16
/
19
Electrical wiring connections must only be made by electricians with valid licenses.
Connections for 230/400V motors
Connections for 400/690V motors
7.4. Commissioning____________________________________________________________
Before commissioning your installed smoke exhaust fan, do the following:
Check that the smoke exhaust fan is properly and firmly fastened.
Check all seals for tightness.
Check that all electrical wiring is properly and firmly connected.
Check that the phase connection sequence and PE/neutral wiring is properly connected.
Check that the smoke exhaust fan and its connected ducting are free of foreign bodies.
Check that all protective/safety components have been installed.
If the checks are positive, start the fan and do a functional test.
When starting the smoke exhaust fan, verify the motor sense of rotation against the direction arrow
on the enclosure.
8. TRANSPORT & STORAGE CONDITIONS __________________________
During transport and storage, the mcr Monsun smoke exhaust fans are placed on pallets. Do not topple
or throw the packaging during loading and transport. The smoke exhaust fans can be handled and shipped
on any means of transport, provided that they are secured against weather and elements. The smoke
exhaust fans on transport vehicles must be secured against shifting. Visually inspect each piece of
equipment following transport and handling.
Store in sheltered rooms, where:
there is no exposure to dust particulates, gases, corrosive vapours and other aggressive
chemical emissions detrimental to insulation parts and structural components of the ventilator
and/or its motor;
the maximum relative humidity is 80% at +20°C;
the ambient temperature does not exceed the range of -20ºC to + 40ºC;
no vibrations are present.
Type WS service switch
Type WW service switch
console
Ventilator flange
Bolted joint
Min.
9
cm