7
www.procontechnology.com.au
Phone: (03) 98306288
P/No.
A301/A302-1K0
A301/A302-1K7
A301/A302-2K5
Up to 1.5m 2/6AWG(33/14mm²)
00/2AWG(67/33mm²) 000/0AWG(85/50mm²)
3m
0/4AWG(50/21mm²)
-/0AWG(100/50mm²)
Not recommended
6m
00/2AWG(67/33mm²) Not recommended
Not recommended
•
It is recommended that a circuit breaker or high current fuse be placed in the DC
positive (+) line close to the batteries.
Part No.
A301/A302-1K0
A301/A302-1K7
A301/A302-2K5
Fuse or Circuit
Breaker size (+)
Only
125/75AMP
250/125AMP
300/150AMP
•
It is recommended that a heavy duty battery switch with a current rating higher
than the fuse be fitted in the DC positive (+) line close to the batteries to allow the
supply to the inverter to be switched off, this can also be achieved by using a circuit
breaker which has a trip facility.
•
Positive and Negative cables should be run close together to reduce cable
inductance. The cables should also be protected from any damage.
•
Any connections should be made securely using the proper hardware. Procon
Technology recommends the use of DeOxit as a contact cleaner to improve
conductivity and protect metal. See…
www.procontechnology.com.au/deoxit.htm
EXTERNAL EARTHING: (OPTIONAL)
Meanwell inverters have been internally bonded for safety, by connecting the AC socket/s
earth pin to the inverter case. If the inverter is used in a stationary land based application
or if the inverter is causing interference with TV sets or radios it is recommended that an
external earth connection is made by one of the following methods:
•
External Earthing Stationary Applications - Connect an earth wire (preferably solid
green or green with yellow stripe) from the external earth connection (Chassis GND) on
the rear of the inverter to a metal stake or pipe that is driven into the ground at least
1.2m (or according to local electrical safety authority recommendations).