83
Power
(Auto Ranging)
Ranges and Resolution
0 to 4 kW in 6 ranges, with 0.1 % resolution
Accuracy:
± 1.5 % of VA, ± 1 digit
Reactive Power
(Auto Ranging)
Ranges and Resolution
0 to 4 kVAR in 6 ranges, with 0.1 % resolution
Accuracy:
± 1.5 % of VA, ± 1 digit
Timer
Range and Resolution:
Displays in either seconds and cycles, with
the following range and resolution
Seconds:
0.0001 to 99999.9 (Auto Ranging)
Cycles:
0.01 to 99999.9 (Auto Ranging)
Accuracy:
± 1 least significant digit or ± .005% of
reading, whichever is greater.
Start/Stop/Monitor Gates:
Two identical, independent, Start, Stop or Monitor Gate circuits are provided. To
monitor operation of relay contacts or trip SCR, a continuity light is provided for
the Stop gate. Upon sensing continuity the monitor lamp will glow and a tone
generator will sound. The following modes are provided for the Start,
Stop/Monitor Gates:
1.
Timer will start, stop or continuity indicator darkens at the opening of
normally closed contacts or when conduction through a semiconductor
device such as a triac or transistor is interrupted.
2.
Timer will start, stop or continuity indicator glows at the closing of normally
open contacts or upon conduction through a semiconductor device such
as a triac or transistor.
3.
Timer will start, stop or continuity indicator glows or darkens upon the
application or removal of either an AC or DC voltage (60 to 300 Vac), (5 to
300 Vdc). The maximum voltage to be applied is 300 Volts AC or DC.
4.
Starting or Stopping with any selected output. The Timer can be started
or stopped when turning on or off selected outputs.
5.
In the Current Actuate Mode the Timer stops when output current is
interrupted.
Start Latch:
The Timer Start Gate is provided with a latch feature, which allows timing to be
initiated by a Start Gate and to be stopped only by the selected Stop Gate.
When unlatched, the Start Latch allows timing to be stopped when the Start Gate