DM16-01.01.06en
MIV V5 Individual DC Inverter R410A
6
Specifications & Performance
ESP
Pa
0-20 (default)
Pa
20-40 (customized)
Outdoor coil
Number of rows
2
Tube pitch(a)×
row pitch(b)
mm
22×19
Fin spacing
mm
1.6
Fin type
Hydrophilic fin
Tube outside
diameter
mm
7.94
Tube type
Inner thread tube
Coil dimension
(W×H×D)
mm
3135×1232×38
3504×1232×38
3504×1232×38
Number of circuits
inlet:28; outlet:28
inlet:52; outlet:33
inlet:52; outlet:33
Outdoor air flow
m
3
/h
20000
23000
23000
Sound pressure level
dB(A)
62
63
63
Connectable
indoor unit
Total capacity
%
50-130
Max. quantity
33
36
39
Outdoor unit
Net dimension
(W×H×D)
mm
1390×1615×765
1585×1615×765
1585×1615×765
Packing
(W×H×D)
mm
1455×1790×830
1650×1810×840
1650×1810×840
Net/Gross
weight
mm
360/375
385/400
390/405
Refrigerant
Type
R410A
Factory
charged
kg
17
18.5
18.5
Throttle type
EXV
Design pressure (Hi/Lo)
MPa
4.4/2.6
Refrigerant
piping
Liquid pipe
mm
Φ19.1
Gas pipe
mm
Φ31.8
Ambient temp.
range
Cooling
o
C
-5~48
Heating
o
C
-20~27
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27
o
C DB/19
o
C WB; Outdoor temperature 35
o
C DB/24
o
C WB.
Heating: Indoor temperature 20
o
C DB/15
o
C WB; Outdoor temperature 7
o
C DB/6
o
C WB.
Piping length: Interconnecting piping length 7.5m, level difference of zero.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.
The above data may be changed without notice for future improvement on quality and performance.