TM1800
ZP-CG01E
CG0757JE
6 CABA LOCAL
pulse and graphs settings. Every setting that is needed
for the test but the selection of transducers. However,
if a conversion table for the transducer is used this
is stored in the template. During a test it adapts the
TM1800 for your needs.
There are three kinds of templates, the Max Config
template, Standard templates (delivered with the
TM1800) and custom made templates. The Max
Config template and Standard templates are non edit-
able.
Note
Breakers associated to a Standard template
cannot be edited.
How to create a template
1]
To create a template for a breaker you must
have created the breaker in the “Breaker
List”, see section 6.10.
2]
Create a breaker by choosing “MAX Config
Template” or one of the standard templates.
Do all needed settings under “Breaker
View”.
3]
Go to “Templates”.
4]
Choose the “Define New Template” and
choose your breaker from “Breaker List”.
Give the template a suitable name e.g. for
which type of circuit breaker is it meant to
be used. All settings done for the breaker are
now also set in the new template. When you
in the future will test a new breaker of the
same type you choose this template and then
run the test.
Max Config Template
As factory setting the “MAX CONFIG TEMPLATE” is
set as default. This is to make sure that you can run a
test the first time without any settings. If you get into
problem doing measurements due to settings, it is a
good basic template to use to see that the TM1800
and the breaker works correct together. When you
make breaker setup it is also good to use the “MAX
CONFIG TEMPLATE” as a base.
The “MAX CONFIG TEMPLATE” is automatically up-
dated every time you start the analyzer. This procedure
is done to make sure that the “MAX CONFIG TEM-
PLATE” always comply with the TM1800 configura-
tion.
Note
If you work with a certain type of breaker dur-
ing a period in time you can set its template
as default. By this you do not have to choose
template. As soon as you turn the operation
knob the TM1800 use your template.
If you do not select any breaker before you run a
measurement (i.e. turn the operation directly after
starting the analyzer) the TM1800 use the template
that is set as default (“MAX CONFIG TEMPLATE”).
Note
If you set another template as default, that
template can not be adapted to the current
configuration of the TM1800.
Comparison to test plans in CABA
Win
The template in CABA Local is a test plan with ad-
ditional settings. All possible settings are made, only
transducer needs to be selected before the test is
performed.
Create a subfolder
The TM1800 is delivered with a set of standard
breaker templates located in the Standard Template(s)
folder. you may however want to create your own
sets of templates. Start off by creating a subfolder:
1]
Navigate to the folder in which you want to
create a subfolder.
2]
Press the “CREATE SUBFOLDER” button.
3]
Write the name (ABB in this example) of the
folder in the Folder ID text field.
4]
Press the “OK” button.
Delete a subfolder
This is how you delete a subfolder and all its content:
1]
Navigate to the folder that you want to
delete.
2]
Press the “CHANGE/DELETE” button.
3]
Press the “DELETE” button.
4]
Confirm deletion by pressing the “YES” but-
ton.
Rename a subfolder
1]
Navigate to the folder you want to rename.
2]
Press the “CHANGE/DELETE” button.
3]
Enter the new name of the folder in the
Folder ID text field.
4]
Press the “OK” button.
Summary of Contents for TM1800
Page 2: ......
Page 7: ...CG0757JE ZP CG01E TM1800 7...
Page 17: ...CG0757JE ZP CG01E TM1800 17 3 System overview...
Page 25: ...CG0757JE ZP CG01E TM1800 25 3 System overview Keyboard in position 3...
Page 71: ...CG0757JE ZP CG01E TM1800 71 7 Perform testing...
Page 97: ...CG0757JE ZP CG01E TM1800 97 12 Quick Guide...
Page 103: ......