ALARM RESET
The fire alarm is reset by pressing and holding the ALARM RESET button of the Power and Control Panel
for 5 seconds. If the fire alarm inputs receive no fire alarms from any fire protection zone, the alarm will be
reset. The alarm can also be reset remotely via a dry contact output from the fire alarm system control
panel to the dedicated RESET input of the Power and Control Panel. The dry contact input must be made
for at least 5 seconds and then open to reset the alarm.
END OF SERVICE LIFE (FOR ELECTRICAL EQUIPMENT)
At its end of service life, this product becomes hazardous waste which, once
dismantled, must be handed over to the nearest licensed WEEE (waste electrical and
electronic equipment) collection point. Proper disposal of WEEE (waste electrical and
electronic equipment) contributes to avoidance of harmful effects of improper
landfilling and processing of WEEE on human health and the environment.
7.
TESTING
____________________________________________________________________
The mcr OMEGA pro features a function of testing the fire algorithms. Inside the Power and Control
Panel are TEST switches, each for one fire algorithm programmed. The Power and Control Panel must be
in the monitoring mode to test a fire algorithm. Start the test by operating the TEST switch of choice and
monitor the operation of the controller and the interfaced equipment. Depending on the fire algorithm being
tested, its assigned dampers, fans, and output devices will be operated, also according to their delay times.
The exact specification of the fire algorithms is available in the operating logic algorithm specification
enclosed with the Power and Control Panel. The yellow FAULT LED will flash during the test. Testing is
stopped by resetting the TEST switch again. Once a test has been stopped, the Power and Control Panel
will revert to the monitoring mode and switch all tested equipment and devices to the monitoring mode. If
the Power and Control Panel is interfaced with several FAS alarm outputs, each with a TEST button, the
test alarm procedure shall be carried out for each FAS alarm output.
8.
TRANSPORT AND STORAGE
____________________________________________
Each mcr OMEGA pro Power and Control Panel is packed separately. The product is supplied in a
cardboard box and protected against damage in transport. If the product is relatively large, the cardboard
box packaging is supplied fastened to a wooden pallet.
The Power and Control Panel can be transported on any vehicle if protected against mechanical damage,
temperatures below -
20°C and above +80°C and RH > 93% at +40°C. When on a transport vehicle, the
Power and Control Panel shall rest on its base plate (the back of the Panel). NEVER rest the Power and
Control Panel on its LED indicators or controls, i.e. the front/door side. Visually inspect the product for
damage after transport and unloading. The battery banks are disconnected for shipping of the Power and
Control Panel to prevent their drainage.
Keep the Power and Control Panel sheltered indoor at temperatures from 0°C and 40°C and RH < 80% at
35 °C, and away from volatile Sulphur compounds, acid vapors and alkaline vapors. Protect the Power
and Control Panel from direct UV rays (i.e. direct sunlight) and heating equipment. Keep the product
isolated from the ground/floor, if possible.