Drop Out Timing Test:
1.
Repeat steps 1 through 3 of the
Contact Close Timing Test
.
2. Press
the
TIMER SETUP
Button. The following screen should appear.
3.
Select Start Option to
V. REMOVED
(Voltage Applied).
4.
Select Stop Option to
N. CLOSED
(assuming Normally Closed trip contacts).
5.
Select Start and Stop Latch
ON
.
6. Press
PREV SCREEN
.
7. Press
TIMER RESET
Button. Press the
DC AUX
Button to turn the DC output
voltage OFF. The test voltage is removed, and the timer is started. When the
relay trip contacts open, the Timer Stops. Record drop out time.