CB-7080 & CB-7080D Counter/Timer User's Guide
@AADA
2-42
@AADA
Description
: Disable alarm (for alarm-mode 1). Refer to "
Counter alarm mode selection
" for more
information.
Syntax
: @AADA[chk](cr)
@
A delimiter character
AA
2-character HEX module address, from 00 to FF
DA
[chk]
2-character checksum. If checksum is disabled, no [chk]
(cr)
0x0D
Response
:
Valid response
!AA[chk](cr)
Invalid response
?AA[chk](cr)
no response
Syntax error, communication error or address error
!
A delimiter character indicating a valid response
?
A delimiter character indicating an invalid response
AA
2-character HEX module address
[chk]
2-character checksum. If checksum is disabled, no [chk]
(cr)
0x0D
Examples
:
Disable the alarm for module 1:
command:
@01DA(cr)
response:
!01(cr)
Disable the alarm for module 2:
command:
@02DA(cr)
response:
!02(cr)