Exhaust Fan, Auxiliary Airflow, Hood Controller, Virtual Input Module and Virtual
Output Module Device Instance ID
This is the statically assigning the Device Instance ID for each Exhaust Fan, Auxiliary
Airflow, Hood Controller, Virtual Input Module and Virtual Output Module. If “BACnet
Auto Number” is set to “Yes”, these numbers are ignored. These all default to 0. Note that
if you are statically assigning Device Instance IDs that they all need to be unique on the
BACnet network.
Exhaust Fan, Auxiliary Airflow, and Hood Controller Active on BACnet
Given the number of Device Objects that are possible with the Intelli-Hood system, some
sites may not need to monitor all devices and may want to limit the number of Device
Objects on their BACnet network. If you do not want to monitor a particular Exhaust Fan,
Auxiliary Airflow or Hood Controller then you can use this parameter to remove that
particular device from the BACnet interface. If a devices “Active on BACnet” parameter is
set to “No”, then there will not be a Device Object created for that device. This setting
defaults to “Yes” for the Exhaust Fans and Auxiliary Airflows. This setting defaults to “No”
for the Hood Controllers.