Installation

61

Mellanox Technologies

2.7.1 Power Supply Units

The power supplies deliver 2500W at 48V

DC

. The input to each of these power supplies requires 

12A current in order to output 2500W.
For N+N configuration up to half of the PSUs can go down and the system will continue to run.
The power required to run the switch system is equally divided between all of the working PSUs.

2.7.1.1 Extracting and Inserting the PSU

With all of the N+N 2500W power supplies installed, the system is in N +N redundant configura-
tion, half of the PSUs may be extracted without bringing down the system.

To extract a PSU:

 Step 1.

Determine  which AC  connector  on  the  connector  side  of  the  chassis  corresponds  to  the 
defective PSU.

 Step 2.

Remove the power cord from the PSU’s inlet. Note which power cord it is according to the 
AC numbering.

Figure 44: Power Unit AC Inlet Numbering

 Step 3.

On the spine side of the chassis, remove the cover to the PSUs. There are four Phillips head 
screws for the cover plate.

Figure 45: Power Supply Unit

Han-

Latch

 Step 4.

Grasping the handle with one hand, push the black latch release while pulling the handle 
outward. As the PSU unseats, the PSU status indicators will turn off.

 Step 5.

Remove the PSU.

To insert a power supply unit:

A new system would have the PSU already installed so there

Summary of Contents for Switch-IB

Page 1: ...Mellanox Technologies www mellanox com 324 Port EDR InfiniBand Switch IB Series Switch Platform Hardware User Manual PN CS7510 Rev 1 9...

Page 2: ...Doc MLNX 15 4748 324 2 Mellanox Technologies...

Page 3: ...y Warnings 19 2 2 Environmental and Safety Recommendations 23 2 3 Switch Components 24 2 4 Unpacking the Switch System 25 2 4 1 Verifying Crate Condition 25 2 4 2 Opening the Chassis Crate 26 2 5 Phys...

Page 4: ...Chapter 4 Chassis Power Up 88 4 1 System Status After Power Up 88 4 2 Switch Shut Down Procedure 89 Chapter 5 Switch Management Tools 90 5 1 InfiniBand Subnet Manager 91 5 2 Fabric Inspector Diagnost...

Page 5: ...inese 114 H 5 Avertissements de s curit pour l installation French 118 H 6 Installation Sicherheitshinweise German 121 H 7 Advertencias de seguridad de instalaci n Spanish 124 H 8 Russian 127 H 9 Aver...

Page 6: ...Status LED 80 Table 11 Spine Fan Status LED 81 Table 12 Spine to Leaf IB Link Status 81 Table 13 Bad Port LED Configurations 81 Table 14 Spine Side Panel LED Display for Normal Operation 82 Table 15...

Page 7: ...ssis on Spine Side 36 Figure 16 Cage Nut Placement for Cable Holders on Leaf Side 37 Figure 17 Loosening the Leaf Side Shelf Arms 38 Figure 18 Adjusting the Leaf Side Shelf Arms 39 Figure 19 Placing S...

Page 8: ...igure 50 Management Module Numbering 65 Figure 51 Releasing Spine Ejector Handles 66 Figure 52 Intact Spine Signal Connectors 67 Figure 53 Intact Spine Power Pin Holders 67 Figure 54 Spine Module Inse...

Page 9: ...pine Side Panel Display Status Indications 89 Figure 75 Management Module Status Indications for Normal Operation Master 89 Figure 76 Management Module Status Indications for Normal Operation Slave 89...

Page 10: ...r MTDF KIT B 1 4 29 June 2016 Added Section 1 5 Fan Redundancy on page 18 1 3 18 May 2016 Added Section 2 5 2 Required Installation Tools on page 31 Updated Table 5 Chassis Installation Kit Items on p...

Page 11: ...Release Notes For possible hardware issues see the switch support prod uct page This requires a customer support login Look up the relevant Switch IB based switch system series release note file MLNX...

Page 12: ...s BB Switch system type CS Chassis MB Management Board SB Switch IB in leaf or spine module C Data rate 7 EDR InfiniBand D System type 5 director switch EE Number of ports 00 648 ports 10 324 ports 20...

Page 13: ...ires an InfiniBand compliant Subnet Manager running from one of the hosts or the management module of the switch system The initial configuration proce dure should be followed to initialize the switch...

Page 14: ...e on the spine side 1 1 2 Management Module MAC Each management module has a label with its MAC address See Figure 3 for the location of this label Figure 3 Management Module MAC Address Location 1 1...

Page 15: ...side Figure 4 CS7510 Leafs Each leaf has 36 ports and up to 9 leafs can fit in the chassis Chassis fan modules Power supply units 6 Spines AC inlets Fuse box Do not tamper with Power supplies Manageme...

Page 16: ...support Forward Error Correction FEC as described in IEEE Std 802 3ap 2007 Amendment to IEEE Std 802 3 2005 chapter 74 1 4 Power Supply Redundancy The CS7510 platform comes standard with 6 power suppl...

Page 17: ...ired minimum due to power supply failure MLNX OS may power down some leafs If this happens it may be necessary to reboot the chassis once the defective PSU has been replaced Two ways to reboot are to...

Page 18: ...ment 2 1 Installation Safety Warnings These safety warnings are in English For other languages please refer to the appendixes 1 Installation Instructions 2 Bodily Injury Due to Weight 3 Heavy Equipmen...

Page 19: ...commended 40 C 104 F Moreover to guarantee proper air flow allow at least 8cm 3 inches of clearance around the ventilation openings The chassis should not be stacked on any other equipment If the chas...

Page 20: ...from the bottom to the top This equipment should be installed replaced and or serviced only by trained and qual ified personnel Disposal of this equipment should be in accordance to all national laws...

Page 21: ...equipment shall be permanently connected to that by a service person A SERVICE PERSON shall check whether or not the socket outlet from which the equipment is to be powered provides a connection to t...

Page 22: ...ce The rails are not intended for sliding the unit away from the rack It is for permanent instal lation at final resting place only not used for service and maintenance According to the WEEE Directive...

Page 23: ...r cords 250V 16A 2m C19 to C20 USA UL Standard The management spine and leaf modules are shipped separately It is highly recommended that the installation site building be equipped with a light ning r...

Page 24: ...te look for and inspect the shock sticker to confirm that it has not triggered The shock stickers turn red if the crate has been mishandled or handled roughly If one of the shock stickers is red notif...

Page 25: ...4 2 Opening the Chassis Crate Step 1 Before starting the procedure put the ESD strap on and connect it to a valid ground Step 2 Unscrew and remove the top cover of the crate Step 3 Unscrew and remove...

Page 26: ...ed Step 6 Remove all protective plastic film from the sides and top of the chassis Unpack the system and check against the parts list to make sure that all the parts have been sent Check the parts for...

Page 27: ...9 inch racks Guaran tee proper ventilation by leaving 8cm 3 of space to the front and rear of the switch This ensures proper airflow through the chassis This is crucial for maintaining good airflow at...

Page 28: ...Chassis Installation Kit Due to the space required by up to 648 connector cables it is recommended to use a rack that is 120cm long and 80cm wide This should allow for proper cable manage ment and en...

Page 29: ...nstallation Kit 10 8 M6X16 hex head screw a Use the item number to identify the corresponding item in Figure 8 Each item number appears in a call out bubble Table 5 Chassis Installation Kit Items Item...

Page 30: ...rts Item No a a Use the item number to identify the corresponding item in Figure 9 Each item number appears in a call out bubble 1 1 Left riveted cable holder 3 14 Pan head screw 2 1 Right riveted cab...

Page 31: ...Kit The shelf installation kit includes 18 shelves only Figure 10 Shelf Installation Kit 2 5 2 Required Installation Tools Figure 11 includes the tools which are required for the installation of the...

Page 32: ...e switch system chassis For the purpose of clarity the racks in those figures will have the side panels removed You however do not need to remove the side panels to install the switch chassis It is re...

Page 33: ...34 Mellanox Technologies Step 2 Insert 6 M6 cage nuts from the inside each of BEAM 3 and BEAM 4 on the leaf side in order to support the shelf Figure 13 Figure 13 Cage Nut Placement for Shelf on BEAM...

Page 34: ...Step 3 Place the top end of the support bracket at the top of U4 using 2 M6x25 screws and 2 M6 flat washers on BEAM 3 and BEAM 4 Figure 14 Do not tighten the screws completely at this point Figure 14...

Page 35: ...he Chassis Installation Kit Items box on the inside of each of the spine side beams of the rack in the slots indicated in Figure 15 Figure 15 Cage Nut Placement for Switch System Chassis on Spine Side...

Page 36: ...the Cable Management Installation Kit Parts box on the inside of each of the leaf side beams of the rack in the slots indicated in Figure 16 Figure 16 Cage Nut Placement for Cable Holders on Leaf Side...

Page 37: ...Installation 38 Mellanox Technologies Step 6 Using a ratchet wrench loosen the shelf arms M6 hex screws enough to allow for slight movement Figure 17 Figure 17 Loosening the Leaf Side Shelf Arms...

Page 38: ...ologies Step 7 Adjust the shelf s leaf side arms so that the distance between the leaf side and spine side arms is at least 5mm longer than the distance between the rack beams Figure 18 Figure 18 Adju...

Page 39: ...Installation 40 Mellanox Technologies Step 8 Place the shelf in U3 of the rack by inserting it at a tilt Figure 19 Figure 19 Placing Shelf At least 2 people are necessary for installing the shelf...

Page 40: ...ad screws and the arm brackets at an intermediate 3Nm torque Figure 20 Figure 20 Tightening Shelf Cage Nut Screws on Spine Side Step 10 Assemble the leaf side M6X25 pan head screws and the arm bracket...

Page 41: ...ws of the shelf arms on the spine side at 9Nm torque Figure 22 Figure 22 Tightening Spine side Shelf Arm Screws Step 12 Screw in 4 more M6X25 pan head screws in the support brackets as fasteners from...

Page 42: ...Installation 43 Mellanox Technologies Step 13 Tighten the 10 hex head screws of the shelf s leaf side arms at 9Nm torque on both sides Figure 24 Figure 24 Tightening Spine side Shelf Arm Screws...

Page 43: ...tion 44 Mellanox Technologies Step 14 Tighten the 12 M6X25 pan head screws of the shelf s leaf side arms at 9Nm torque now that the shelf has been placed Figure 25 Figure 25 Tightening Leaf side Shelf...

Page 44: ...allation 45 Mellanox Technologies Step 15 Assemble the bracket weld to the shelf on the spine side and tighten at 5Nm with 2 hex screws 2 spring washers and 2 flat washers Figure 26 Weld Bracket Assem...

Page 45: ...ve more room on the leaf port cables side to allow room for cable management Figure 27 Placement of Chassis in Rack Top View Step 17 Put the crate on the fork lift or a mechanical lift Figure 28 Fork...

Page 46: ...lock down bars Step 20 Using a fork or mechanical lift position the middle of the leaf side of the chassis in front of the spine side of the rack Figure 30 Figure 30 Rack and Chassis Alignment The ch...

Page 47: ...e the rotated strip on top of the bracket weld Figure 31 Figure 31 Rotated Strip and Bracket Weld Step 22 Unscrew the lock down bar facing the rack Note that the chassis is on ball bearings and with t...

Page 48: ...49 Mellanox Technologies Step 23 Slide the switch system chassis halfway into the rack Figure 32 Figure 32 Sliding Chassis in Rack Push only from the spine side so as to not injure your fingers durin...

Page 49: ...24 Slide the switch system chassis all the way into the rack until it stops Step 25 Slide in the left and right chassis slides from the leaf side Figure 33 Figure 33 Sliding in Chassis Slides Beware n...

Page 50: ...Installation 51 Mellanox Technologies Step 26 Slide the switch system chassis all the way into the rack Figure 32 Figure 34 Sliding Chassis into Rack...

Page 51: ...llation 52 Mellanox Technologies Step 27 Screw the chassis to the rack on the spine side using 12 M6X16 screws where the cage nuts have been placed at 9Nm torque Figure 35 Screwing the Chassis to the...

Page 52: ...logies Step 28 Assemble the 2 4 oval washer plates to the left and right chassis slides on the leaf side Figure 36 at 3 23 3 58Nm torque using 4 M5 pan head screws on each side Figure 36 Figure 36 Scr...

Page 53: ...Installation 54 Mellanox Technologies Step 29 Remove the M6X16 screws holding the weld bracket on the spine side using a ratchet wrench Figure 37 Figure 37 Removing the Weld Bracket...

Page 54: ...ed fixing bracket on the shelf from the leaf side and assemble it using a ratchet wrench with 8mm socket and 6 10 32 hex screws 6 10 flat washers and 6 10 spring washers to the chassis at 3 23 3 58Nm...

Page 55: ...lace the perforated fixing bracket on the shelf from the spine side and assemble it using 6 10 32 hex screws 6 10 spring washers and 6 10 flat washers to the chassis at 3 23 3 58Nm torque Figure 39 Fi...

Page 56: ...Installation 57 Mellanox Technologies Step 32 Screw the perforated fixing bracket on the leaf side to the shelf at 9Nm torque Figure 40 Figure 40 Leaf Side Fixing Bracket With Shelf...

Page 57: ...anox Technologies Step 33 Screw the fixing bracket on the spine side to the shelf using 3 M6X16 hex screws 3 M6 spring washers and 3 M6 flat washers at 9Nm torque Figure 41 Figure 41 Spine Side Fixing...

Page 58: ...gure 42 Figure 42 Installing Cable Holders 2 6 Ground Connections Make sure to connect the ground post to a valid electrical ground Use a grounding lug and a ground wire of sufficient capacity to safe...

Page 59: ...tion wrist strap on your wrist and connect to the chassis This switch platform supports hot swap capabilities for the following parts Power supply units Leaf modules Spine modules Leaf fan modules Spi...

Page 60: ...racted without bringing down the system To extract a PSU Step 1 Determine which AC connector on the connector side of the chassis corresponds to the defective PSU Step 2 Remove the power cord from the...

Page 61: ...the command below switch master config no power enable L16 Step 2 Disconnect all cables connected to the leaf Step 3 Push the ejector handles in the direction of the red arrows in Figure 46 and pull...

Page 62: ...Intact Leaf Signal Connectors Step 4 Check power connector s integrity Look for any damage on the power connector casing or blades damage Figure 48 Intact Leaf Power Pins Step 5 Start with the ejecto...

Page 63: ...les can be hot swapped when these two management modules are installed and working Spine module slots are numbered from top to bottom from S1 to S9 on both sides of the chassis Do not apply excessive...

Page 64: ...swapping the spine module connected to the master management module will cause the chassis to crash Neither the CLI nor the GUI management tools will allow you to shut down spine 1 or spine 2 as the...

Page 65: ...e Step 4 Pull out the module halfway through the guiding rails using both ejectors Step 5 Re lock the ejector handles Step 6 Hold the body of the module on both sides and remove it from the chassis 2...

Page 66: ...ont panel of the spine Step 5 Holding the spine by its sides carefully set the spine module halfway into the chassis Step 6 Using only the ejector handles slowly slide the module into the chassis unti...

Page 67: ...an Module There are 12 fan modules on the chassis for the leaf and management modules They are located on the spine side of the chassis with 6 on the right of the spines and 6 on the left When a fan m...

Page 68: ...gure 55 Leaf Fan Locations on the Chassis Extracting the Leaf Fan Module Step 1 Push and hold the blue latch release See Figure 56 Step 2 Slowly pull out the fan module using the handle Figure 56 Leaf...

Page 69: ...us LED on the spine and the fan status LED on the management module light up indicating the necessity to replace the fan module Airflow through the spines is independent of the airflow through the lea...

Page 70: ...at lock the module in place and serve as a lever for seating or extracting see Figure 59 When hot swapping any of the units it is necessary to wait 1 minute after removing the defective part before in...

Page 71: ...remove it from the chassis Inserting a Management Module To insert a management module Step 1 Check for foreign objects in or mechanical damage to the chassis management slots Step 2 Check management...

Page 72: ...the ejector han dles shut Figure 62 Figure 62 Management Module Insertion Vertical Ejector han dle hooks Ejector han Locking mecha Step 9 Lock the ejector handles onto the module Do not apply excessi...

Page 73: ...e LED indicator above the port will light when the physical connection is established when both ends of the cable are properly connected to working devices Allow 15 seconds for link to get up To remov...

Page 74: ...ower cords you may place the 18 cable supporters onto the cable holders Figure 63 Figure 63 Cable Supporter Placement 2 9 1 Supported Approved Cables For a list of approved cables for this switch see...

Page 75: ...uld comply with 180 265VAC 50Hz or 60Hz charac teristics C19 to C20 type power cords 15A rated should be used to connect system to AC power The maximum power consumption of each power supply is 12A En...

Page 76: ...its upper side and are behind two cover panels The plugs for these PSUs are on the leaf side of the chassis Each power supply unit has the following LED indicators Figure 65 Power Supply Unit Status...

Page 77: ...tem An appropriate capacitor discharge unit CDU should be installed to interface with the sys tem 3 1 3 Leaf Module LED Indicators Figure 67 Leaf Module LED Indicators Leaf Status LED Bad Port LED UID...

Page 78: ...ustomers in the near future For details please contact Mellanox Technologies support 3 1 3 4 Leaf Module Port Connector LED Assignment Above the ports are two LEDs one for the upper port and one for t...

Page 79: ...are connected to the spine All spines must be installed and work ing to ensure that full BW exists between nodes The maximum number of connections from each leaf is 1 If the number of leafs x the max...

Page 80: ...spine Table 12 shows the leaf to spine status according to the LED condition Table 12 Spine to Leaf IB Link Status LED Color Description Off Link is down Green Solid Logical connection Green Flashing...

Page 81: ...dition Figure 69 Spine Side Panel Display Status Indications Sta PSU Sta SpineFan Status Leaf Fan Status MNG1 Master Status MNG2 Master Status Table 14 Spine Side Panel LED Display for Normal Operatio...

Page 82: ...in one or more of the leaf fans check individual leaf fan LEDs for fault indications MNG1 Mas ter Status Off No power Management module is not installed Management module is not the master Green Green...

Page 83: ...ion Amber Fatal error in one or more of the spine fans check individual spine fan LEDs for fault indications Leaf Fan Sta tus Off No power Green Green Normal operation Amber Fatal error in one or more...

Page 84: ...ment Module Interfaces The switch system requires at least one management module The management module has 6 interfaces to connect to the director switch system They are 1 I2C CONSOLE port this is an...

Page 85: ...the management module A quick push of this button performs this reset When the reset button is pushed on the master management module this management mod ule is reset becoming the slave and the other...

Page 86: ...Interfaces 87 Mellanox Technologies 15 seconds the management module is reset and the password is deleted You will then be able to enter without a password and make a new password for the user admin...

Page 87: ...flow 4 Connect the power cords to the PSUs 5 Connect the power cords to grounded electrical outlets 4 1 System Status After Power Up As system boot been completed you should observe the following Step...

Page 88: ...nt Module Status Indications for Normal Operation Slave Step 6 Connect the system to the power main Step 7 Make sure all that PSUs get powered on 4 2 Switch Shut Down Procedure The chassis cannot be s...

Page 89: ...se refer to the MLNX OS User Manual The managed switch system includes the following software components Embedded Subnet Manager SM Chassis manager and system BIST SNMP agent 3rd party tool integratio...

Page 90: ...ying and filtering all identified systems and nodes within the fabric Fabric Inspector includes a complete set of tools for fabric wide diagnostics to check node node and node switch connectivity and...

Page 91: ...Us are showing DC OK 2 Uninstall and reinstall the Leaf module 3 When the amber LED is on this indicates a fault in the module uninstall and reinstall the leaf module 4 If uninstalling and reinstallin...

Page 92: ...anagement module is lit 1 Check the MLNX OS management for confirmation and possible explanation of the alert 2 Make sure that there is nothing blocking the front or rear of the chassis and that the f...

Page 93: ...are not blocked especially dust over the holes 3 If you find dust blocking the holes it is recommended to clean the fan unit and remove the dust from the front and rear panels of the switch using a va...

Page 94: ...h1 Hit Ctrl B to stop autoboot 0 Mellanox FabricIT Boot Menu 1 EFM_PPC_M460EX EFM_1 1 1000 2010 06 24 16 32 03 ppc 2 EFM_PPC_M460EX EFM_1 1 1200 2010 06 25 18 00 03 ppc 3 U Boot prompt Choice Troubles...

Page 95: ...enter of Gravity CoGh 343 34 mm from base of chassis CoGw 241 3 mm from left side surface as one faces the spine side CoGd 356 46 mm from spine side surface Total Max Airflow 31 1 M3 min 1100 CFM SerD...

Page 96: ...com page switch_certification_matrix EMC Emissions CE FCC ICES RCM VCCI For more compliance information please refer to the following page on the Mellanox webpage http www mellanox com page switch_cer...

Page 97: ...ww mellanox com page cables mtag cable_overview A 3 EMC Certifications The list of EMC certifications per chassis model type for different markets in the world is located on the Mellanox Website at ht...

Page 98: ...by the MLNX OS management SW indicating to system administration that the switch has crossed the Warning threshold Note that this temperature threshold does not require nor lead to any action by hardw...

Page 99: ...stem Table 17 Switch System Weight Calculation Number of FRUs FRU Type Weight of 1 FRU Total Weight FRU Type Chassis as shipped 156 of Spines 3 015 of leafs 5 045 of leaf blanks 1 303 of management mo...

Page 100: ...umption QSFP Cable Type Typical W Maximum W Optical 3 5 3 5 To calculate the total power consumption of the switch system at a certain configuration fill out Table 20 in the following manner 1 In the...

Page 101: ...8 ModSelL Module Select 9 ResetL Module Reset 10 Vcc Rx 3 3 V Power supply receiver 11 SCL 2 wire serial interface clock 12 SDA 2 wire serial interface data 13 GND Ground 14 Rx3p Receiver Non Inverte...

Page 102: ...Supply 31 LPMode Low Power Mode 32 GND Ground 33 Tx3p Transmitter Non Inverted Data Input 34 Tx3n Transmitter Inverted Data Input 35 GND Ground 36 Tx1p Transmitter Non Inverted Data Input 37 Tx1n Tra...

Page 103: ...104 Mellanox Technologies Figure 77 InfiniBand QSFP Connector Symbol...

Page 104: ...105 Mellanox Technologies Figure 78 QSFP Connector Male and Female Views...

Page 105: ...e connector Table 22 RJ 45 CONSOLE and I C Pinout Signal Pin Color Not connected 1 G W I C_SCL 2 G TXD 3 O W Not connected 4 Bl GND 5 Bl W RXD 6 O I C_SDA 7 Br W Not connected 8 Br RS232 harness cable...

Page 106: ...ts RoHS R6 MSB7520 E Switch IB 2 EDR InfiniBand spine blade 36 ports RoHS R6 MSB7570 E MCS75x0 director system Spine Blank MTDF BLK A x86 dual core chassis management module RoHS R6 MMB7500 MCS75x0 di...

Page 107: ...re connecting the equipment to the power source Use enough people to safely lift this product This equipment is heavy and should be moved using a mechanical lift to avoid injuries Risk of Electric Sho...

Page 108: ...inside of the switch platform During periods of lightning activity do not work on the equipment or connect or dis connect cables Copper InfiniBand cables are heavy and not flexible as such they should...

Page 109: ...l electrical codes For North America equipment must be installed in accordance to the applicable requirements in the US National Electrical Code and the Canadian Electri cal Code Cables for connecting...

Page 110: ...111 Mellanox Technologies 21 Country of Norway Power Restrictions H 3 1 2 3 4 5 This unit is intended for connection to a TN power system and an IT power system of Norway only...

Page 111: ...112 Mellanox Technologies 6 7 8 9 10 11...

Page 112: ...113 Mellanox Technologies 12 13 14 15 16 17...

Page 113: ...114 Mellanox Technologies 18 19 20 21 WEEE 22 H 4 Chinese 1...

Page 114: ...115 Mellanox Technologies 2 3 4 5 6 7 8 r r 368...

Page 115: ...116 Mellanox Technologies 9 10 InfiniBand 11 12 13 14 15 UL CSA 16 QILQL DQG 8 6 9 5 9 39 9...

Page 116: ...117 Mellanox Technologies 17 18 19 20 WEEE 21 56 8 3 3 36 71 7...

Page 117: ...plac avec un syst me de levage m canique pour viter les blessures Danger d lectrocution Lorsque le module de ventilation est retir les broches d alimentation sont expos es dans l emplacement du modul...

Page 118: ...nchez toutes les alimen tations Pendant un orage ne pas travailler sur l quipement ni brancher ou d brancher des c bles Les c bles InfiniBand en cuivre sont lourds et peu flexibles Par cons quent il f...

Page 119: ...Le cordon doit avoir une prise moul e 250 V 10 A Avertissement courant de fuite lev une connexion la terre est indispensable avant de brancher l alimentation Les c bles de connexion aux interfaces RS2...

Page 120: ...eben gen gend Personen einsetzen Dieses Ger t ist schwer und muss mit einem mechanischen Hebeger t verschoben werden um Verletzungen zu vermeiden Stromschlagrisiko Bei abgenommenem Ventilatormodul sin...

Page 121: ...ines Gewitters und Blitzschlag nicht am Ger t schlie en Sie keine Kabel an oder ab InfiniBand Kupferkabel sind schwer und nicht flexible Deshalb m ssen sie vorsichtig an die Anschl sse angebracht bzw...

Page 122: ...m PVC Mantel isoliert Das Kabel muss eine angespritztem Stecker bewertet bei 250 V 10 A WARNUNG Hohe Ableitstrom Earth Verbindung bevor Sie die Verbindung von wesentlicher Bedeutung werden Dieses Ger...

Page 123: ...le seine Teile in verantwortungsvoller und umweltfreundlicher Art und Weise entsorgen Antes de conectar el equipo a la fuente de alimentaci n leer todas las instrucciones de instalaci n Recurra a sufi...

Page 124: ...su lugar una vac a Si se dispone de una fuente de alimentaci n vac a no utilizar el producto si su tapa est quitada o no est bien cerrada Riesgo de descarga el ctrica y peligro de corriente Todas las...

Page 125: ...acional de los EE UU y del C digo El ctrico de Canad En conexiones de Am rica del Norte seleccionar un cable de alimentaci n homologado por UL y con certificaci n CSA de tres conductores 16 AWG termi...

Page 126: ...do de f cil acceso con una corriente nominal de 20 A Cuidado Equipos montados en deslizadores o rieles no se deben utilizar como estantes ni como espacio de trabajo La finalidad de los rieles no es de...

Page 127: ...128 Mellanox Technologies 3 4 5 6 7 8 9 45 C 113 F 8 3...

Page 128: ...129 Mellanox Technologies 10 InfiniBand 11 12 13 14 15 16 UL CSA InfiniBand UL CSA 3 16 AWG 1 5 6 4 5 125 13 HAR 3 1 0 300 250 10...

Page 129: ...ologies 17 18 19 20 WEEE H 9 Avertismente privind siguran a la instalare Romanian 1 Instruc iuni de instalare RS232 Ethernet DP 1 DP 2 UL 20 2002 96 EC WEEE Citi i toate instruc iunile de instalare na...

Page 130: ...r Acest echipament nu trebuie s fie ac ionat ntr o zon unde temperatura ambiant dep e te valoarea maxim recomandat 45 C 113 F n plus pentru a asigura un flux de aer adecvat l sa i un spa iu liber de c...

Page 131: ...uni speciale C nd acest produs este montat sau depanat ntr un rack trebuie s fie luate m suri de precau ie speciale pentru a se asigura c sistemul r m ne stabil n general trebuie s umple i rack ul cu...

Page 132: ...egal cu 250 V 10 A Avertisment Curent de scurgere de nalt frecven mp m ntarea este esen ial nainte de a conecta sursa de alimentare Cablurile pentru conectarea la unitatea RS232 i la interfe ele Ether...

Page 133: ...premje tati pomo u mehani kog dizala kako bi se izbjegle ozljede Rizik od strujnog udara S uklonjenim modulom ventilatora perima napajanja se mo e pristupiti u otvoru mod ula NEMOJTE umetati alat ili...

Page 134: ...napajanja kako biste osigurali stanje bez napajanja unutar platforme preklopnika Tijekom djelovanja munja nemojte raditi na opremi ili spajati ili odspajati kabele Bakreni kabeli InfiniBand su te ki i...

Page 135: ...opsku mre u odaberite kabel napajanja koji je me unarodno uskla en i ozna en HAR 3 ilni s najmanje 1 0 mm2 ice nazivnog napona od 300 V s PVC izolacijom Kabel mora imati lijevani utika nazivnog napona...

Page 136: ...bao odlagati kao obi an ku anski otpad Odlaganje ovog proizvoda i svih njegovih dijelova vr ite na odgovoran i ekolo ki na in Ovaj je ure aj namijenjen samo za spajanje na elektri ni sustav s TN uzeml...

Page 137: ...ato lasciare almeno 8 cm 3 pollici di spazio attorno alle aperture di ventilazione Ku i te se ne bi trebalo slagati na drugu opremu Ako ku i te padne mo e izazvati tje lesne ozljede i o te enje opreme...

Page 138: ...nga di 4 5 m Per una connessione europea selezionare un cavo di alimentazione armonizzato a livello internazionale e contrassegnato da HAR a 3 conduttori minimo 1 0 mm2 fili con guaina isolante in PVC...

Page 139: ...ione per la Norvegia Attenzione un apparecchiatura scorrevole o montata su binari non va utilizzata come scaffale o piano di lavoro I binari non sono progettati per far scorrere e allontanare l unit d...

Page 140: ...in 5 A r s nma Bu ekipman nerilen maksimum ortam s cakl n a an alanlarda al t r lmamal d r 45 C 113 F Ayr ca d zg n hava ak sa lamak i in havaland rma deliklerinin 6 asi stif asinin di er herhangi bir...

Page 141: ...ezler Bu nedenle ba lant lara ok dikkatli bir ekilde tak lmalar veya kar lmalar gerekir zel uyar lar talimatlar i in kablo 11 skele Montaj ve Bak m Bu r n bir iskelede monte edildiyse veya bir iskele...

Page 142: ...ilebilecek 20 V Kay tl devre par as a r ak m koruma cihaz n n bina elektrik ebekesinde kurulu olmas gerekir 19 Anahtar Raf veya al ma Alan olarak kullanmay nl Dikkat S rg l rayl ekipman raf veya al ma...

Page 143: ...144 Mellanox Technologies 21 Norve G K s tlamalar Bu nite bir TN g sistemine ve sadece Norve in IT g sistemine ba lanmak H 13 Japan VCCI Class A Statement H 14 1 2 3 4 i indir...

Page 144: ...145 Mellanox Technologies 5 6 7 8 9 10 11 FP 368...

Page 145: ...146 Mellanox Technologies 12 13 14 15 8 6 16 17 18 9 8 6 P 5 FRQGXFWRU PP 9 39 9 1DWLRQDO OHFWULFDO RGH DQDGLDQ OHFWULFDO RGH 56 8 3 3 36...

Page 146: ...147 Mellanox Technologies 19 20 21 2 2 71 7...

Reviews: