METERING FUNCTIONS:
From the
TEST MENU
Screen, select
METERING
. The following test screen should be
displayed.
Function buttons allow the user to select either Amperes AC or DC and Volts AC or DC.
The METERING Screen allows the SR-98 to measure external voltage and current, as a
multi-purpose single-phase meter. AC or DC voltages up 600 Volts and AC or DC
currents up to 6 Amperes may be measured. Other measured and calculated values
are simultaneously displayed such as Phase Angle (current lags voltage), VAR, Power
and Power Factor.
Meter connections are made to the
MEASUREMENT INPUT
Terminals. When AC or
DC voltage is applied, CATII insulated test leads are required (use PN684000 and
684001 leads). When AC or DC currents are to be metered, take care not to exceed
the 6 Ampere input rating.