18
Quota under floor heating
Total power of the heating system [kW] >
5
8
10
12
15
18
up to 10%
V
UK
[l/min]
T = 15 K
4.3
6.9
8.6
10.3
12.9
15.5
T = 20 K
3.2
5.2
6.4
7.7
9.7
11.6
V
MK
[l/min]
T = 15 K
0.5
0.8
1.0
1.1
1.4
1.7
T = 20 K
0.4
0.6
0.7
0.9
1.1
1.3
V
ges
[l/min]
T = 15 K
4.8
7.6
9.5
11.5
14.3
17.2
T = 20 K
3.6
5.7
7.2
8.6
10.7
12.9
Pump level Thermix for the pumps
1.0
1.0
1.0
1.0
1.0
1.0
up to 25%
V
UK
[l/min]
T = 15 K
3.6
5.7
7.2
8.6
10.7
12.9
T = 20 K
2.7
4.3
5.4
6.4
8.1
9.7
V
MK
[l/min]
T = 15 K
1.2
1.9
2.4
2.9
3.6
4.3
T = 20 K
0.9
1.4
1.8
2.1
2.7
3.2
V
ges
[l/min]
T = 15 K
4.8
7.6
9.5
11.5
14.3
17.2
T = 20 K
3.6
5.7
7.2
8.6
10.7
12.9
Pump level Thermix for the pumps
1.0
1.0
1.0
1.0
1.0
1.0
up to 50%
V
UK
[l/min]
T = 15 K
2.4
3.8
4.8
5.7
7.2
8.6
T = 20 K
1.8
2.9
3.6
4.3
5.4
6.4
V
MK
[l/min]
T = 15 K
2.4
3.8
4.8
5.7
7.2
8.6
T = 20 K
1.8
2.9
3.6
4.3
5.4
6.4
V
ges
[l/min]
T = 15 K
4.8
7.6
9.5
11.5
14.3
17.2
T = 20 K
3.6
5.7
7.2
8.6
10.7
12.9
Pump level Thermix for
4m - Pump
1.0
1.0
1.0
2.0
2.0
3.0
6m - Pump
1.0
1.0
1.0
2.0
2.0
2.0
up to 75%
V
UK
[l/min]
T = 15 K
1.2
1.9
2.4
2.9
3.6
4.3
T = 20 K
0.9
1.4
1.8
2.1
2.7
3.2
V
MK
[l/min]
T = 15 K
3.6
5.7
7.2
8.6
10.7
12.9
T = 20 K
2.7
4.3
5.4
6.4
8.1
9.7
V
ges
[l/min]
T = 15 K
4.8
7.6
9.5
11.5
14.3
17.2
T = 20 K
3.6
5.7
7.2
8.6
10.7
12.9
Pump level Thermix for
4m - Pump
1.0
1.0
2.0
3.0
3.0
3.0
6m - Pump
1.0
1.0
2.0
2.0
2.0
3.0
6. Reference value table for presetting the heating system
with Thermix
All data are reference values, deviations may be required according to the system used. The mixed heating circuit is taken into account with a
pressure loss of 0.15 bar.
V
UK
[l/min]
= volumetric flow for unmixed circuit
V
MK
[l/min]
= volumetric flow for mixed circuit
V
ges
[l/min]
= total volumetric flow
GB