Specification
9
INSULATION RANGE
Insulation Resistance:
0,1
Ω
- 2000 M
Ω
(0,1
Ω
-1000M
Ω
for
MJ160
)
Nominal Test Voltages d.c:
100 V, 250 V, 500 V, 1000 V.
(
MJ160
only is 50 V, 100 V, 250 V, 500 V)
Accuracy:
250 V, 500 V, 1000 V +30%, -0% maximum
50 V, 100 V, +40%, -0% maximum
Midscale:
4 M
Ω
(2 M
Ω
for
MJ160
)
Short Circuit Current:
1,9 mA (0,65 mA for
MJ160
)
Test Voltage characteristics:
Accuracy:
±1,25% of fsd on a 2,8 in. (71,1mm) arc length: [0,035 in. (0,9mm)]
RESISTANCE RANGE
0,1
Ω
- 5000
Ω
Open circuit Test voltage:
3 V ±0,2 V
Short Circuit Current:
2 mA ±10%
Accuracy: