7 Installation
7.1 Power supply
Supply voltage and protective earth must be applied to the device via the 5-pole connector `Power'. The supply
line used for this device must be equipped with an appropriate switch that must be mounted close to the device
and must be marked as a mains switch for the device. Furthermore, to ensure safe operation supply mains con-
nected to this device must be equipped with a fuse and a fault-current circuit breaker according to the applicable
national standards. The device must be connected to a protective earth with low grounding resistance according
to the applicable national rules.
max. 25 VA
100 V to 240 V
100 V to 240 V
max. 8 W
47 Hz to 63 Hz
Supply
Input voltage
Power consumption
Frequency
WARNING: DANGER TO LIFE BY ELECTRICAL SHOCK!
NO LIVE WORKING !
Terminals of the power connector are energized at dangerous voltage levels!
Do not carry out electrical works when terminals or cables are energized!
All connectors must be equipped with suitable covers to prevent from electrical
shock or hazard!
7.2 Assignment of the DSUB connectors
The serial ports COM0 and COM1 are accessible via nine-pole DSUB connectors in the frontpanel. These RS-232
interfaces can be connected to a computer by using a standard modem cable. TxD describes the sending, RxD
the receiving line of the GPS164xHS.
1
6
5
9
RS-232
COM 0 / COM 1
TxD
RxD
GND
WARNING: DANGER TO LIFE BY ELECTRICAL SHOCK!
NO LIVE WORKING !
Disconnect both sides of the serial port cable before working on its connectors.
This device is equipped with two galvanically isolated serial ports. Hazardous
voltages may be applied to the serial cable if a connected device is faulty.
All connectors must be equipped with suitable covers to prevent from electrical
shock or hazard!
16
Date: 27th January 2016
GPS164
Summary of Contents for GPS164-LQ/PPFO-3/REL-1/DAHS
Page 1: ...MANUAL GPS164 PPFO 3 REL 1 DAHS 27th January 2016 Meinberg Radio Clocks GmbH Co KG ...
Page 2: ......
Page 6: ...Page 2 1 General Details 2 Date 27th January 2016 GPS164 ...
Page 16: ...Page 12 6 GPS164 Features 6 4 4 IRIG Standard Format 12 Date 27th January 2016 GPS164 ...
Page 17: ...6 4 Time code outputs Page 13 6 4 5 AFNOR Standard Format GPS164 Date 27th January 2016 13 ...