WARNING
DO NOT PROCEED WITH OPERATION OF THIS FIREPLACE
UNLESS BURNER "CYCLES" ON/OFF WITHOUT DELAYS!
CHECKING FOR NORMAL BURNER (S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, light the main burners.
Turn Gas Dial counterclockwise to "ON" then set Thermostat or push Main Burner ON/OFF switch to turn on
burners. Main burner should now light IMMEDIATELY and flame should not "lift" off burner. If there is any delay
in ignition or if flame is "lifting off" burner, turn off burner and carefully check for proper installation of logs/coals,
vent system and proper pilot flame impingement on burner and thermopile. Logs or coals must not block pilot
flame or main burner flame. Vent system must be leak proof.
ATTACHING LPG CONVERSION LABELS AND HIGH ALTITUDE DERATION LABEL
Two printed informational labels are included with the LPG Conversion Kit. Attach these two labels to the rear sur-
face of this insert adjacent to the Serial Number Plate. If you are derating this appliance at a high altitude, also
attach the High Altitude Deration Label, supplied in the Owner’s Manual Packet, to this same surface adjacent to
other labels.
Prior to attaching the labels, fill in all the information that is requested in these labels.
For installations from 610-1370 meters (2000-4500 ft.) the orifice sizes (DMS) for natural and propane gas are
_#46R/#49F_ and _#56R/#3/64”F_, respectively. See data plate for additional information. For high altitude in-
stallations consult the local gas distributor or the authority having jurisdiction for proper rating methods. If the in-
staller must convert the unit to adjust for varying altitudes, the information sticker must be filled out by the installer
and adhered to the appliance at the time of conversion."
«Cet appareil est equipé pour des altitudes compries entre 0 et 2000 pieds (0-610 m) seulement»
This appliance has been converted for use at an altitude of ______________
Orifice size _______________
Manifold Pressure ________________
Input (Btu/h)_______________
Fuel Type _______________________
Date of conversion _________
Converted by _____________________
«Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________
GAS LEAK TEST REQUIREMENT:
It is the responsibility of the installer/service person to assure that
each and every gas connection and supply tubing that are a part of this fireplace are leak proof. The qualified/
certified individual connecting the gas supply line, performing pressure tests or performing any service to this fire-
place is required to perform a THOROUGH LEAK TEST on ALL gas fittings that are a part of this appliance or the
gas supply line connection using soap-water solution or a calibrated combustible gas detector. Failure to perform
this leak test may lead to a house fire and/or an explosion. Mendota is not responsible for any damages due to
an Installer’s failure to conduct a leak test and verify that all connections and supply lines are leak proof.
WARNING: Do not operate appliances with glass front removed, cracked, or broken. Replacement of glass
should be done a licensed or qualified service person.
Note: Consult the local or national installation code(s) to assure that adequate combustion and ventilation air is
available.
WARNING: It is of the utmost importance that the correct burner orifices be installed for both the rear
and front burners.