Time Sync Error Relay
On the back panel of the device you can find a DFK connector labeled „Error“. This
relay output is connected to the TTL TIME_SYNC output of the reference clock
(GPS, PZF, TCR, ...). If the internal reference clock has been synchronized by its
source (GPS, DCF77 or IRIG) the relay will switch to mode „NO“ . In case of bad
antenna signal or the device has been switched off the relay falls back to mode „NC“.
Additionally the relay can be switched by one of the notification conditions. In the
notification condition table via WEB or CLI interface you can select the relay out.
The priority is on the “TIME SYNC ERROR” signal of the receiver (“refclock not
sync”). Relay state which will be set via notification conditions will be reseted by any
access via the WEB or CLI interface (if no “TIME SYNC ERROR” is active).
Technical Specification
SWITCHING VOLTAGE max.:
125 VDC
150 VAC
SWITCHING CURRENT max.:
1A
SWITCHING LOAD max.:
DC
30 W
AC
60 VA
SWITCHING-CURRENT UL/CSA:
0.46A
150V AC
0.46A
65V DC
1A
30V DC
RESPONSE TIME:
ca.2ms
Error
CO
(COMM)
NO NC
(OFF) (ON)
(ON)
(OFF)
(COMM)
130