T-Type Transformers
T-type transformers represent a special type of three-phase transformers. This
transformer may be tested as a single phase transformer.
To make a measurement on a T-type transformer, the jumpers indicated in Table
C-1 should be applied to the appropriate terminals of the T-type transformer. The
TTR20 measured turns ratio should be compared to the calculated turns ratio
indicated in Table C-1.
Notes to Table C-1
1. Any connection(s) to ground/case of T-type transformer on H or X side should
be removed before testing a transformer.
2. Expect that polarity of the windings is normal (“+” sign is displayed in front of
the turns ratio test result)
Table C-1 ANSI Transformer Winding Phase Relationship
Winding Connection
Winding Tested
IEC
Vector
Group
High-Voltage
Winding (H)
Low-Voltage
Winding (X)
External
Jumpers
Phase
tested
High-
Voltage
Winding
Low-
Voltage
Winding
Calculated
Turn Ratio
T-T
0
-
H
1
-H
2
X
1
-X
2
A
B
H
1
- H
2
H
1
– H
3
X
1
- X
2
X
1
– X
3
T-T
30
lag
H
2
-H
3
X
1
-X
2
A
B
H
1
– H
3
H
2
– H
3
X
1
- X
2
X
1
– X
3
T-T
30
lead
H
2
-H
3
X
1
–X
3
A
B
H
1
– H
3
H
2
– H
3
X
1
– X
3
X
2
– X
1
X
H
V
V
X
H
V
V
2
3
•
X
H
V
V
3
2
•
X
H
V
V
2
3
V
V
X
H
•
3
2
•
X
H
V
V
H
1
X
1
Summary of Contents for TTR20
Page 2: ......
Page 3: ...TTR20 and TTR20 1 Handheld TTR Transformer Turn Ratio Test Set Instruction Manual ...
Page 8: ......
Page 14: ...M AVTMTTR20 Rev 4 Dec 2015 6 M ...
Page 34: ...M AVTMTTR20 Rev 4 Dec 2015 26 M ...
Page 42: ...M AVTMTTR20 Rev 4 Dec 2015 34 M ...
Page 46: ...M AVTMTTR20 Rev 4 Dec 2015 38 M ...