background image

32

DELTA 4000 

ZM-AH02E

3 TESTING POWER SYSTEM COMPONENTS

smaller than any other type of  circuit-breaker of  equivalent 

power and are far less noisy than air circuit-breakers.

Test connections

Test setup is essentially the same for all live tank circuit 

breakers. Additional Hot-Collar tests may be conducted on 

breakers equipped with gas-filled bushings to detect internal 

contamination or exterior cracks and other problems that 

may have occurred along the surface of  the bushing. See 

also section bushing testing.
Connect a ground wire from the test set to the grounded 

frame of  the breaker.

1] 

Connect the high voltage lead to the main conduc-
tor lug of the bushing under test. Ensure that the 
cable extends out away from the bushing and does 
not rest on the porcelain.

2] 

Connect the low voltage lead to the test tap if 
available. Refer to previous discussion on test taps. 
Both the overall GST test and the C

UST test can 

be performed without a lead change.

Test procedure

 

Tests are performed at 2.5kv or 10kv or a voltage suitable 
for the insulation.

 

Tests 1 - 9 are conducted with the breaker open. Tests 10 
- 12 are conducted with the breaker closed.

 

Some breaker designs have internal insulators to support 
other linkage and apparatus inside the tank.

The closed breaker tests verify the insulation integrity of  

these components.
Identify each set of  readings with the apparatus and/or 

bushing serial number. Record the manufacturer, type, style, 

model and other nameplate ratings. Note any special or 

unusual test connections or conditions.

1] 

Measure actual test voltage, current, watts, power 
factor and capacitance. Correct current and watts 
to a standard test voltage 2.5kv or 10kv if neces-
sary.

2] 

Record ambient temperature and relative humidity 
and a general indication of weather conditions at 
the time of the test.

3] 

If the C1 test is performed on the bushings, correct 
power factor readings to 20°C.

Test results

High watts loss and power factor results on tests 1 - 6 and 

10 - 12 could be related to an excess of moisture on the 

internal apparatus. If  moisture is the problem, opening 

and closing the breaker several times in succession could 

improve the test results.

The results of the UST measurements in tests 7 - 9 are 

meaningful to breakers that have grading capacitors across 

the contacts. High capacitance’s compared to similar tests 

may be the result of short-circuited sections in one or more 

of  the grading capacitors .

Vacuum circuit breakers

These circuit-breakers operate on a different principle from 

other breakers because there is no gas to ionize when the 

contacts open. They are hermetically sealed; consequently, 

they are silent and never become polluted. Their interrupt-

ing capacity is limited to about 30kv. For higher voltages, 

several circuit-breakers are connected in series. Vacuum 

circuit-breakers are often used in underground systems.

Test connections

Connections are the same as for dead-tank oil breakers. 

Additional Hot-Collar tests may be performed on suspect 

bushings that have unusually high losses.
Connect a ground wire from the test set to the grounded 

frame of  the breaker.

1] 

Connect the high voltage lead to the main con-
ductor lug of the bushing under test. Ensure that 
the cable extends out away from the bushing and 
does not rest on the porcelain. All other bushings 
should float.

2] 

Connect the low voltage lead to the test tap if 
available. Refer to the previous discussion on test 
taps.

Both the overall GST test and the C

UST test can be per-

formed without a lead change.

Test procedure

Tests are performed at 2.5kv or 10kv or a voltage suitable 

for the insulation. All tests are performed with the vacuum 

breaker in the open position. Tests 1 - 6 are conducted in 

the GST mode and tests 7 - 9 are in the UST mode.

Identify each set of  readings with the apparatus and/or 

bushing serial number. Record the manufacturer, type, style, 

model and other nameplate ratings. Note any special or 

unusual test connections or conditions.

1] 

Measure actual test voltage, current, watts, power 
factor and capacitance. Correct current and watts 
to a standard test voltage 2.5kv or 10kv if neces-
sary.

2] 

Record ambient temperature and relative humidity 
and a general indication of weather conditions at 
the time of the test.

If  the C1 test is performed on the bushings, correct power 

factor readings to 20°C.

Test results

Charging currents are expected to be small. Under dry 

ambient conditions, power factor results will be small and 

dielectric losses close to zero. Higher than normal UST 

measurement could be due to a defective vacuum bottle 

allowing moisture to enter or surface leakage across the vac-

uum housing. Clean the surface of the vacuum bottle and 

retest. Ensure all cabinet heaters are working to maintain a 

sufficient temperature surrounding the vacuum bottles.

Summary of Contents for DELTA 4000

Page 1: ...WWW MEGGER COM Reference Manual Applications Guide DELTA4000 12 kV Insulation Diagnostic System ZM AH02E Advanced Test Equipment Rentals www atecorp com 800 404 ATEC 2832 Established 1981...

Page 2: ......

Page 3: ...f this document However the information contained in this manual is subject to change without notice and does not represent a commitment on the part of Megger Sweden AB Any attached hardware schematic...

Page 4: ...nsformer excitation current tests 19 Shunt reactors 21 Potential transformers 21 Current transformers 21 Voltage regulators 21 Dry type transformers 22 Bushings 22 Introduction 22 Definitions 22 Bushi...

Page 5: ...ZM AH02E DELTA4000 5...

Page 6: ...HV terminal and the current is measured at the LV terminal Voltage and current are accurately measured in amplitude and phase and CHL capacitance dissipation factor power loss etc are calculated and d...

Page 7: ...phase angle q q 90 It is more convenient to use the dielectric loss angle d where d 90 q For low power factor insulation Ic and I are substantially of the same mag nitude since the loss component Ir...

Page 8: ...internal measure ment connections UST Ungrounded specimen testing Test mode Measure Ground Guard UST R Red Blue UST B Blue Red UST RB Red and Blue GST Grounded specimen testing Test mode Measure Grou...

Page 9: ...ZM AH02E DELTA4000 9 1 Introduction...

Page 10: ...lar types of insulation used Changes in the normal capacitance of an insulation material indicate such abnormal conditions as the presence of a moisture layer short circuits or open circuits in the ca...

Page 11: ...factor values Typical power factor values 20 C New Old Warning alert limit Power trans formers oil insulated 0 2 0 4 0 3 0 5 0 5 Bushings 0 2 0 3 0 3 0 5 0 5 IEEE 62 1995 states The power factors reco...

Page 12: ...ielectric loss which in turn causes a further rise in temperature etc thermal runaway It is important to determine the dissipation factor tempera ture characteristics of the insulation under test Othe...

Page 13: ...may be contaminated enough to cause a signifi cant error Surfaces of potheads bushings and insulators should be clean and dry when making a measurement It should be noted that a straight line plot of...

Page 14: ...to the test specimen Other sources for interference may be corona discharges espe cially at high humidity and is some cases DC fluctuations in the grounding system Trouble from magnetic fields encoun...

Page 15: ...ZM AH02E DELTA4000 15 2 Interpretation of measurements...

Page 16: ...its from each other and it can increase or decrease the apparent value of a capacitor an inductor or a resistor Furthermore the transformer enables us to transmit electrical energy over great distance...

Page 17: ...applying any voltage on the transformer make sure that all bushing current transformers are shorted out 4 Never perform electrical tests of any kind on a unit under vacuum Flashovers can occur at volt...

Page 18: ...additional tests of the tertiary winding In some cases transformers are constructed so that the inter windings are shielded by a grounded electrostatic shield or a concentric winding arrangement This...

Page 19: ...e Subscripts are test num bers H High voltage winding L Low voltage winding T Tertiary winding G Ground Autotransformers In the design of an autotransformer the secondary winding is actually part of t...

Page 20: ...nd on wye connected transformers Also note that in many cases the maximum applied voltage is limited by the maximum current output Test voltage must always be the same as prior tests if any comparison...

Page 21: ...tial transformer is securely grounded to a system ground before testing begins this also includes testing of spare transformers Test procedure Ensure the test set is securely grounded 1 Record all tes...

Page 22: ...handle high electrical stress they could be subjected to mechanical stresses affiliated with connectors and bus support as well Although a bushing may be thought of as somewhat of a simple device its...

Page 23: ...e the space between the core and the insulating envelope being filled with oil Resin bonded paper insulated bushing A bushing in which the internal insulation consists of a core wound from resin coate...

Page 24: ...ual inspection Power factor Tan delta test Hot collar test Dete rioration of cemented joints Moisture enters Oil and or gas leaks Filler leaks out Visual inspection Power factor Tan delta test Hot col...

Page 25: ...e plate voltage rating of the bushing under test If 10kV exceeds the rating of the bushing test at or slightly below the voltage rating 3 Proceed with the test and record the results 4 Identify each s...

Page 26: ...5kV to prevent inadvertent damage to the insulation An excessive voltage may puncture the insulation and render the tap useless Some bushings do not have a power factor or capacitance tap or an isola...

Page 27: ...y and Surface Leakage if tests are made under unfavorable weather conditions Test connections GST Connect a ground wire between the test set and the host apparatus for the bushing under test 1 Install...

Page 28: ...rminal in that phase should be guarded It is also desirable to test samples of the liquid insulation Oil circuit breakers Oil circuit breakers are composed of a steel tank filled with insulating oil A...

Page 29: ...uld be recorded on the test form Enter all the nameplate information of the oil circuit breaker Identify each set of readings with the bushing se rial number Record manufacturer type or model and othe...

Page 30: ...loss indexes without the unit being defec tive or deteriorated The losses in an oil circuit breaker are different between an open circuit test and a closed circuit test because the voltage stress on t...

Page 31: ...rounded Test procedure Tests are performed at 10kV or a voltage suitable for the insulation rating 1 All tests are conducted with the breaker in the open position 2 Identify each set of readings with...

Page 32: ...s High capacitance s compared to similar tests may be the result of short circuited sections in one or more of the grading capacitors Vacuum circuit breakers These circuit breakers operate on a differ...

Page 33: ...voltage or slightly above rated voltage The tip up value is obtained by subtracting the value of the dissipation factor measured at the lower test voltage from that measured at the higher test voltage...

Page 34: ...t at the winding surface Avoid prolonged exposure to high humidity conditions before testing because such exposure may result in moisture absorption in the insulating materials It is desirable to make...

Page 35: ...s such as thyrite autovalve etc This material has a resistance that decreases dramatically with increasing volt age Arresters are effectively switching devices that serve as an insulator under normal...

Page 36: ...dependent non linear may be built into an arrester Except for the specific purpose of investigation surface leak age the exposed insulation surface of an arrester should be clean and dry to prevent le...

Page 37: ...ate contact is made with the critical areas of the insulation Pe troleum jelly or Dow Corning 4 insulating grease applied at the interface surface often helps to obtain better physical contact It may...

Page 38: ...imen Test The capacitance value from this test is C1 Figure 14 TTR Capacitor measurement The second step of the procedure is to connect the test set and the HV TTR Capacitor to the transformer winding...

Page 39: ...ZM AH02E DELTA4000 39 3 Testing power system components that no temperature change has occurred and the trans former ratio determined by this method is correct...

Page 40: ...nce 14 H High Voltage turns ratio measurements 38 Hot collar test 27 Humidity 13 I IEEE 62 1995 power factor values 11 Insulating envelope 23 Internal insulation 23 Interpretation of measurements 10 I...

Page 41: ...nnections 36 Surge lightning arresters 35 T Temperature 12 Testing power system components 16 Three winding transformers 18 Transformer excitation current tests 19 Transformers 16 Two winding transfor...

Page 42: ...eactors IEEE New York 1995 2 US Bureau of Reclamation Transformer Diagnos tics Facility instructions standards and techniques Vol 3 31 2003 3 US Bureau of Reclamation Testing and Mainte nance of High...

Page 43: ...ZM AH02E DELTA4000 43...

Page 44: ...TYPES S SI SM TYPE U 0 32 0 1 09 0 93 1 00 1 18 1 26 1 02 1 33 8 1 09 0 94 1 00 1 17 1 25 1 02 2 35 6 1 09 0 95 1 00 1 16 1 24 1 02 3 37 4 1 09 0 96 1 00 1 15 1 22 1 02 4 39 2 1 09 0 97 1 00 1 15 1 2...

Page 45: ...59 0 1 00 0 95 1 12 1 03 16 60 8 1 00 17 62 6 1 00 18 64 4 1 00 19 66 2 1 00 20 68 0 1 00 1 00 1 00 1 00 21 69 8 1 00 22 71 6 1 00 23 73 4 1 00 24 75 2 1 00 25 77 0 1 00 1 04 0 89 0 97 26 78 8 1 00 2...

Page 46: ...46 DELTA4000 ZM AH02E...

Page 47: ...ZM AH02E DELTA4000 47...

Page 48: ...d Dover CT17 9EN England T 44 0 1304 502101 F 44 0 1304 207342 E UKsales megger com Other Technical Sales Offices Dallas USA Toronto CANADA Trappes FRANCE Oberursel GERMANY Oberkulm SWITZERLAND Johann...

Reviews: