background image

27

5.8

Auxiliary Output

Built-in 12V/1A auxiliary output

+12V-AUX

GND-AUX

to

12Vdc

5.9

Factory Resetting

O

F

F

ON

2 3 4

1

Users can follow the steps below to restore factory settings for

commands:

VOUT_TRIM(VOUT_SET IOUT_OC_FAULT_LIMIT(IOUT_SET) ,

),

OPERATION, SYSTEM_CONFIG and all charge commands

DIP switch diagram is as shown below.

(1) Set all DIP switch positions to ON.

(2) Power on in REMOTE OFF mode (no output at this step).

(3) After power on, in 15 seconds, switch all DIP switch from ON to

O

FF

and then switch ALL back to ON position.

(4) Green LED will blink 3 times if set successfully.

(5) Factory default setting will be restored after re-power on.

DIP switch diagram is as shown below.

Figure

5 10

-

CN53

SVR

DIP

SW81

CN86

& 16 +12V-AUX

PIN15

PIN17 & 18 GND-AUX

5

28

SHP-10K

is compliant with PMBus Rev.1.1, the maximum

communication speed is 100KHz and has the capability of identifying up to

4 addressed units.

PMBus communication interface is able to provide the current operating
status and information. Supported information is as below:

1.

Output voltage, current and internal temperature

2.

Alarm and status.

3.

Manufacturer and mode data.

Each SHP-10K unit should have their unique and own device address to
communicate over the PMBus. 7-bit address setting is used to assign
advice address, shown in the description below

A0-A2 allow users to designate an address for the SHP-10K unit,
these

bits are defined through a DIP switch (DIP-SW81) on the side

three

case. There are up to 8 different addresses are available to be assigned.
Please refer to Table 6-1 for the detailed setup advice.

6.1

PMBus Communication Interface

6 1 1

. .

PMBus Device Addressing

1

0

0

0

A2 A1 A0

MSB

LSB

6.

Communication Protocol

Table 6-1

Device No.

0

1

2

3

4

5

6

7

ON

1

ON

ON

ON

ON

2

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

3

DIP

switch position

ON

OFF

2

1

3

4

There are two means to control the unit, analog signals and digital

communication. Analog is the default setting for the unit, signals including
PV, PC and SVR can be used immediately once receiving the unit. The digital
communication (PMBus, CAN bus or Modbus) is initially uncontrollable but
readable. To activate the adjustment commands of OPERATRION,
VOUT_TRIM or VOUT_SET.., ect., set

PM_CTRL/CAN_CTRL/MOD_CTRL of

SYSTEM_CONFIG (PMBus: BEh; CAN bus: 0x00C2; Modbus: 0x00C4) at 1

" "

and then reboot the unit. Once the digital communication dominates the
unit, the analog signals become invalid.

6

Summary of Contents for SHP-10K-115

Page 1: ...SHP 10K HV Series 10KW HVDC Power Supply Installation manual 3 3 wire wide input range High efficiency Intelligent Automate Telecom Industrial EV Security...

Page 2: ...demanded by various industries Two types of cooling methods forced air and water cooling that can be working at ambient temperature up to 70 Moreover SHP 10K HV provides vast design flexibility by eq...

Page 3: ...ion 5 1 Inrush Current Limiting 5 2 Power Factor Correction PFC 5 3 Output Voltage Adjustment 5 4 Output Current Adjustment 5 5 Parallel function 5 Remote Control 6 5 7 Alarm Signal Output 5 8 Auxilia...

Page 4: ...range n Please do not stack any object on the unit n The safety protection level of this supply is class I The Frame Ground of the unit must be well connected to PE Protective Earth n The device shou...

Page 5: ...axes 40A 400VAC 65A 480VAC 6 5mA peak 530VAC 100 105 of rated current Protection type Constant current limiting unit will shutdown after 5 sec re power on to recover 60 5 69 1V Protection type Shut do...

Page 6: ...lerance includes set up tolerance line regulation and load regulation 4 Derating may be needed under low input voltages Please check the derating curve for more details 5 Additional EMI filter is need...

Page 7: ...ical specification Forced Air Cooling Blank type Mounting Instruction Mounting Screw Mounting Surface Chassis of SHP 10K Hole No Recommended Screw Size MAX Penetration Depth L Recommended mounting tor...

Page 8: ...Normal Mounting The B type is suggested mounting on horizontal surfaces lank 3 1 2 Mounting on a Water Cooled Plate A L type with a water cooled plate for heat dissipation it is suggested mount the su...

Page 9: ...cification to receive the maximum length of mounting screw C Mounting methods other than chapter 3 1 or operate under high ambient temperature may increase the internal component temperature and will...

Page 10: ...LOAD SHP 10K CORE AC I P DC O P Cx Cx Cy R1 R2 L L L L L3 L2 L3 PE L2 PE LOAD LINE A Schematic FREQ MHz FREQ MHz 0 01 10 20 70 5 13 0 05 20 47 93 7 16 0 10 30 61 111 47 0 15 50 66 136 58 0 50 60 100...

Page 11: ...nts signal rebound for differential signals of CAN bus and Modbus 4 16 4 1 2 Pin Assignment of CN53 2 1 10 9 Pin No 1 2 3 4 5 6 7 8 9 10 Function V Signal PV PC DB DA Description Negative output volta...

Page 12: ...e signal return is isolated from the output terminals V V For PMBus model Serial Clock used in the PMBus interface Note For PMBus model Serial Clock used in the PMBus interface Note For CANBus model D...

