GD-5610
Instructions Manual
6-3.Connecting AC Input/Motor Output Terminal Block(J2,J3)
Turn the main power OFF.
Failure to do so may cause electric shock.
Securely ground the protective earth
Failure to do so may cause electric shock.
Do not force the power line or the motor
line to be bent or pulled or pinched.
Doing so may cause electric shock or fire.
Erroneous connection may result
in breakage of the motor or the driver.
Correctly connect the motor wiring.
The following items are required:
● Crimping terminal
8
(TMEV1.25-3: Nichifu or the equivalent)
● Manually operated crimping tool for AWG22-16
One unit
(NH-11: Nichifu or the equivalent)
(1) Turn power of the equipment [OFF].
(2) Crimp the crimping terminals to the cable used for wiring.
(3) Remove the covers of terminal block, then connect.
(4) Fix the terminal block covers after completing connection.
GD-5610
J2
〈Wiring〉
〈Connection〉
〈Crimping〉
Crimping terminal
1
2
3
N
L
NEUTRAL
LIVE
Single-phase 100-115V
Protective earth terminal
for the equipment (PE)
100-
115V~
Protective earth
terminal
〔Protective earth terminal ・ AC input terminal〕
WARNING
WARNING
WARNING
CAUTION
-24-