background image

Semi-Automatic Control with Manual Reset 

Prefixed  by  DR,  DRF,  DRH,  DRE,  DRW  -  with  suffix  -L  or  -U.  Example: Type  DR-

21-2U. A single adjustment sets the operating point for automatic operation. A push-

button reset must be operated manually to restore the circuit to the original position 

after  automatic  operation.  Example: Type  DA-21-2L.  Circuit  will  open  automatically 

on a pressure rise to the pressure indicated by the pointer on the scale. No matter 

how much the pressure drops, the circuit will not re-close until the reset button has 

been  operated.  Suffix  -L  denotes  control  will  operate  automatically  on  an  increase 

in  pressure.  Suffix  -U  denotes  control  will  operate  automatically  on  a  decrease  in 

pressure.

Manual Lock Type Reset Control

Operates automatically on a decrease of pressure with provision for man-ual reset 

when pressure is below set point. Prefixed by DL, DLW, DLE, DLH. A single adjustment 

sets the low pressure operating point of the control at any value on the scale range. 

The control will operate automati-cally at the set point only on a drop in pressure. The 

lock-type feature per-mits the circuit to be reset and locked in position when pressures 

are below control setting. The lock remains in effect until the pressure has risen to a 

value above the control setting. Lock then releases and the circuit is held in the reset 

position due to the pressure rise. It will remain in the reset position until it is called on 

to again operate automatically on a pressure drop to the select-ed setting.

Two-Stage Pressure Controls - Series D-400

Types  DA,  DAW,  DAH,  DAE  -  with  suffixes  421,  423,  431,  433,  etc.,  followed  by 

specification numbers 4122, 4123, 4129, 4132.

This  series  incorporates  two  single  pole,  single  throw  magnetic  mercury  switches, 

actuated by the same Bourdon tube. The operating point of each switch is adjustable 

through an outside adjustment.

The change in pressure which opens and closes each switch at its respective setting 

is the switch’s fixed differential. The pressure represented by the difference between 

the two adjustment pointers is the pressure “spread” between operation of the two 

switches. Upper pointer “U” indicates the operating point of the HIGH pressure circuit. 

Lower point “L” indicates the operating point of the low pressure circuit.

General  Watertight  or  Weather-Resistant  Types:

 These  controls  are  prefixed  by 

the letters DAW, DRW, DSW and DLW. They are supplied with flanged case, bottom 

connection only, for surface mounting. Again, install firmly in a level position. Do not 

mount the control by twisting the case; use a wrench on the square part of the 1/4˝ 

bottom pipe connection. Be sure pipe connection is in a vertical position. After cover is 

properly attached, with the name plate on bottom of the cover, sight across the lower 

end of the glass opening in the cover to see that the control is lined up vertically. Do 

not use holes in case bottom for mounting.

Explosion-Proof  Types: 

Install  controls  prefixed  by  the  letters  DAH,  DAHF,  DRH, 

DSH, DAE, DRE, DSE, firmly in a level position by means of mounting lugs attached 

to the control housing. Line up horizontally by sighting across the left and right conduit 

hubs.

Note:

 Series D-30, D-230, D-430, D-530 (i.e., DA-31-3, etc.), when used for steam 

with  operating  ranges  of  35  psi  or  higher,  must  be  siphoned  to  prevent  live  steam 

from entering the Bourdon tube. With high pressure steam in excess of 100 psi, use 

a remote connection. 

Series D-20, D-220, D-420, D-520 (i.e., DA-21-2, etc.), when incorpo-rate an orifice as 

standard in the bottom stem to dampen out surges or pul-sations. 

WIRING

Wire in accordance with local electrical codes or equipment manufacturer’s instructions. 

For general purpose controls, use a short piece of BX between the rigid conduit and 

the control so that it will not be subjected to conduit expan-sion and contraction. Where 

control is directly connected into load circuit, it should be connected into hot side of 

line. For electrical rating, see name-plate attached to control case.

ADJUSTMENTS: How to Set Operating Point Double Adjustment Types - Fully 

Automatic

 

Prefixed by DA, DAF, DAW, DAH, DAHF - provided with double adjustments. Adjust 

the upper pointer “C” to set the HIGH PRESSURE POINT for switch operation. Adjust 

the lower

pointer “U” to set the LOW U PRESSURE POINT. The differ-ence between the HIGH 

and LOW pointers is the operating differential between “on-off” switch operation. 

Single Adjustment Types - Fully Automatic

Prefixed  by  DS,  DSE,  DSF,  DSH  -equipped  with  a  single  adjustment.  The  single 

pointer on the scale sets the pressure where switch operation occurs. Differential is 

fixed (not adjustable). Example setting: Type DS-21-2, range 0-60 psi: circuit opens on 

pressure rise. If pointer is set at 40 psi, the control will operate to OPEN circuit at 40 

psi and RE-CLOSE circuit at the fixed differential of 4 psi.

C

Adjustment

Reset

Single 

adjustment

Switch B high

U

Double adjustment types - Fully automatic

 Semi-automatic control with manual reset

 Manual lock type reset control

Single adjustment types - Fully automatic

Two-stage pressure controls Series 400 

Adjustment

Reset

Upper 

pointer U

Switch A low

Lower 

pointer L

Summary of Contents for D Series

Page 1: ...ght across the two cover screws or check the lower end of the glass opening in the cover to see that the control is lined up horizontal ly On general purpose controls provided with a flange mount by means of the three holes in the flange SPECIFICATIONS Wetted Materials Brass 403 SS or 316 SS Temperature Limit 180 F 82 C Pressure Limit Maximum pressure of the operating range Enclosure rating Genera...

Page 2: ...ing Again install firmly in a level position Do not mount the control by twisting the case use a wrench on the square part of the 1 4 bottom pipe connection Be sure pipe connection is in a vertical position After cover is properly attached with the name plate on bottom of the cover sight across the lower end of the glass opening in the cover to see that the control is lined up vertically Do not us...

Page 3: ...l full scale Minimum Differential listed below Fixed Differenital Single Adjustment Adjustable operating point Differential fixed NOT ADJUSTABLE APPLICATION Bourdon tube Material Adjustable Operating Range psig Range Number DA 31 DA 531 DS 231 Brass Bourdon Tubes 0 30 Hg VAC 10 in Hg VAC 12 1 8 to 15 psig 1 8 to 20 psig 1 to 35 psig 25 in Hg VAC 50 2 to 60 psig 5 to100 psig 5 to 150 psig 10 to 200...

Page 4: ...sitivity For Steam and Other Applications DA 431 DAW 433 DAH 431 1 2 3 3A 4 5 6 7 8 9 27 1 8 to 15 psig 0 to 30 in Hg VAC 10 in VAC 12 psig 1 8 to 20 psig 1 to 35 psig 2 to 60 psig 5 to 100 psig 5 to 150 psig 5 to 200 psig 10 to 300 psig 25 in VAC 50 psig Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass Brass 2 1 2 psig 4 in Hg 2 1 2 psig 2 1 2 psig 3 1 2 psig 5 psig 7 psig 10 5 8 psig ...

Page 5: ...ose Opens 155 1 Circuit 2 Circuit B Closes Open 156 SP DT A One Closes as Other Opens 705 SP DT SP DT B A One Closes as Other Opens Opens 729 SP ST SP DT B A One Closes as Other Opens Opens 804 DP DT B Two Close Two Open 815 B 4P ST Close 2 9 67 816 B 4P ST Open 2 9 67 Consult factory ELECTRICAL RATING CHART Code Circuit Suffix AC Capacity DC Capacity Horsepower 120 V 240 V 440 V 120 V 240 V AC DC...

Page 6: ... HOLES 3 4 CONDUIT CONNECTION BREATHER OPTIONAL MOUNTING HOLES OPTIONAL 3 1 2 88 90 9 7 8 250 83 5 127 4 Ø7 16 11 23 MOUNTING HOLES 7 5 8 193 7 10 13 16 274 7 6 7 8 174 6 10 11 16 271 5 3 4 NPT CONNECTION TYP Explosion proof prefixed by DAH DAHF DRH DSH DSHF Watertight NEMA 2 3 4 Prefixed by DAW DRW DSW DLW Explosion proof prefixed by DAE DLE DRE DSE ...

Page 7: ...__________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ _______________________________________________________________________________________...

Page 8: ...______________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ___________________________________________...

Reviews: