11
PrSt
Pump Run Time Reset: Select
0n
or
0FF
. Selecting
0n will allow Pump Run Time to be reset in the
Secondary menu while an
0FF
selection will not
allow Pump Run Time to be reset.
SPH
Set Point High: Select from the highest input range
value to
SPL
value. This will set the maximum
SP1H
or
SP2H
value that can be entered. The
value for
SP1H
or
SP2H
will stop moving when this
value is reached. Factory Default is
23.1
.
SPL
Set Point Low: Select from the lowest input range
value to
SPH
value. This will set the minimum
SP1L
or SP2L value that can be entered. The value
for
SP1L
or
SP2L
will stop moving when this value
is reached. Factory Default is
0.0
.
S2ti
Setpoint 2 Time Delay. Select from 0 to 60 seconds.
Factory default is 0. This will set a time delay for
setpoint 2 on power up of the MPC that will assure
that setpoint 2 will not be brought into use until after
the programmed time delay.
PEA
The Peak feature stores the highest input the
control has measured since the last reset or Power
On. At Power On
PEA
is reset to the present input.
To manually reset the value
PEA
must be in the
lower display. Press the ENTER key to reset.
PEA
will be reset and display the present input
value.
UAL
The Valley feature stores the lowest input the
Controller has measured since the last reset or
Power On. At Power On
UAL
is reset to the present
input. To manually reset the value
UAL
must be in
the lower display. Press the ENTER key.
UAL
will be reset and display the present input value.
ALARM TYPE AND ACTION
Caution: In any critical application where failure could
cause expensive product loss or endanger personal
safety, a redundant limit controller is required.
When setting the alarm value for a deviation alarm (
A1t
=
dE
or
A2t
=
dE
), set the difference in value from the Set
Point (
SP1H
) desired.
Since the input for the MPC is driven from a transmitter,
the input display can be programmed in different ways.
Regardless of the position of the decimal point, a change
of one in the right most digit is referred to as a count.
For example, if there were no decimal point selected, a
change from 235 to 236 is a change of one count. If the
decimal point were selected at
0.0
, a change of 23.5 to
23.6 is a change of one count.
When setting up an alarm for deviation the deviation is
set in counts. For example if a low alarm is required to
be 5 counts below the
SP1H
, then set
A#Lo
to -5. If a high
alarm is required 20 counts above the
SP1H
, then set
A#Hi
to +20. If
SP1H
is changed, the alarm will continue to hold
the same relationship as originally set.
When Alarm Power Interrupt,
A#P
, is programmed ON
and Alarm Reset,
A#rE
, is programmed for Hold, the
alarm will automatically reset upon a power failure and
subsequent restoration if no alarm condition is present.
If Alarm Inhibit,
A#iH
is selected ON, an alarm condition
is suspended upon power up until the process value
passes through the alarm set point once. Alarm inhibit
can be restored as if a power up took place by pressing
both the
INDEX and ENTER keys for 5 seconds.
The following menu items apply only to the alarms.
AL1
Alarm 1 function: Select
0FF
,
Lo
,
Hi
, or
HiLo
. Factory
default is
Hi
.
0FF
Alarm 1 is disabled. No Alarm 1 menu items
appear in the Secondary or Secure menus.
Lo
Low Alarm Only.
A1Lo
appears in the Secondary
Menu.
Hi
High Alarm Only.
A1Hi
appears in the
Secondary Menu.
HiLo
High and Low Alarms. Both
A1Lo
and
A1Hi
appear in the Secondary Menu, and share the
same Alarm 1 Relay output.
SF
Seal Failure ONLY will trigger Alarm.
0t
Over Temperature Failure ONLY will trigger
Alarm
SF0t
Both Seal Failure and Over Temperature
Failure will trigger Alarm.
With the Alarm Function settings on
0FF
,
SF
,
0t
,
SF0t
certain alarm related menu items will disappear as those
menu items do not apply.
A1t
Alarm 1 Type: Select
AbS
or
dE
. Factory default is
AbS
.
AbS
Absolute Alarm that may be set anywhere
within the values of
SCAL
and
SCAH
and is
independent of
SP1H
.
dE
Deviation Alarm that may be set as an offset
from
SP1H
. As
SP1H
is changed the Alarm Point
will track with
SP1H
.
A1rE
Alarm 1 Reset: Select
0n0F
or
HoLd
. Factory default
is
0n0F
.
0n0F
Automatic Reset.
HoLd
Manual Reset. Reset (acknowledge) by
simultaneously pressing the
INDEX and
DOWN ARROW keys for 5 seconds.
A1Pi
Alarm 1 Power Interrupt: Select
0n
or
0FF
. Factory
default is
0FF
.
0n
Alarm Power Interrupt is
0n
.
0FF
Alarm Power Interrupt is
0FF
.
A1iH
Alarm 1 Inhibit: Select
0n
or
0FF
. Factory default is
0FF
.
0n
Alarm Inhibit is
0n
. Alarm action is suspended
until the process value first enters a non-alarm
condition.
0FF
Alarm Inhibit is
0FF
.
A1St
Alarm 1 Output State: Select
CL0S
or
0PEn
. Factory
default is
CL0S
.
CL0S
Closes Contacts at Alarm Set Point.
0PEn
Opens Contacts at Alarm Set Point.
A1LP
Alarm 1 Lamp: Select
0 on
or
0oFF
. Factory default is
0 on
.
0 on
Alarm Lamp is
ON
when alarm contact is
closed.
0oFF
Alarm Lamp is
OFF
when alarm contact is
closed.
IF INHIBIT IS ON AND A POWER
FAILURE OCCURS DURING A
HIGH ALARM, RESTORATION OF POWER WILL NOT
CAUSE THE ALARM TO OCCUR IF THE PROCESS
VALUE DOES NOT FIRST DROP BELOW THE HIGH
ALARM SETTING. DO NOT USE THE ALARM INHIBIT
FEATURE IF A HAZARD IS CREATED BY THIS
ACTION. BE SURE TO TEST ALL COMBINATIONS OF
HIGH AND LOW ALARM INHIBIT ACTIONS BEFORE
PLACING CONTROL INTO OPERATION.
WARNING
When setting an alarm value for an
absolute alarm (
A1t
=
AbS
or
A2t
=
AbS
), simply set the value at which
the alarm is to occur.
CAUTION
www.
.com
1.800.561.8187