5.4. Accesories  ___________________________________________________________________  

 

Type SW bottom feet 

made of galvanized steel sheet. Powder-coated in standard, or galvanized on custom order. The bottom 
feet are intended for horizontal installation of the fan [horizontal orientation of the fan axis]. Fasten the feet 
to the fan housing flange with M8 or  M10 bolts, depending on the equipment size.  Note that the motor 
base must be level in the horizontal plane once the fan has been set in place. The openings in the bottom 
shelf of each feet allow tightening of vibration dampers. 
Do not use type SW bottom feet for installation in the vertical orientation.  

Type SW bottom foot 

 

Fan - Type 

Type 

[mm] 

[mm] 

[mm] 

[mm] 

[mm] 

[mm] 

[kg] 

mcr Monsun 35 

SW-35 

305 

245 

50 

12.5 

260 

344 

1.1 

mcr Monsun 40 

SW-40 

300 

240 

50 

12.5 

280 

444 

0.9 

mcr Monsun 45 

SW-45 

320 

260 

50 

12.5 

320 

444 

1.1 

mcr Monsun 50 

SW-50 

400 

320 

50 

12.5 

350 

544 

1.4 

mcr Monsun 56 

SW-56 

450 

370 

50 

12.5 

375 

644 

1.7 

mcr Monsun 63 

SW-63 

500 

420 

50 

12.5 

425 

544 

2.1 

mcr Monsun 71 

SW-71 

550 

470 

50 

12.5 

475 

694 

2.4 

mcr Monsun 80 

SW-80 

650 

570 

50 

12.5 

525 

694 

3.1 

mcr Monsun 90 

SW-90 

700 

620 

60 

12.5 

575 

834 

3.4 

mcr Monsun 100 

SW-100 

780 

670 

70 

12.5 

650 

924 

10.2 

mcr Monsun 112 

SW-112 

900 

780 

75 

18 

710 

1065 

15,5 

mcr Monsun 125 

SW-125 

1000 

880 

75 

18 

775 

1065 

17,5 

 

Type KD flexible joint 

features  a laminar design;  it is terminated with a flange with the holes sized and spaced as on the fan 
housing flange. The special fiberglass silicate textile ensure durability at 400ºC for 120 min.

 

Type KD flexible joint is used to eliminate the vibrations transmitted from the fan to the ventilation system. 
It acts as a vibration damper. It is also used to compensate for thermal elongation. The fan integrated in a 
ventilation system should feature the flexible joint on the suction and pressure sides.

 

Type KD flexible joint 

 

 

Fan - Type 

Type 

[mm] 

~A 

[mm] 

[mm] 

[mm] 

C  

nxd 

[mm] 

[kg] 

mcr Monsun 35 

KD-35 

355 

425 

395 

150 

45 

8x9.6 

1.1 

mcr Monsun 40 

KD-40 

400 

470 

438 

150 

30 

12x9.6 

1.3 

mcr Monsun 45 

KD-45 

450 

520 

487 

150 

30 

12x9.6 

1.4 

mcr Monsun 50 

KD-50 

500 

570 

541 

150 

30 

12x9.6 

1.6 

mcr Monsun 56 

KD-56 

560 

640 

605 

150 

22.5  16x10.5 

1.8 

mcr Monsun 63 

KD-63 

630 

710 

674 

200 

22.5  16x10.5 

2.0 

mcr Monsun 71 

KD-71 

710 

790 

751 

200 

22.5  16x10.5 

2.3 

mcr Monsun 80 

KD-80 

800 

875 

837 

200 

15 

24x10.5 

2.6 

mcr Monsun 90 

KD-90 

900 

975 

934 

200 

15 

24x10.5 

2.9 

mcr Monsun 100 

KD-100 

1000 

1080 

1043 

200 

15 

24x10.5 

3.2 

mcr Monsun 112 

KD-112 

1120 

1240 

1190 

200 

15 

24x14 

3,5 

mcr Monsun 125 

KD-125 

1250 

1370 

1320 

200 

15 

24x14 

3,8 

 

 

 

Summary of Contents for mcr Monsun F200

Page 1: ...ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 48 58 341 39 85 TECHNICAL MANUAL Smoke exhaust axial fan mcr Monsun Version Monsun 19 06 27 3 FIRE VENTILATION SYSTEMS ...

Page 2: ...INCIPLE 5 5 1 Design 5 5 2 Function 6 5 3 Dimensions 6 5 4 Accessories 6 6 IDENTIFICATION MARKING 11 7 INSTALLATION 11 7 1 Pre assembly inspection 11 7 2 Location and assembly 11 7 3 Electrical connections 13 7 4 Commissioning 14 8 TRANSPORT STORAGE CONDITIONS 14 9 SAFETY MANUAL 16 10 MAINTENANCE SERVICING 16 11 WARRANTY TERMS CONDITIONS 16 FAN MEASUREMENT REPORT 17 ...

Page 3: ... This equipment has been designed and manufactured according to the following standards PN EN 12101 3 2004 Smoke and heat control systems Part 3 Specification for powered smoke and heat exhaust fans PN EN ISO 12100 1 2005 Safety of machinery Basic concepts general principles for design Part 1 Basic terminology methodology PN EN ISO 12100 2 2005 Safety of machinery Basic concepts general principles...

Page 4: ...ates evacuation of persons from the area on fire protect the building structure and its furnishing from high temperature facilitate fire fighting and inhibit spreading of fire to adjacent fire zones The available versions include single functional with single speed motors two functional i e for general and fire ventilation and with two speed motors The fans can be installed indoors or outdoors on ...

Page 5: ... end intended for connection with the ventilation system Inside of the enclosure the motor is located and supported by the motor base The rotor is set directly on the motor shaft neck At the rotor intake and in line with its centreline is an aerodynamic cone which improves the flow performance The fan can also feature an air stator type KP located inside of the ventilator casing on the rotor end T...

Page 6: ...s ___________________________________________________________________ mcr Monsun smoke exhaust axial fans Table of dimensions Fan Type D mm A mm L mm B mm C nxd mm mcr Monsun 35 355 425 400 395 45 8x9 6 mcr Monsun 40 400 470 500 438 30 12x9 6 mcr Monsun 45 450 520 500 487 30 12x9 6 mcr Monsun 50 500 570 600 541 30 12x9 6 mcr Monsun 56 560 640 700 605 22 5 16x10 5 mcr Monsun 63 630 710 600 674 22 5...

Page 7: ...nsun 100 SW 100 780 670 70 12 5 650 924 10 2 mcr Monsun 112 SW 112 900 780 75 18 710 1065 15 5 mcr Monsun 125 SW 125 1000 880 75 18 775 1065 17 5 Type KD flexible joint features a laminar design it is terminated with a flange with the holes sized and spaced as on the fan housing flange The special fiberglass silicate textile ensure durability at 400ºC for 120 min Type KD flexible joint is used to ...

Page 8: ...56 1370 1320 15 24x14 9 1 Type SO safety mesh made of galvanized steel sheet and galvanized wire mesh Powder coated in standard or galvanized on custom order The fitting protects the fan from ingress of foreign bodies The product is designed for direct mounting on the fan housing flange with free flow suction and forcing Periodically check that the safety mesh is clean and clean it when necessary ...

Page 9: ...tal and KS V vertical the damper body is made of galvanized steel sheet Powder coated in standard or galvanized on custom order The damper blade is made of aluminium sheet Type KS and KS V automatic non return dampers are installed to prevent air circulation and heat losses when the fan is in standstill The damper needs to be truly level to operate correctly Automatic non return damper type KS KS ...

Page 10: ... 155 mcr Monsun 100 TH 100 1006 1250 560 1043 1400 15 24xM10 170 mcr Monsun 112 TH 112 1126 1370 480 1190 1400 15 24xM12 200 mcr Monsun 125 TH 125 1256 1500 480 1320 1400 15 24xM12 250 Type DS nozzle with safety mesh the nozzle with safety mesh is made of galvanized steel sheet The product is designed to equalize the air stream entering the fan Dysza ssawna osiatkowana DS wentylator typ typ D mm A...

Page 11: ...r Monsun 125 WO 125 1250 1370 1320 24x14 co 15 1D 3D Type WS service switch Designed to cut off electric power from the fan when inspection or maintenance work is necessary Each service switch features an auxiliary contact which indicates the power off position Install the service switch at a minimum distance of 9 cm from the fan body i e on a console attached to e g the casing flange The 3 pole s...

Page 12: ...e vibration dampers are bolted to type SW bottom feet or type PP vertical support holders Type AM BM vibration damper wentylator typ typ Amm B mm C mm E mm F mm M S mm d mm m kg mcr Monsun 35 AM 35 136 80 108 85 135 M12 7 10 0 6 mcr Monsun 40 AM 40 mcr Monsun 45 AM 45 mcr Monsun 50 AM 50 mcr Monsun 56 AM 56 mcr Monsun 63 AM 63 mcr Monsun 71 AM 71 mcr Monsun 80 AM 80 mcr Monsun 90 AM 90 mcr Monsun ...

Page 13: ...ducting When installing the smoke exhaust fan vertically on a baseplate put the equipment on type PP vertical support It is recommended to bolt vibration dampers to the support in order to reduce the vibration from the fan operation When installing the smoke exhaust fan horizontally fasten type SW bottom feet to the fan housing flange with bolts Set the finished assembly on previously prepared vib...

Page 14: ...omatic non return damper must be levelled for good performance Install a straight duct section with a min length of 2 5xD on the fan pressure side Seal the system joints with silicone or other high temperature compound Example vertical installation of the smoke exhaust fan Notes The support structure must carry the load of the fan weight Counterflanges Seal with HT silicone Vibration damper Vibrat...

Page 15: ...The electrical power supply from the control cabinet to the fan power junction box must guarantee uninterrupted operation in the case of a fire This can be achieved with high temperature resistant wiring or with protective tubing and proper safe routing of the electrical power system No external service maintenance switches are to used which is to prevent inadvertent shutdown of the smoke exhaust ...

Page 16: ...sense of rotation against the direction arrow on the enclosure 8 TRANSPORT STORAGE CONDITIONS __________________________ During transport and storage the mcr Monsun smoke exhaust fans are placed on pallets Do not topple or throw the packaging during loading and transport The smoke exhaust fans can be handled and shipped on any means of transport provided that they are secured against weather and e...

Page 17: ... the Ministry of the Interior and Administration of 7 June 2010 on the fire protection of buildings other structures and areas Polish Journal of Laws Year 2010 No 109 Item 719 Do these recommended actions in the inspection intervals Check the electrical connections especially for all mechanical damage Check the equipment casing especially for all mechanical damage Check for any obstructions to pro...

Page 18: ...tual condition and extent of damage shall be considered at the site of their origin as the action of torrential rain Hurricane is understood as any wind with a minimum speed of 17 5 m s and damage shall be recognised as caused by hurricanes if the effects of such weather phenomenon has been found in the direct vicinity of the damaged property Damage due to failure to immediately report any defect ...

Page 19: ...f the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems Ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than in 8 weeks from the date of equipment purchase equivalent to the date of the VAT sales invoice THE EQUIPMENT WARRANTY...