2

 

 

System description

 

SEC-K 

Multi gas detection, air quality monitor, fan interlock and gas pressure proving system 

 

The SEC-K is a gas pressure proving system with electric isolation, gas detection and ventilation interlock. By monitoring the carbon dioxide and 
temperature the system can control ventilation levels where required. It is designed for use primarily in commercial kitchens.  
The system comprises of a mains powered panel capable of operating a mix of up to 16 devices of different types. The device types are, carbon 
dioxide, carbon monoxide, combustible gases, oxygen depletion and temperature.   
The system will perform a down stream integrity check ensuring gas tightness before use, close the gas solenoid valve in the event of a high-level 
gas alarm or ventilation failure, low incoming gas pressure or if the emergency stop button is pressed. 

 

Control Panel 

the front of the panel has the following controls and indications: 

 

Emergency stop button 
key switch 
On/off buttons for gas and electric 
Blind button 

A

 and 

B

 

 

LED indications: 

 

Power On - green………...

A

 blind button for displaying gas pressures on the LCD screen 

Gas/Electric - red 
Fans running light – yellow….

blind button for displaying connected devices (detectors & temperature) on the LCD screen 

 

LCD display: 

 

For displaying system status during both installation and normal use, also for displaying diagnostics 

Other points to note 
The maximum cable length between a detector  and the control panel should not exceed 100 metres, If the distance between the 
main panel and the detectors is greater than 20metres 1mm cable should be used on the +VE, 0v terminals. 
 
Pressure Sender Unit Mounting. This has an inlet and an outlet port (1/4 inch NPT). The inlet must be connected to the inlet test point 
on the  solenoid valve (see fitting kit page) and the outlet port after the solenoid valve typically using 8mm OD copper pipe. Use the 
appropriate Medem fitting kit to fit the control valve size. The pressure sender is connected to the control panel with low voltage two 
core cable using the terminal marked A & B.  NOTE: This is low voltage and should be segregated from mains wiring. 

INS/1017/002 

System On/Off enables gas detection and use 
of each service button 

A                                        B 

A

 Blind button for displaying gas pressures on the LCD screen 

Blind button for displaying first 8 detectors (Gas & temperature) on the LCD screen.  

    Press 

A

 & 

B

 together to display second set of 8 detectors.

 

    (

Press button 

B

 3 times in quick succession to enable fire test mode see page 4)

 

Summary of Contents for SEC-K

Page 1: ...The Home of Control Automation in Ireland SEC K Multi Function Control System for Kitchens...

Page 2: ...use Each services can be individually controlled using the tactile buttons on the panel with overall secure isolation provided by the main on off switch Gas detectors for carbon dioxide and temperatur...

Page 3: ...by testing for leaks and open appliances before allowing gas available by using Medem patented true differential gas pressure measuring across the solenoid valve This eliminates nuisance tripping of t...

Page 4: ...Gas Pressure Proving Using the patented differential pressure proving method the SEC K can test for low pressure natural LPG gas pipe work or can pressure prove a variety of gas delivery lines includ...

Page 5: ...d extra low voltage The connections marked CM2 or PD switches are for the connection of a current monitor or pressure switches for interlocking fans with the gas supply The connections marked detector...

Page 6: ...13 Fire alarm input signal N C contact required 14 0 10 volt output to fan speed controllers based on CO2 and temperature levels 15 Two relays for connection to a BMS to indicate high alarm gas on EM...

Page 7: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Page 8: ...pur 230v EM Stop Buttons TT 70c Series connected Addressable Gas detector Addressable Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v ou...

Page 9: ...a Medem engineer this can be increased to 10 years and includes a 24hr helpline During the commissioning process a Medem engineer would attend site to ensure full and correct operation of the supplie...

Page 10: ...nough to ensure the downstream pipe work comes up to pressure factory default 5 seconds The prove time should be set at installation to find the smallest possible leak factory default 50 seconds To te...

Page 11: ...ational test on any installed Emergency stop buttons which when operated will isolate the gas supply and remain isolated until a manual reset is completed If utilized an auto stop time out will isolat...

Page 12: ...r Medem UK should commission this safety system whereupon a commissioning report will be forwarded to the installing agent who should provide a copy to the end user At the point of our commissioning a...

Page 13: ...ing light yellow B blind button for displaying connected devices detectors temperature on the LCD screen LCD display For displaying system status during both installation and normal use also for displ...

Page 14: ...evels 15 Two relays for connection to a BMS to indicate high alarm gas on EM stop low alarm One selectable for each relay 16 OPTA Over pressure check will isolate gas supply if pressure exceeds 70 mba...

Page 15: ...sing button 22 This will bypass the ventilation interlock allowing the gas to be tested the system must not be left in this state and as such is only this for a maxim 24hour period but auto exiting Wh...

Page 16: ...s Connect multiple detector in parallel fans Medem CM2 2 channel current Monitor 6 core low voltage 1 x 12v fans Fan speed controls Fan Supply 6 core low voltage cable Earth Connections not shown Fan...

Page 17: ...present within the panel N L To Contactor Coil Method 2 IMPORTANT If wired this way a warning notice must be attached to the panel to indicate that there are two separate mains feeds L N Supply in Co...

Page 18: ...ble Gas detector 6 core low voltage cable Sender unit Mounts on the gas valve Requires a volt free NC contact 0 10v output for connecting to a fan speed controller fans Medem CM2 2 channel current Mon...

Page 19: ...ections in the panel TB2 TB1 TB3 Use terminals TB2 A and TB2 C TB2 TB1 TB3 Use terminals TB2 A and TB2 C Multiple Switches Wire in series Remote stop buttons can be connected to the panel terminal mar...

Page 20: ...alled so they monitor the general level of CO2 within the cooking area They should be mounted above standing head height and between 1m and 3m from the cooking line Care should be taken so they are no...

Page 21: ...Limited Otter House Naas Road Clondalkin Dublin 22 Tel 00353 1 461 4300 E sales modernplant ie W www modernplant ie Please do not hesitate to call for advice on the following number 00353 1 461 4300...

Page 22: ...Correct Incorrect Incorrect Never mount the valve such that the Solenoid or Sender Unit are below the horizontal In addition check that the valve is correctly installed with regard to the direction o...

Page 23: ...IT ON VALVE WALL MOUNTING STRAP PRESSURE SENDER UNIT NOTES Solenoid coil of the valve should never be mounted below the horizontal Pressure sender unit should never be mounted upside down to protect f...

Page 24: ...safety product range Both companies work closely to ensure the products remain best in class We stock a comprehensive range of Haws AG emergency equipment We also supply special models to the highest...

Reviews: