5.4.3 SDI-N2X - Signal Input Module
•
Configuration and montoring with
•
PTP Multicast (Power Profile compatible / PTP Unicast (Telecom Profile compatible) / NTP)
•
PPO (PPS, PPM, PPH ...),
•
IRIG AM, Freq. Synth. sinus outputs
•
Generates several different unmodulated IRIG time codes
The Meinberg N2X180 is synchronized by an PTP Grandmaster or by a NTP Server and can be used as
reference time source for the IMS MDU. The module provides equipment that requires Freq.Synth/sine, PPOs
(PPS, PPM, PPH, Time Code DCLS - IRIG/AFNOR/IEEE1344) or serial time string for synchronization.
The N2X180 operates as an IEEE-1588 slave clock or NTP client in a network.
This converter can synchronize many different systems. Our IEEE-1588 Grandmaster or LANTIME NTP Server,
such the LANTIME M1000, can be used as a reliable time source.
In order to support network management systems the N2X180 offers an extensive SNMP Interface, which
can be accessed by SNMP V1.
Four Status LEDs:
St
(Status):
blue:
during initialisation
green:
normal operation
In
(Init):
red:
no network cable connected
(requires a few minutes after connection)
yellow:
signal is available, not synchronized
green (blink):
locked to input signal and synchronized
but not accurate
green:
Oscillator is warmed up, internal clock
is accurate
Sp
(Speed):
out:
no cable connection
yellow:
10 Mbit
green:
100 Mbit
Li
(Link):
out:
no cable connection
yellow (blink):
if traffic and 10 Mbit
green (blink):
if traffic and 100 Mbit
22