47
RECLOSING RELAY:
From the
TEST MENU
Screen, select
RECLOSING RELAY
. The following test screen
should be displayed.
Connect relays’ reclosing and lockout contacts to
STOP/MONITOR
gate.
Connect the
RECLOSING RELAY
,
B
(Normally Closed) contacts to the relays’ breaker
sensing input (52B Contacts). Initially the 52
A
contacts are open and 52
B
contacts are
closed.
Connect
DC AUX
output to relay (for solid state or microprocessor-based).
Note: If relay is solid state, or microprocessor-based, and requires a DC logic voltage
prior to applying test, connect the relay dc power terminals to the
DC AUX
terminals.
With the arrow key, highlight the
DC VOLTS
and press the
DC
Button. Increase the DC
voltage output by rotating the Control Knob until proper logic voltage is applied.
1.
Set Reclosing Shot Count to desired value.
RECLOSE SHOT: #
is where the
user enters the number of reclose operations that the relay is set for. A maximum
of 10 reclose operations (shots) may be recorded.
2. Press
the
TIMER SETUP
Button. The following screen should appear.
3.
Select Start Option to
INITIATE
.