![mercor mcr OMEGA pro Technical Manual Download Page 12](http://html.mh-extra.com/html/mercor/mcr-omega-pro/mcr-omega-pro_technical-manual_1772917012.webp)
mcr OMEGA pro
Power and Control Panel
„MERCOR” S.A. –
The company reserves the right to modify and amend this document without notice.
12/28
3.6.3.
OPTIONAL MONITORING AND CONTROL MODULES
EVCO C-pro
In mcr OMEGA pro units it is possible to install EVCO C-pro 3 PLC devices in two versions: kilo +
and node kilo +. According to the driver version, they have:
9 or 13 digital inputs
9 or 10 analog inputs
9 or 11 digital outputs
6 analog outputs
RS485, CAN, Ethernet/BACnet
communication ports
Depending on the version, EVCO
controllers may have a display with
signaling of the I / O status. The mcr
MMS modules are powered by 24 VAC
/ DC connected to the V ~ + and V ~ - terminals.
Digital
inputs
(IN)
are optically isolated and allow reading 24 VDC / 24VAC signals at 50 / 60Hz.
Additionally 2 digital inputs also support fast signals with 24 VDC / 24VAC parameters up to 2kHz.
Analog inputs (IN)
can be configured to read signals from temperature sensors (PTC / NTC / Pt 1000),
0-20mA and 4-20mA current signals and 0-5 VDC and 0-10 VDC voltage signals.
Digital (relay) outputs (OUT)
can be customized by wiring the output terminals because each output has
three changeover contact terminals. The load capacity of a single output is a maximum 3A at a maximum
voltage of 250V AC. In the event of control from these solid state relay outputs, the load capacity of a single
output drops to 0.6A at 24VAC / DC.
Analog outputs (OUT)
can be configured as 0-10V voltage output, PWM output and 0-20mA/4-20mA