22
DELTA 4000
ZM-AH02E
3 TESTING POWER SYSTEM COMPONENTS
Dry-type transformers
Testing notes
Test voltages should be limited to line-to-ground ratings
of the transformer windings. Insulation power factor tests
should be made from windings to ground and between
windings. Temperature at the time of testing should be at
or near 20°C. ANSI/IEEE C57.12.91 - 1997 recommends
correcting results other than 20°C. However, there is very
little data available for temperature correction of dry-type
transformers. Repeat tests should be performed as near as
possible, in the same conditions as the original test.
Higher overall power factor results may be expected on dry-
type transformers. The majority of test results for power
factor is found to be below 2.0%, but can range up to 10%.
The insulation materials necessary for dry-type construc-
tion, must meet the thermal and stress requirements.
If power factor results appear to be unacceptable, an ad-
ditional Tip-Up Test can be performed if a 10kV test set
is used. This test can be performed to evaluate whether
moisture or corona is present in the insulation system.
The applied test voltage is varied starting at about 1kV and
increased in intervals up to 10 kV or the line-to-ground rat-
ing of the winding insulation. If the power factor does not
change as the test voltage is increased, moisture is suspected
to be the probable cause. If the power factor increases as
the voltage is increased, carbonization of the insulation or
ionization of voids is the cause.
Note
DELTA 4000 has a specific feature where the
test set recognizes voltage dependence and
will automatically indicate a non-linear behav-
ior and by this indicate to the user to perform
a tip-up test
Bushings
Introduction
Bushings provide an insulated path for energized conduc-
tors to enter grounded electrical power apparatus. Bushings
are a critical part of the electrical system that transforms
and switches ac voltages ranging from a few hundred volts
to several thousand volts. Bushings not only handle high
electrical stress, they could be subjected to mechanical
stresses, affiliated with connectors and bus support, as well.
Although a bushing may be thought of as somewhat of a
simple device, its deterioration could have severe conse-
quences.
All modern bushings rated 23 kV and higher have a power
factor or a capacitance tap which permits dissipation factor
testing of the bushing while it is in place on the apparatus
without disconnecting any leads to the bushing. The dis-
sipation factor is measured by the ungrounded specimen
test (UST) which eliminates the influence of transformer
winding insulation, breaker arc-interrupters, or support
structures which are connected to the bushing terminal.
Figure 11 shows the test connections between the test set
and bushing when using the UST test mode.
1]
Connect test ground to apparatus ground.
2]
Connect the high-voltage lead to the terminal at
the top of the bushing and the low-voltage lead
(red) to the power factor tap.
3]
Ground the apparatus tank. The tap is normally
grounded through a spring and it is necessary,
when making measurements, to remove the
plug which seals and grounds the tap. Use the
UST measure red, ground blue test mode setting
(UST-R).
The UST test also can be used for making measurements
on bushings which have provisions for flange isolation. The
normal method of isolating the flange from the apparatus
cover is to use insulating gaskets between the flange and
cover and insulating bushings on all but one of the bolts
securing the mounting flange to the cover. During normal
operation, the flange is grounded by a single metal bolt;
however, when testing the bushing, this bolt is removed.
The measurement is identical to that when testing bushings
which have a power factor tap except that the low-voltage
lead, red in this case, is connected to the isolated bushing
flange.
Definitions
Bushing voltage tap
A connection to one of the conducting layers of a capac-
itance graded bushing providing a capacitance voltage divid-
er. Note: additional equipment can be designed, connected
to this tap and calibrated to indicate the voltage applied to
the bushing. This tap can also be used for measurement of
power factor and capacitance values.
Summary of Contents for DELTA 4000
Page 2: ......
Page 5: ...ZM AH02E DELTA4000 5...
Page 9: ...ZM AH02E DELTA4000 9 1 Introduction...
Page 15: ...ZM AH02E DELTA4000 15 2 Interpretation of measurements...
Page 43: ...ZM AH02E DELTA4000 43...
Page 46: ...46 DELTA4000 ZM AH02E...
Page 47: ...ZM AH02E DELTA4000 47...