Installation manual
Outer wall terminals M-WRG-II ES (-P, -PK), M-WRG-II KSR (-1, -2)
- 15 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L A T I O N & H E A T R E C O V E R Y
6.1.3
Attaching the outer wall terminal
►
Remove the three cross-head screws
3.5 x 16 (item 1 in Fig. 9) at the top of
the outer wall terminal.
►
Slide the cover (item 2 in Fig. 9) up
roughly 10 mm. Lift the cover forward
and away from the base plate (item 3
►
Fully coat both 4 mm wide sealing
surfaces (item 4 in Fig. 9) on the
inside with Vaseline.
►
Carefully position the base plate
(item 1 in Fig. 10) correctly on the
ventilation pipes. Be careful not to
damage the seals.
► Use a spirit level to align the base
plate vertically (see item 2 in Fig. 10).
► Use the four screws provided to fix
the base plate (item 3 in Fig. 10).
►
Position the cover (item 1 in Fig. 11)
on the base plate so that the tabs of
the cover (item 2 in Fig. 11) slide into
the guides on the base plate (item 3
► Use the three cross-head screws
3.5 x 16 (item 4 in Fig. 11) to fix the
cover.
► Remove the protective films from the
cover (this does not apply to powder-
coated outer wall terminals).
►
Clean the outer wall terminal (see
chapter 7 on page 18).