4)

Loop impedance value is displayed directly in  . (>2 k

displayed if

resistance exceeds 2 k

).

High Current (20 ) measurement (0,01  resolution)
This mode measures  L i v e t o E a r t h loop impedance via installation sockets  o r t h e
L i v et oE a r t h or the L i v et oN e u t r a l loop impedance using the optional dual lead test
set. N o t e: This mode may cause RCDs to trip. The measurement sequence takes 
5 seconds. 
1 )

Turn rotary switch to ‘ 2 0   ’.

2 )

Connect 

LT7

by mains cord, or using the dual test lead firmly connect

red test probe to Live and the black test probe to Neutral or to
Protective Earth (ground). Mains (line) voltage is displayed.

3 )

Test progress is indicated by a sequential display of vertical bars. 

4 )

Loop impedance value is displayed directly in  .   N o t e : Any measurement
<0,01

 will cause the display to flash, and should be investigated.  (>20 

displayed if resistance exceeds 20

).

High Current (PSCC) m e a s u r e m e n t
In this mode, 

LT7 

displays the Prospective Short Circuit Current (calculated at the

nominal supply voltage of 230V divided by loop impedance). This mode can be used
for L i v e to Earth connection via unprotected installation sockets, o r for Live to E a r t h ,
o r L i v e to Neutral connection on unprotected circuits using the optional lead set. T h i s
mode may cause RCDs to trip. The measurement sequence takes   5 seconds. 
1)

Turn rotary switch to ‘PSCC’.

2)

Plug in the

LT7

, or firmly connect red test probe to Live and black

test probe to Protective Earth (ground) or to Neutral. Mains (line)
voltage is displayed.

3)

Test progress is indicated by a sequential display of vertical bars. 

4)

PSCC value displayed directly in kA. (>20kA displayed if value
exceeds 19,9kA).

Earth Bond Testing
By using the earth bond test lead available as an optional extra, the

LT7

can measure the quality of Equipotential bonding within an installation.
1) 

Turn rotary switch to ‘Auto’ or ‘20 ’.

2) 

Firmly connect the flying lead probe to the metalwork to be tested
and plug the 

LT7

into a convenient installation socket. 

3)

Reading displayed will consist of socket supply (live conductor)
impedance plus the impedance of the equipotential earth bonding.

SPECIFICATION

Ranges:
20  (23Anominal)

0,01

 - 19,9

 ±2% ±3 digits (230 V supply)

±5% ±6 digits (110 V supply)

200 /2k  (15mAnominal) 1

 -1,99k

 

±2% ±1 digit (230 V supply)
±5% ±2 digits (110 V supply)

When set to 0,1 

 resolution

±2% ±3 digits (230 V supply)
(±3 digits  at 1

σ

typical)

PSCC (23Anominal)

0,01 - 0,99 kA
1,0 - 19,9 kA

Note: Calibration includes the test leads and plug. To maintain accuracy,
these must not be changed. See note overleaf.

Nominal System Voltage: 110 V / 230 V at 50 Hz

Voltage Accuracy:

±2% ±2 digits (when L-PE neon indicates).

Power supply:

4 x 1,5 V Alkaline cells  IEC LR6 type 

or 

4 x 1,2 V NiCd or NiMHrechargeable cells

Auto shut off:

After 5 minutes of instrument inactivity 

Battery life: 

Typically 1200, one minute tests

Low Battery Indicator:

The 

symbol will appear when A l k a l i n e

battery cells are almost exhausted.

Note: Battery cells should not be left in an instrument which may remain
unused for extended periods of time.

Summary of Contents for LT7

Page 1: ...fied before carrying out an earth fault loop impedance test Exposed metalwork of an installation or equipment under test must not be touched LT7 must not be connected across two phases of a 3 phase su...

Page 2: ...short circuit current A special range is provided to carry out loop measurement on installations protected by Residual Current Devices 30mAwithout causing the breaker to trip out The resolution in thi...

Page 3: ...s are reversed N PE neon activated 2 Neutral Earth voltage 50 V when performing a 3 wire test L PE and N PE neons activated 3 Electrical noise exceeds rejection level on low current range displayed 4...

Page 4: ...t probe to Protective Earth ground or to Neutral Mains line voltage is displayed 3 Test progress is indicated by a sequential display of vertical bars 4 PSCC value displayed directly in kA 20kA displa...

Page 5: ...ted instrument with a clean cloth dampened with soapy water or Isopropyl Alcohol IPA ACCESSORIES Supplied Part number User Guide 6172 087 Power cord test lead with 3 pin plug to BS1363 A 6231 601 or P...

Page 6: ...8579 Fax 44 0 1304 207342 Fax 1 610 676 8625 or an approved repair company Returning an Instrument for Repair If returning an instrument to the manufacturer for repair it should be sent freight pre p...

Page 7: ...indicateur de tension N PE Neutre Terre est activ Des mesures r p t es peuvent tre effectu es soit en d connectant puis en reconnectant l instrument par exemple lors de l utilisation de sondes de tes...

Page 8: ...e l interrupteur rotatif sur 20 2 Brancher le LT7 ou connecter fermementle capteur de test rouge sur Phase et le capteur de test noir sur Neutre ou sur Terre de Protection terre La tension du secteur...

Page 9: ...smessungen k nnen entweder durch Abnehmen und Wiederanschlie en des Instruments an die Installation z B wenn Pr fsonden verwendet werden oder durch Bet tigen des Wiederholungspr fknopfes Retest durchg...

Page 10: ...7 ein oder schlie en die rote Pr fsonde fest an Spannungsf hrend und die schwarze Pr fsonde an die Schutzerdung Erde oder Neutral an Netzspannung Leitung wird angezeigt 3 Der Pr fverlauf wird durch di...

Page 11: ...camente una medici n Los cables de prueba terminados en un enchufe de dos patillas deber n invertirse si s lo se activa el indicador de tensi n N PE Pueden realizarse mediciones repetidas bien sea des...

Page 12: ...o conectar firmemente la sonda de prueba roja al Conductor con corriente y la sonda de prueba negra al Neutro o a Tierra Protectora masa Se visualiza la tensi n de la red l nea 3 La marcha de la prue...

Reviews: