mercor mcr OMEGA pro Technical Manual Download Page 7

mcr OMEGA pro

 

Power and Control Panel  

 

„MERCOR” S.A. – 

The company reserves the right to modify and amend this document without notice. 

7/28 

 

3.2.

 

MAINS POWER SUPPLY 

The Power and Control Power can work either on 230 VAC / 1L+N+PE mains or 3x400 VAC/3L+PE or 
3L+N+PE mains. The mains can be supplied over wiring without a PE conductor; this requires a local PE 
connection of the Power and Control Panel. The mains input terminals are inside the Power and Control 
Panel and coupled directly to the main power switch which is used to isolate the Power and Control Panel 
from live voltage for e.g. servicing. 

The  mcr  OMEGA  pro  Power  and  Control  Panel  requires  uninterruptible  (secure  or 
redundant)  power  supply  which  shall  be  provided  from  a  separate  fire  power  supply 
section of the building's main switchboard to guarantee continued operation, even in the 
event of a fire. 

Optionally,  the  Power  and  Control  Panel  supply  input 
can be secured with type B+C or C surge protection that 
will  prevent  catastrophic  failure  of  this  device  in 
overvoltage  conditions,  e.g.  a  lightning  stroke  to  the 
building installation. 
 
 
 
 
 
 

3.3.

 

AUTOMATIC TRANSFER SWITCHING MODULE (ATS) 

 If the installation system design or the existing conditions of the building features no load transfer 

switching  at  the  main  switchboard,  whereas  no  uninterruptible  power  supply  can  be  connected  to  the 
Power  and  Control  Panel,  the  mcr  OMEGA  proF  can  be  optionally  equipped  with  the  Load  Transfer 
Switching Module. The Load Transfer Switching Module enables power for the Power and Control Panel 
from either of two separate mains supply lines. The Load Transfer Switching Module automatic control 
switches over the power loads from the primary mains supply to the backup power supply if the former 
suffers from an excessive voltage dip or failure. The backup power supply power rating must be equal to 
the primary mains supply power rating to ensure operating continuity of the Power and Control Panel. The 
load transfer switching delay is only several seconds long. During this delay, the control actuators will not 
cease to function; the panel control system is maintained by a UPS battery. The backup power supply can 
be replaced with an emergency power generator. In this configuration, the Power and Control Panel will 
start the emergency power generator via a dry contact signal upon a primary mains supply failure. When 
the  Power  and  Control  Panel  acknowledges  that  the  emergency  power  generator  outputs  the  correct 
voltage, the loads will be switched over to the latter. The time to correct output voltage of the emergency 
power generator cannot exceed 15 seconds. The Power and Control Panel may optionally feature a LED 
indicator for the emergency power generator status monitoring.  
The  following  operating  statuses  of 
the emergency power generator can 
be  indicated  (if  supported  by  the 
emergency power generator): 

  

 

Low battery, 

 

 

Startup failed, 

 

 

Engine overheated, 

 

 

Low oil pressure, 

 

 

Engine overspeed, 

 

 

Generator overload, 

 

 

Low fuel.

 

Fig. 4. Main power switch diagram.

 

Fig. 6.Diagram of ATS in mcr OMEGA proF Power Supply. 

Fig. 5. Surge protection diagram. 

Primary mains line 

Secondary mains line 

Summary of Contents for mcr OMEGA pro

Page 1: ...ąca ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 58 341 42 45 tel fax 58 341 39 85 TECHNICAL MANUAL Power and Control Panel mcr OMEGA pro mcr OMEGA pro mcr OMEGA proF Power Supply Unit mcr OMEGA pro revision 06 03 20 3 FIRE VENTILATION SYSTEMS _ ...

Page 2: ...AN STARTING CONTACTOR SYSTEMS 14 3 7 3 SOFTSTARTERS 15 3 7 4 INVERTERS FREQUENCY CONVERTERS 15 3 8 KLI LINE CONTINUITY MONITORING MODULE 16 3 9 MCR 0204 FIRE DETECTION MODULE 16 3 10 GAS EXTINGUISHING MODULE FFES 16 4 TECHNICAL SPECIFICATIONS 17 5 INSTALLATION AND CONNECTIONS ___________________________________ 18 5 1 ACTUATOR CONNECTIONS 18 5 1 1 FIRE PROTECTION DEVICE CONECTION CABLES 23 6 OPERA...

Page 3: ...nterior and Administration of 27 April 2010 amending the Regulation on the specification of products used to assure public safety or the protection of health and life and property as well as rules for issuance of certificates of admittance for the use of those products Compliance with these documents has been confirmed with applicable certificates granted by Polish institute CNBOP PIB for the mcr ...

Page 4: ...it and the mcr OMEGA pro Power and Control Panel must be installed in the same enclosure Power and Control Panel capabilities Manual alarm tripping with manual smoke venting controls Automatic fire detection with smoke detectors Fire Alarm System output handling Fire Alarm relay System fault data relay Alarm resetting and smoke damper closing Operating status monitoring for interfaced devices Manu...

Page 5: ...e Power and Control Panel operating logic algorithm is customized per the specification data and fire scenario requirements provided by the installation designer The panel is delivered to the customer complete with the installation diagrams operating logic algorithm specification and specification of components Optional functions available with the Power and Control Panel Actuators immobilized con...

Page 6: ...led on the top the bottom or the sides of the Power and Control Panel The mcr OMEGA pro Power and Control Panel enclosure may feature optional single or toggle switches for manual control of the interfaced devices and an emergency stop device switch Optional LED indicators can be installed on custom order to read the status of interfaced devices e g the emergency power generator live phases air fa...

Page 7: ...oad Transfer Switching Module enables power for the Power and Control Panel from either of two separate mains supply lines The Load Transfer Switching Module automatic control switches over the power loads from the primary mains supply to the backup power supply if the former suffers from an excessive voltage dip or failure The backup power supply power rating must be equal to the primary mains su...

Page 8: ...quipment including BE230V actuator dampers or small power fans up to 1 5 kW even if the primary mains supply of the Power and Control Panel fails The DC AC power converter generates a pure sine wave 230 V power output by conversion of battery output voltage The mains supply is isolated when the DC AC power converter is online The available DC AC power converter output ratings range from 200 W to 3...

Page 9: ...ORING AND CONTROL MODULES Each mcr MMS module has 12 digital inputs and 6 relay outputs Each mcr MMS module can feature one of the available extension cards that is installed in the CARD SLOT and feeding control signals to terminals 12 13 and 14 The available extension card types include 3 digital inputs 1 relay output 0 10 VDC analogue input 0 10 VDC analogue output RS 485 Modbus RTU The mcr MMS ...

Page 10: ...orized until the ALARM RESET button is pressed on the Power and Control Panel front door The memory functionality maintains the control actuator fault data as required until the alarm is reset Relay outputs OUT feature status readings on orange LED indicators If a LED indicator is on the respective output is active The output logic can be customized by rewiring the output terminals each SPDT relay...

Page 11: ...l the operation of individual modules Data exchange is initiated by a module with MASTER authorization SLAVE modules respond to its inquiry SLAVE modules have unique addresses set with a microswitch The data exchange protocol between MASTER and SLAVEs is similar to the MODBUS protocol The modules are interconnected with the HBUS rail at the bottom of the housing Digital inputs IN are optically iso...

Page 12: ...to the V and V terminals Digital inputs IN are optically isolated and allow reading 24 VDC 24VAC signals at 50 60Hz Additionally 2 digital inputs also support fast signals with 24 VDC 24VAC parameters up to 2kHz Analog inputs IN can be configured to read signals from temperature sensors PTC NTC Pt 1000 0 20mA and 4 20mA current signals and 0 5 VDC and 0 10 VDC voltage signals Digital relay outputs...

Page 13: ... mains supply voltage is lost the 24 VDC systems can be fed from the battery banks connected to the Power Supply Unit The Power Supply Unit feature a four level battery charging current control The battery charging current setting is as shown in the Power Supply Unit manual and adapted to the battery capacity This provides for optimized battery operating parameters and maximum battery service life...

Page 14: ...ctor arrangement permits automatic control over the motor rpm speed by changing the pole pair number Y YY Independent winding two speed This contactor arrangements provides rpm speed control for the motors with double independent windings e g double star Reversing connections this contactor arrangement enables reversing the rotation direction of a fan by swapping the order of phases in all of abov...

Page 15: ... garage rooms or variable controlled by 0 10 V or 4 20 mA analogue control outputs of various transducers used e g for pressure or temperature monitoring An inverter in a fan starting system greatly reduces the starting current to ca 2 In and the installation costs In an installation with high power fans wiring based on 4 wire cables instead of 7 wire cables will greatly reduce the smoke venting s...

Page 16: ...RE DETECTION MODULE The mcr OMEGA pro Power and Control Panel can be equipped with the mcr 0204 Fire Detection Module This device has a single detection circuit to which up to 10 conventional detectors and manual smoke vent buttons can be connected The Fire Detection Module is an optimum choice for fire detection in small areas e g garage rooms staircases etc without a need for an extensive fire a...

Page 17: ... line 10 15 Monitored signalling lines 20 16 Signalling line components Sound sound and light alarms warning display panels 17 Outputs for manual smoke venting controls Yes depending on building specifications 18 Outputs for manual air venting controls Yes depending on building specifications 19 Outputs for control actuators Yes depending on building specifications 20 No and type of control actuat...

Page 18: ...nfrastructure dated 12 03 2009 ref Dz U 75 690 as amended All electrical connections shall be made exactly as shown in the electrical wiring diagram enclosed with this Power and Control Panel be made by personnel with relevant qualifications which have been certified as required by current laws be made with a selection of cables and conductors and their fire resistance classes that meet the electr...

Page 19: ...g closing Double action electric actuator e g BELIMO type BE NO For MERCOR brand dampers only Fig 15 Wiring diagram electric actuator NO Return spring actuator e g BELIMO type BF BFG BFL BFN actuator driven opening NC Fig 16 Return spring actuator wiring diagram actuator opening Double action electric actuator e g BELIMO type BE NC For MERCOR brand dampers only Fig 17 Wiring diagram electric actua...

Page 20: ...urn spring actuators spring closing NO or NC CAUTION Connect all S1 and S2 contacts in parallel Connect all S4 and S5 contacts in series Return spring actuators e g BELIMO type BF BFG BFL or BFN actuator driven opening movement NC Fig 19 Wiring diagram return spring actuators actuator opening NC CAUTION Connect all S1 and S3 contacts in parallel Connect all S4 and S6 contacts in series Cabinet Cab...

Page 21: ...S1 and S2 contacts in parallel Connect all S4 and S5 contacts in series If the damper actuators are installed in the reverse orientation or other actuator types are used connect the limit switches as follows In the monitoring mode the limit switch contacts are open and the MMS module input LEDs are green In the alarm mode the limit switch contacts are closed and the MMS module input LEDs are red T...

Page 22: ...switches Here the limit switches shall be connected as for the actuators with electromagnetic release units The closed damper limit switch alarm position shall be closed in the alarm position whereas the open damper limit switch monitoring position shall be open in the monitoring position CONNECTIONS OF FIRE ALARM SYSTEM SIGNALS The mcr OMEGA pro requires connection with the fire alarm system via ...

Page 23: ...g limit switches w o or w spring action Fire alarm comfort PH0 YnTKSY 2x2x0 8 Duct smoke detector Fire alarm PH90 HTKSH 3x2x1 Smoke detector e g YT102 Detection PH0 YnTKSY 1x2x0 8 Manual smoke venting control Fire alarm PH90 HTKSH 4x2x0 8 CO LPG detectors Comfort PH0 LiYY YDY 5x1 5 2 Warning display panels Comfort PH0 OMY YDY 3x1 5 2 FAS output Fire Fire alarm PH90 HTKSH 1x2x0 8 FAS output Reset P...

Page 24: ...o fire protection requirements and user requirements The table below lists the operating status indications for the Power and Control Panel Table 3 Operating status readings of the P C Panel LED indicators LED Description Monitoring The Power and Control Panel power is online Fault P C Panel or any of connected devices fault Alarm Fire Alarm status fire alarm algorithm active Test Testing of an al...

Page 25: ... also according to their delay times The exact specification of the fire algorithms is available in the operating logic algorithm specification enclosed with the Power and Control Panel The yellow FAULT LED will flash during the test Testing is stopped by resetting the TEST switch again Once a test has been stopped the Power and Control Panel will revert to the monitoring mode and switch all teste...

Page 26: ...RCOR S A grants 12 months of quality warranty for the equipment from the date of purchase unless the sales contract states otherwise 2 If physical defects of equipment are found during the warranty period MERCOR S A undertakes to remove them in 21 days from serving the written warranty claim with the proof of purchase or sales contract subject to Item 6 3 MERCOR S A has the right to extend the tim...

Page 27: ...y mail at the following address MERCOR S A ul Grzegorza z Sanoka 2 80 408 Gdańsk Poland 9 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance according to the Technical Manual Servicing and Maintenance 10 This warranty shall be made immediately void and null if The buyer warranty beneficiary modifies the product design w...

Page 28: ...A pro Power and Control Panel MERCOR S A The company reserves the right to modify and amend this document without notice 28 28 ul Grzegorza z Sanoka 2 80 408 Gdańsk Poland tel 58 341 42 45 tel fax 58 341 39 85 ...

Reviews: