper egress door installation Door lock mechanisms can generate E...

Page 7: ...ne 80 ON 2 Host Communication Activity 3 Readers combined Clock Data or D1 D0 Mode Flashes when Data is Received Either Input RS 485 Mode Flashes when Transmitting Data F 2F Mode Flashes when Data Acknowledgment is Received 4 Input IN1 Status OFF Inactive ON Active Flash Fault See Note 1 5 Input IN2 Status OFF Inactive ON Active Flash Fault See Note 1 6 Cabinet Tamper 7 Reserved for Future Use D9 ...

Page 8: ...nication Ethernet 10 BaseT 100Base TX and Micro USB port 2 0 with optional adapter pluggable model USB2 OTGE100 Inputs Two unsupervised supervised Programmable End of Line resistors 1k 1k ohm 1 watt standard One unsupervised input dedicated for cabinet tamper Outputs Two relays Form C contacts 2 A 30 Vdc resistive Reader Interface Power 12 Vdc 10 PoE PoE or local power supply 300 mA maximum Data I...

Page 9: ...Levels Feature Level Standby Power I Endurance IV Line Security I Destructive Attack I These specifications are subject to change without notice 14 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 FIELD WIRING LP1501 WITH IN...

Page 10: ...ied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an alternative method for exit is available This prod...

Reviews: