Page | 9
Highest
The affected Exhaust Fans and Auxiliary Airflows either run at the calculated fan speed or
the percent speed governed by this analog input, whichever is highest.
Add
The analog input percentage is added to the calculated fan speed for the Exhaust Fans and
Auxiliary Airflows.
Average
The fan speed for the Exhaust Fans and Auxiliary Airflows is first calculated and then is
averaged with the analog input value.
Aux. Highest
The affected Auxiliary Airflows either run at the calculated fan speed or the percent speed
governed by this analog input, whichever is highest. Exhaust Fans are not affected.
Aux. Add
The analog input percentage is added to the calculated fan speed for the Auxiliary
Airflows. Exhaust Fans are not affected.
Aux. Average
The fan speed for the Auxiliary Airflows is first calculated and then is averaged with the
analog input value. Exhaust Fans are not affected.
Analog Output Status
There is one physical analog output on the Intelli-Hood System Controller. The analog
output can be configured in either 0-10VDC or 0-20mA operation and can be associated
with any Auxiliary Airflows in the system. The Analog Output Status reports the current
value of the system’s physical analog output as a percentage.