12
A1td
Alarm 1 Time Delay: Select
0FF
or
1 to 8000
seconds. Factory default is
0FF
.
0FF
Alarm function will operate when triggered at
programmed Alarm Set Point.
1-8000
Alarm function will only operate once the
programmed time has elapsed after the
alarm was triggered by the Alarm Set Point.
AL2
Alarm 2 function: Select
0FF
,
Lo
,
Hi
,
HiLo
,
SF
,
0t
, or
SF0t
. Factory default is
Lo
.
0FF
Alarm 2 is disabled. No Alarm 2 menu items
appear in the Secondary or Secure menus.
Lo
Low Alarm Only.
A2Lo
appears in the
Secondary Menu.
Hi
High Alarm Only.
A2Hi
appears in the
Secondary Menu.
HiLo
High and Low Alarms. Both
A2Lo
and
A2Hi
appear in the Secondary Menu, and share
the same Alarm 2 Relay output.
SF
Seal Failure ONLY will trigger Alarm.
0t
Over Temperature Failure ONLY will trigger
Alarm
SF0t
Both Seal Failure and Over Temperature
Failure will trigger Alarm.
With the Alarm Function settings on
0FF
,
SF
,
0t
,
SF0t
certain alarm related menu items will disappear as those
menu items do not apply.
A2t
Alarm 2 Type: Select
AbS
or
dE
. Factory default is
AbS
.
AbS
Absolute Alarm that may be set anywhere
within the values of
SCAL
and
SCAH
and is
independent of
SP1H
.
dE
Deviation Alarm that may be set as an offset
from
SP1H
. As
SP1H
is changed the Alarm Point
will track with
SP1H
.
A2rE
Alarm 2 Reset: Select
0n0F
or
HoLd
Factory default
is
0n0F
.
0n0F
Automatic Reset.
HoLd
Manual Reset. Reset (acknowledge) by
simultaneously pressing the
INDEX and
DOWN ARROW keys for 5 seconds.
A2Pi
Alarm 2 Power Interrupt: Select
0n
or
0FF
. Factory
default is
0FF
.
0n
Alarm Power Interrupt is
On
.
0FF
Alarm Power Interrupt is
OFF
.
A2iH
Alarm 2 Inhibit: Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Inhibit is
On
. Alarm action is suspended
until the process value first enters a non-
alarm condition.
0FF
Alarm Inhibit is
OFF
.
A2St
Alarm 2 Output State: Select
CL0S
or
0PEn
. Factory
default is
CL0S
.
CL0S
Closes Contacts at Alarm Set Point.
0PEn
Opens Contacts at Alarm Set Point.
A2LP
Alarm 2 Lamp: Select
0 on
or
0oFF
. Factory
default is 0 on.
0 on
Alarm Lamp is
ON
when alarm contact is
closed.
0oFF
Alarm Lamp is
OFF
when alarm contact is
closed.
A2td
Alarm 2 time Delay: Select
0FF
or
1 to 8000
seconds.
Factory default is
0FF
.
0FF
Alarm function will operate when triggered at
programmed Alarm Set Point.
1-8000
Alarm function will only operate once the
programmed time has elapsed after the
alarm was triggered by the Alarm Set Point.
FiLt
Digital Filter: Select
0FF
or
1
to
99
. In some cases
the time constant of the sensor, or noise could
cause the display to jump enough to be unreadable.
If this value is set too high, controllability will suffer.
Factory default is
3
.
P0H
(Analog Retransmission Output, see page 8)
Process Output High: Select from any value greater
than
P0L
to 9999 counts. Factory default is
23.1
.
P0L
(Analogw Retransmission Output, see page 8)
Process Output Low: Select -1999 counts to any
value less than
P0H
. Factory default is
0.0
.
The remaining menu items appear if the corresponding
option was purchased with the control.
L0rE
(Option 232 and 485, Serial Communications)
Local / Remote Status: Select
L0C
or
rE
. Factory
default is
rE
.
L0C
The host computer is advised not to send
remote commands. Any write commands
sent to the controls will be rejected.
rE
The host computer is allowed to send
write commands. If the control is not
addressed within the time set in the
nAt
(No
Activity Timer, see Secure Menu) the
CHEC
L0rE
error message will be displayed.
Addr
(Option 232 or 485, Serial Communications)
Control Address: Set from
1
to
99
. This number
(hexadecimal, base 16) must match the address
number used by the host computer. Factory default
is 32.
bAUd
(Option 232 or 485, Serial Communications)
Communication Baud Rate: Select
300
,
1200
,
2400
,
4800
,
9600
, or
19200
. This number must match the
baud rate used by the host computer. Factory
default is
9600
.
nAt
(Option 232 or 485, Serial Communications) No
Activity Timer: Set from
0FF
or
1
to
99
minutes.
Factory default is
0FF
.
1-99
Maximum time between host computer
accesses. If timer counts to 0,
CHEC
/
L0rE
will
be displayed.
0FF
No Activity Timer function is disabled.
Stor
(Option 232 or 485, Serial Communications) Store
to EEPROM: Select
Yes
or
no
.
YES
Menu item changes made through serial
communications are stored directly to
EEPROM.
no
Menu item changes made through serial
communications are stored in RAM.
(Settings are lost if power is disconnected)