Page 13: ...rcing current is 10mA and only for output Note The maximum sourcing current is 10mA and only for output Note The maximum sourcing current is 10mA and only for output Note The maximum sourcing current...

Page 14: ...tration below 5 1 3 SVR Figure 5 1 ON OFF 1 2 3 coarse tune fine tune DIP SW1 5 22 A Have the DIP switch position 3 set as B Connect output of the external DC source to PV and as V signal shown in Fig...

Page 15: ...5 5 E Covered by over temperature protection auto de rating function works under operation either in PC mode or under control by communication protocol T1 Typ Maximum ambient temperature of full load...

Page 16: ...owing equation Maximum output current at parallel operation Rated current per unit Number of unit 0 95 When the total output current is less than 5 of the total rated current or say 5 of Rated current...

Page 17: ...nd mode data Each SHP 10K unit should have their unique and own device address to communicate over the PMBus 7 bit address setting is used to assign advice address shown in the description below A0 A2...

Page 18: ...t reading value format linear N 5 STATUS_MFR_SPECIFIC STATUS_FANS_1_2 READ_VIN READ_VIN READ_VIN READ_IIN READ_IIN READ_IIN READ_VOUT READ_IOUT Read Word Read Word Read Word Read Word Read Word Read W...

Page 19: ...READ_FAN_SPEED_1 READ_FAN_SPEED_2 6 Physical layer specification This protocol follows CAN ISO 11898 with Baud rate of 250Kbps Data Frame This protocol es Extended CAN 29 bit identifier frame format o...

Page 20: ...11 MFR_DATE_B0B5 MFR_SERIAL_B0B5 MFR_SERIAL_B6B11 MFR_MODEL_B6B11 MFR_REVISION_B0B5 MFR_LOCATION_B0B2 MFR_MODEL_B0B5 READ_VIN_TR READ_ IN_ I R READ_ IN_ I S READ_ IN_ I T READ_VOUT READ_IOUT READ_ TEM...

Page 21: ...value is 0x0960 hexadecimal 2400 decimal then VDC_real 2400 0 01 24 00V 6 36 MFR_MODEL_B0B5 0x0082 is the first 6 codes of the manufacturer s model name ASCII MFR_MODEL_B6B11 0x0083 is the last 6 code...

Page 22: ...t7 Bit0 Reserved Bit3 Bit3 Bit3 Bit3 Bit2 Bit2 Bit2 Bit2 Bit1 Bit1 Bit1 Bit1 Bit0 Bit0 Bit0 Bit0 byte4 5 byte3 byte2 byte1 byte0 byte0 Bit 0 3 VOUT Factor The factor of output voltage 0x 0 Output volt...

Page 23: ...l status 0 The output voltage current defined by control over SVR PV PC 1 The output voltage current ON OFF control defined by control over CANBus VOUT_SET IOUT_SET OPERATION Bit 1 2 OPERATION_INIT Pr...

Page 24: ...code 1byte what The function code is used to tell the slave kind of action to perform Data N bytes For data exchange contents and data length are dependent on different function codes Error Check 2by...

Page 25: ...0C3 0x00C4 Note The conversion of setting and reading values is defined as following Actual value Communication reading value Factor F x value Among them Factor needs to refer to the definition of SCA...

Page 26: ...0 0x41 0x50 0x20 0x2D 0x4E 0x2D 0x20 0x32 0x57 0x33 0x20 0x34 0x45 0x35 0x20 0x20 MFR_ID_B0B5 0x0080 0x0082 is the first 6 codes of the manufacturer s name ASCII MFR_ID_B6B11 0x0083 0x0085 is the last...

Page 27: ...te 1 Byte 7 Byte 2 Byte 8 Byte 3 Byte 9 Byte 4 Byte 10 Byte 5 Byte 11 6 48 SCALING_FACTOR 0x00C0 Bit7 Bit7 Bit7 Bit7 Bit6 Bit6 Bit6 Bit6 Bit5 Bit5 Bit5 Bit5 Reserved Reserved FAN_SPEED Factor IOUT Fac...

Page 28: ...DD output voltage status TOO LOW 1 Secondary DD output voltage status NORMAL Bit 2 PFC_OK Primary PFC status 0 Primary PFC OFF or abnormal 1 Primary PFC ON normally Bit 4 ADL_ON Active dummy load cont...

Page 29: ...FFFF 0x7DEC 6 3 7 2 Read Input Register FC 04 The request message specifies the starting register and quantity of registers to be read For example The master requests the content of analog input regis...

Page 30: ...8A 40 110 N A 0 57 6V 24 57 6V 31 2 6V 0 165A 30 153 7A 0 138V 57 5 138V 57 5 23V 0 95 7A 17 4 89 1A 0 260V 108 260V 122 30V 0 50 8A 9 2 47 4A 0 400V 167 400V 213 20V 0 33A 6 30 7A Display value rang...

Page 31: ...7 1 1 Over Temperature Protection OTP and T Alarm 7 1 2 AC Fail 7 4 1 Short Circuit Protection 7 3 1 FAN FAIL T ALARM to GND AUX TTL AC OK to GND AUX TTL FAN FAIL to GND AUX TTL Condition Condition C...

Page 32: ...not replace parts or any form of modification to the product in order to keep the warranty effectively MEAN WELL possesses the right to adjust the content of this manual Please refer to the latest ve...

Page 33: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Reviews: