Hood Controllers 

Each Hood Controller houses up to four temperature sensors and one set of optics for 
temperature and effluent detection.  By default there is not a Device Object present for 
each Hood Controller, but the system can be configured to do so.  Below is a list of the 
Hood Controller Objects. 

 
Temperature 1 through Temperature 4 

Each Hood Controller has one Analog Value that represents the current temperature of 
the related temperature probe in Fahrenheit.  The temperature readings are updated 
once every 30 seconds. 

 
Optics Tripped 

The Optics Tripped Binary Value is active if the Hood Controller’s optics have detected 
effluent or if there is an optic fault.  If the Optics Tripped value is active, then any 
associated fans that are on will be running full speed. 
 

Virtual Input Module 

A Virtual Input Module is a virtual device to provide a means to add digital inputs to the 
system that can be controlled via BACnet.  Below is a list of the Objects available on the 
Virtual Input Module. 

 
Digital Input 1 through Digital Input 4 

The Virtual Input Module has four digital inputs that mimic the operation of the physical 
digital inputs on the System Controller.  See the “Digital Input Status” section under the 
System Controller on page 5 for a description of the different digital input configurations.  
The Intelli-Hood system has a BACnet Watchdog timeout that is used to reset the Virtual 
Input Module’s digital inputs if no BACnet communication has been received in a given 
amount of time.  See the BACnet Watchdog description on page 20 for more details on 
this configuration parameter. 
 

Analog Input 1 through Analog Input 4 

The Virtual Input Module has four analog inputs that mimic the operation of the physical 
analog input on the System Controller.  See the “Analog Input Status” section under the 
System Controller on page 8 for a description of the different analog input configurations.  
The Intelli-Hood system has a BACnet Watchdog timeout that is used to reset the Virtual 
Input Module’s analog inputs if no BACnet communication has been received in a given 
amount of time.  See the BACnet Watchdog description on page 20 for more details on 
this configuration parameter. 
 
 

 

 

Summary of Contents for Intelli-Hood IH3 SC

Page 1: ...tegrity Innovation Service Excellence BACnet Protocol Implementation Conformance Statement PICS Version 7 0 Melink Document IH ENG DTS BAC 006 Melink Corporation 5140 River Valley Rd Cincinnati OH 451...

Page 2: ...Drive 18 Networking Setup and Configuration 19 BACnet Setup and Configuration 20 Common BACnet Interfacing Use Cases 22 Monitoring Fan Speeds 22 Monitoring Energy Consumption 22 Setting Time on the In...

Page 3: ...aust Fans and kitchen MUA Make Up Air units When smoke is created under normal cooking conditions the optic sensors signal the exhaust fan VFD to send the exhaust fan motor to full speed until all smo...

Page 4: ...more information Analog Value Binary Value Device Data Link Layer Options BACnet IP Annex J Device Address Binding Is static device binding supported This is currently necessary for two way communicat...

Page 5: ...ead only BV4 24VDC Out 1 Status Energized De Energized Read only BV5 24VDC Out 2 Status Energized De Energized Read only BV6 Analog Input Status 0 100 Read only AV0 Analog Output Status 0 100 Read onl...

Page 6: ...s the list of possible digital input configurations and how they affect the Intelli Hood system Remote On Off A Remote On Off digital input is an edge sensitive input When the digital input changes st...

Page 7: ...do not command fans to turn on or off but only set the minimum speed for the fans when they are on External Fault An External Fault digital input is a level sensitive input An External Fault input can...

Page 8: ...guration and the state of the associated Hood Groups The following is a short description of each digital output configuration option and how the system state affects the digital output Temperature Al...

Page 9: ...ted Hood Groups VFD Fault A VFD Fault digital output will be energized if there is any VFD Fault lost communication or VFD tripped due to a fault on any VFD in any associated Hood Group System Fault A...

Page 10: ...ercent speed governed by this analog input whichever is highest Exhaust Fans are not affected Aux Add The analog input percentage is added to the calculated fan speed for the Auxiliary Airflows Exhaus...

Page 11: ...lt has been resolved the VFD still will need its VFD fault cleared before the VFD will power a fan The Clear VFD Fault Binary Value can be used to attempt to clear a VFD Fault If the Clear VFD Fault B...

Page 12: ...value Output Energy The reported kWh counter of the VFD The kWh counter is not available on all VFD models be sure it is available on your VFD if you would like to monitor this value Note that the In...

Page 13: ...t Module Digital Input 1 through Digital Input 4 The Virtual Input Module has four digital inputs that mimic the operation of the physical digital inputs on the System Controller See the Digital Input...

Page 14: ...list of the Objects available on the Virtual Input Module Digital Output 1 through Digital Output 4 The Virtual Output Module has four digital outputs that mimic the operation of the physical digital...

Page 15: ...ese can be configured on your Intelli Hood system prior to installation Network Settings DHCP Enabled Yes No Static IP ____________________ Netmask ____________________ DNS Server 1 __________________...

Page 16: ...ood Controller 2 BACnet Settings BACnet Device Instance ID ____________________ BACnet Enabled Yes No Hood Controller 3 BACnet Settings BACnet Device Instance ID ____________________ BACnet Enabled Ye...

Page 17: ...at the same time and hold the buttons down for ten seconds System Configuration should change from red to blue to indicate that configuration is unlocked Release the Up and Down buttons at this point...

Page 18: ...et to the Auxiliary Airflow s BACnet configuration settings 5 To get to the Hood Controller BACnet configuration settings from the Main Menu go to System Configuration Hood Controllers to get to the H...

Page 19: ...the USB flash drive with the one titled ConfigurationFiles zip containing the latest configuration It is suggested that you keep a backup of the system configuration in a safe location in case you nee...

Page 20: ...if the Intelli Hood system needs to communicate with devices on another network This is generally not needed unless you are setting up the system for remote access You can set this if DHCP is enabled...

Page 21: ...evice Instance ID sequentially after the System Controller s Device Instance ID See Appendix A if you need specific details on how the automatic Device Instance Numbering works If you cannot use a seq...

Page 22: ...Fan Auxiliary Airflow and Hood Controller Active on BACnet Given the number of Device Objects that are possible with the Intelli Hood system some sites may not need to monitor all devices and may want...

Page 23: ...iary Airflow reports Fault Active on Binary Value 1 If there is a fault at the VFD or if the Intelli Hood system has lost communication to the VFD then Fault Active is set for that fan This may be use...

Page 24: ...ystem s time from your Operator s Workstation The Intelli Hood system supports the UTC Time Synchronization service Follow your Operator Workstation s instructions on how to set a Device Object s time...

Page 25: ...each virtual device when the System Controller auto assigns the Device Instance Numbers The System Controller Device Object is Device Instance Number defaults to 654000 Vendor ID x 1000 Each Exhaust F...

Page 26: ...ll always be Binary Value 0 for each Exhaust Fan or Auxiliary Airflow Device Object MAC Address The MAC address for each Device Object is based upon the IP address of the Intelli Hood 3 System Control...

Page 27: ...e Number Device Object MAC Address Device Object Name 654000 142 51 5 36 0xBAC0 System Controller 654001 36 5 51 1 0xBAC0 KEF 02 654002 36 5 51 2 0xBAC0 KEF 05 654003 36 5 51 3 0xBAC0 MUA 41 654004 36...

Page 28: ...Hood Network Address 2 Hood Controller 3 HC 03 Hood Network Address 3 Hood Controller 4 HC 04 Hood Network Address 4 Resulting Device Object List Device Instance Number Device Object MAC Address Devic...

Page 29: ...if you need to set the Device Instance Numbers to be within a certain range but do not care what the Device Instance Number is for a particular device The following is a modification to the previous e...

Page 30: ...t Fans Auxiliary Airflows Hood Controllers Virtual Input Modules and Virtual Output Modules and auto numbers these devices When BACnet Auto Number is set to No the configured BACnet Device Instance Nu...

Page 31: ...what you expected then check the configuration for that device Similarly you can find the assigned Device Instance Numbers for all Hood Controllers by navigating to Menu Status Hood Controllers The De...

Page 32: ...uchpad or look at the label on the inside door of the System Controller enclosure If the serial number starts with V3 for example V300012 then you have a standard System Controller and BACnet communic...

Page 33: ...BACnet networks Network Discovery or BACnet Discovery as described above If you discover a device that is setup with the Intelli Hood s DNET then determine whether to change the Intelli Hood s DNET o...

Page 34: ...et Watchdog configuration settings The system will reset all the digital inputs and analog inputs on all Virtual Input Modules if the Intelli Hood system receives no BACnet communication for the time...

Page 35: ...dated formatting to clarify device operation Removed references to BBMD and Foreign Device support 5 0 10 21 2015 Updated the Object Property Support Matrix to include the currently supported points A...

Reviews: