CB-7080 & CB-7080D Counter/Timer User's Guide
~AAO(name)
2-8
~AAO(name)
Description
: Sets the module name.
Syntax
: ~AAO(name)[chk](cr)
~
A delimiter character
AA
2-character HEX module address, from 00 to FF
(name)
4-character/5-character module name
[chk]
2-character checksum. If checksum is disabled, no [chk]
(cr)
0x0D
Response
:
Valid response
!AA[chk](cr)
invalid response
?AA[chk](cr)
No response
Syntax error, communication error or address error
!
A delimiter character indicating a valid response
?
A delimiter character indicating an invalid response
AA
2-character HEX module address
[chk]
2-character checksum. If checksum is disabled, no [chk].
(cr)
0x0D
Examples
:
Change module name from 7080 to 8080
command:
$01M(cr)
response:
!017080(cr)
command:
~01O8080(cr)
response:
!01(cr)
Change module name from 7080D to 8080D
command:
$01M(cr)
response:
!017080D(cr)
command:
~01O8080D(cr)
response:
!01(cr)
Note
This command was designed for OEM/ODM users. You can use it to change the module name for other