background image

6

2. Safety and Inspection

Meech Cabinet Coolers are packed carefully at our factory. Nevertheless, we 
recommend careful examination of the carton and contents for any damage. 

To protect yourself and others when using compressed air, you should be aware of the 
following general safety guidelines: 

 

„

Warning – When compressed air is misused, it can cause serious injury or    
even death. 

 

„

Never point an air hose at anyone in fun or to remove dirt from clothing or the  
body. 

 

„

Never use compressed air without adequate eye and ear protection. Use    
safety glasses with side shields or goggles and ear protectors. 

 

„

Before attempting to disconnect a hose from an air line, the air should be cut  
off, and the remaining air bled from the line. 

 

„

Keep air hoses off the floor where they become tripping hazards and are    

subject to damage by vehicles, doors, and dropped tools. If possible, suspend air 
hoses from overhead.

Please be aware of the following safety guidelines specific to the Cabinet Cooler:

 

 

„

Cabinet Coolers create both hot and cold air so parts of the unit will become hot.  

 

„

Do not operate the Cabinet Cooler at compressed air pressures above 11 Bar  
(160 psi) 

 

„

Compressed air temperature must not exceed 55°C 

 

„

Ambient operating temperature must not exceed 66°C 

 

„

Ambient operating temperature can not drop lower than -10°C 

Summary of Contents for A70000

Page 1: ...1 Cabinet Cooler Cabinet Cooler System Operating Manual...

Page 2: ......

Page 3: ...ion please refer to our Head Office or visit www meech com Meech Static Eliminators Ltd Contents Section Page 1 Introduction 5 2 Safety and Inspection 6 3 Maintenance 7 4 Compressed Air Supply 9 5 Com...

Page 4: ......

Page 5: ...and Thermostat is intrinsically safe and requires virtually no maintenance They have no moving parts making them ideal for harsh environments Cabinet Coolers can be used with or without electrical the...

Page 6: ...th side shields or goggles and ear protectors Before attempting to disconnect a hose from an air line the air should be cut off and the remaining air bled from the line Keep air hoses off the floor wh...

Page 7: ...the compressed air supply This could hinder the performance If this happens simply take the unit apart clean the parts with soapy water allow drying time and then reassemble When reassembling ensure y...

Page 8: ...D50088 Silencer Spring 1 8 A D50040 Silencer Foam 1 9 A D50094 Plastic Insert 1 10 D50153 Star Washer 1 11 A D50036 Bulk Head Washer 1 12 B D50033 Bulkhead Nut 33mm 1 13 A D50075 O Ring 17x3mm 1 17 A...

Page 9: ...ure to use a filter may cause clogging and freezing of the compressed air line and the components within the Cabinet Cooler When the temperature of the compressed air within the Cabinet Cooler reaches...

Page 10: ...ere is any doubt that a pipe size may create a pressure drop use the next largest size Remember that an oversize pipe compensates for possible scale build up and provides for future expansion of the o...

Page 11: ...nd use this number to determine the PIPE SIZE you need Specific Cabinet Cooler Pipe Size To obtain maximum performance from the Cabinet Cooler accurate measures of air pressure and air volume must be...

Page 12: ...2 1 1 2 2 2 2 2 225 1 1 2 1 1 2 1 1 2 1 1 2 2 2 2 2 250 2 2 2 2 2 2 2 2 275 2 2 2 2 2 2 2 1 2 2 1 2 300 2 2 2 2 2 2 2 1 2 2 1 2 350 2 2 2 2 2 1 2 2 1 2 2 1 2 2 1 2 400 2 2 2 2 2 1 2 2 1 2 2 1 2 2 1 2...

Page 13: ...t Cooler To fit the Cabinet Cooler follow the steps below A Drill Hole Drill 1 02 26 mm hole in the position you would like to fit the Cabinet Cooler Please be aware that 200mm of the Cabinet Cooler w...

Page 14: ...Refrig 15cfm 293W 1000 Btu hr generator To change the generator simply unscrew the bulk head fitting and replace the generator with another colour Please remember to re fit the o ring and screw bulk h...

Page 15: ...the cold air ducting can be directed to particularly hot areas of the enclosure Alternatively you can drill holes in the cold air ducting and allow air to be distributed to several areas If you choos...

Page 16: ...temperatures and should only be used as a guide The Cabinet Cooler will perform differently when used in other environments Inlet air pressure Product Code Generator Colour Consumption in CFM l min 6...

Page 17: ...pacity of 703W 2 400 Btu hr A single Meech Cabinet Cooler is capable of cooling up to 703 Watts 2 400 Btu hr Optimising the cooling capacity is still a vitally important factor choosing the correct ge...

Page 18: ...ly 45 To prevent condensation forming on the cold air pipe close off any vents or fan outlets on the outside wall of the enclosure This reduces the ambient air from circulating within the cabinet pane...

Page 19: ...stment of Meech Factory settings The thermostat is password protected to stop adjustment of the parameters The following 3 steps explain how to unlock the thermostat for parameter adjustment 1 Power u...

Page 20: ...e main toggle menu 4 Using the 2 arrow buttons toggle through the parameters until you reach HSEt 5 When you have reached HSEt press the P button once This allows you to adjust the differential of coo...

Page 21: ...er is IP56 Nema 4 12 The Cabinet Cooler unit is issued in accordance with Directive 94 9 EC ATEX Equipment and protective Systems Intended for use in Potentially Explosive Atmospheres A Declaration of...

Page 22: ...or size for fitting Cabinet Cooler Air Temperature Problems with air temperature can be caused by 1 Incorrect generator fitted Check and replace generator see section 7 2 Ambient compressed air temper...

Page 23: ......

Page 24: ...H 44203 USA Tel 1 330 564 2000 1 800 232 4210 Fax 1 330 564 2005 email info meech com Meech Static Eliminators Shanghai Co Ltd 7G 7F LP Tower 25 Xiangfeng Road 201103 Shanghai China Tel 86 400 820 010...

Reviews: