DM16-01.01.06en
MIV V5 Individual DC Inverter R410A
8
Specifications & Performance
ESP
Pa
0-20 (default)
Pa
20-40 (customized)
Outdoor coil
Number of rows
2
Tube pitch(a)×
row pitch(b)
mm
22×19
Fin spacing
mm
1.6
Fin type
Hydrophilic fin
Tube outside
diameter
mm
7.94
Tube type
Inner thread tube
Coil dimension
(W×H×D)
mm
(2141×1232×19+2081×1232×19)×2
Number of circuits
(inlet:22; outlet:20)×2
Outdoor air flow
m
3
/h
33100
Sound pressure level
dB(A)
64
64
65
65
Connectable
indoor unit
Total capacity
%
50-130
Max. quantity
43
46
50
53
Outdoor unit
Net dimension
(W×H×D)
mm
2540×1615×765
Packing
(W×H×D)
mm
2600×1800×825
Net/Gross weight
mm
555/590
555/590
600/635
600/635
Refrigerant
Type
R410A
Factory charged
kg
27
Throttle type
EXV
Design pressure (Hi/Lo)
MPa
4.4/2.6
Refrigerant
piping
Liquid pipe
mm
Φ22.2
Gas pipe
mm
Φ38.1
Ambient
temp.
range
Cooling
o
C
-5~48
Heating
o
C
-15~24
Notes:
Capacities are based on the following conditions:
Cooling: Indoor temperature 27
o
C DB/19
o
C WB; Outdoor temperature 35
o
C DB/24
o
C WB.
Heating: Indoor temperature 20
o
C DB/15
o
C WB; Outdoor temperature 7
o
C DB/6
o
C WB.
Piping length: Interconnecting piping length 7.5m, level difference of zero.
Sound values are measured in a semi-anechoic room, at a position 1m in front of the unit and 1.3m above the floor.
The above data may be changed without notice for future improvement on quality and performance.