background image

43

FC = 06

FC = 03/04

Table 6-6

2 Bytes

2 Bytes

Register Address

Register Value

Register

address

0x0000

0x0020

0x0030

0x0040

0x0050

0x0051

0x0052

0x0053

0x0054

0x0055

0x03、0x06

0x03、0x06

0x03、0x06

0x03

0x04

0x04

0x04

0x04

0x04

0x04

1

2

2

2

2

2

2

2

R

phase

input current read value

S phase

input current read value

T phase

input current read value

2

2

OPERATION

VOUT_SET

IOUT_SET

FAULT_STATUS

READ_VIN_

RS

READ_VIN_

ST

READ_VIN_

TR

READ_ IN_

I

R

READ_ IN_

I

S

READ_ IN_

I

T

Command

Name

Function

code

# of data

Bytes

Description

Remote ON/OFF control

ON: 0x0001

OFF: 0x0000

Output voltage set

(format: value, F=0.01)

Output current set

(format: value, F=0.01)

Abnormal status

V

RS

input voltage read value

(format:

, =0. )

value F

1

V

ST

input voltage read value

(format:

, =0. )

value F

1

V

TR

input voltage read value

(format:

, =0. )

value F

1

(format:

, =0. )

value F

1

(format:

, =0. )

value F

1

(format:

, =0. )

value F

1

6.3.5

Data Field and Command Lists

Data field provides additional information by the slave to

complete the action specified by the function code(FC) in a

request. The data field typically includes register addresses,

count values, and written data. There are several forms according

to the function codes.

Quantity of (Input) Registers

2 Bytes

2 Bytes

Starting Address

6

44

0x0097

0x00C0

0x00C3

0x00C4

Note: The conversion of setting and reading values is defined as

following: Actual value = Communication reading value Factor (F

x

value). Among them, Factor needs to refer to the definition of

SCALING_FACTOR in each model list.

EX: VDC_real (actual DC voltage) = READ_VOUT x Factor. If the Factor of

READ_VOUT of a certain model is 0.01, the communication reading

value is 0x0960 (hexadecimal)→2400 (decimal), then VDC_real =

2400 x 0.01 = 24.00V.

0x03

0x03

0x03

0x03、0x06

1

2

2

2

MFR_SERIAL_

B6B11

SCALING_FACTOR

SYSTEM_STATUS

SYSTEM_CONFIG

Command

Name

# of data

Bytes

Description

Manufacture serial number

Scaling ratio

System status

System configuration

Register

address

Function

code

0x0091

0x0094

0x03

0x03

6

6

MFR_DATE_B0B5

MFR_SERIAL_

B0B5

Manufacture date

Manufacture serial number

0x0089

0x008C

0x03

0x03

6

6

MFR_MODEL_

B6B11

MFR_REVISION_

B0B5

Manufacture model name

Firmware version

0x008F

0x03

4

MFR_LOCATION_

B0B2

Manufacture place

0x0061

0x0062

0x0080

0x0083

0x0086

0x04

0x04

0x03

0x03

0x03

2

2

6

6

6

READ_IOUT

READ

TEMPERATURE_1

MFR_ID_B0B5

MFR_ID_B6B11

MFR_MODEL_

B0B5

Output current read value

(format: value, F=0.01)

Manufacture's name

Manufacture's name

Manufacture model name

0x0070

0x0071

R

R

2

2

READ_FAN_
SPEED_1

READ_FAN_
SPEED_2

Fan speed 1 reading value

(format: value, F=1)

Fan speed

reading value

2

(format: value, F=1)

Internal ambient temperature

(format: value, F=0.1)

0x0060

0x04

2

READ_VOUT

Output voltage read value

(format: value, F=0.01)

6

Summary of Contents for SHP-10K-115

Page 1: ...SHP 10K HV Series 10KW HVDC Power Supply Installation manual 3 3 wire wide input range High efficiency Intelligent Automate Telecom Industrial EV Security...

Page 2: ...demanded by various industries Two types of cooling methods forced air and water cooling that can be working at ambient temperature up to 70 Moreover SHP 10K HV provides vast design flexibility by eq...

Page 3: ...ion 5 1 Inrush Current Limiting 5 2 Power Factor Correction PFC 5 3 Output Voltage Adjustment 5 4 Output Current Adjustment 5 5 Parallel function 5 Remote Control 6 5 7 Alarm Signal Output 5 8 Auxilia...

Page 4: ...range n Please do not stack any object on the unit n The safety protection level of this supply is class I The Frame Ground of the unit must be well connected to PE Protective Earth n The device shou...

Page 5: ...axes 40A 400VAC 65A 480VAC 6 5mA peak 530VAC 100 105 of rated current Protection type Constant current limiting unit will shutdown after 5 sec re power on to recover 60 5 69 1V Protection type Shut do...

Page 6: ...lerance includes set up tolerance line regulation and load regulation 4 Derating may be needed under low input voltages Please check the derating curve for more details 5 Additional EMI filter is need...

Page 7: ...ical specification Forced Air Cooling Blank type Mounting Instruction Mounting Screw Mounting Surface Chassis of SHP 10K Hole No Recommended Screw Size MAX Penetration Depth L Recommended mounting tor...

Page 8: ...Normal Mounting The B type is suggested mounting on horizontal surfaces lank 3 1 2 Mounting on a Water Cooled Plate A L type with a water cooled plate for heat dissipation it is suggested mount the su...

Page 9: ...cification to receive the maximum length of mounting screw C Mounting methods other than chapter 3 1 or operate under high ambient temperature may increase the internal component temperature and will...

Page 10: ...LOAD SHP 10K CORE AC I P DC O P Cx Cx Cy R1 R2 L L L L L3 L2 L3 PE L2 PE LOAD LINE A Schematic FREQ MHz FREQ MHz 0 01 10 20 70 5 13 0 05 20 47 93 7 16 0 10 30 61 111 47 0 15 50 66 136 58 0 50 60 100...

Page 11: ...nts signal rebound for differential signals of CAN bus and Modbus 4 16 4 1 2 Pin Assignment of CN53 2 1 10 9 Pin No 1 2 3 4 5 6 7 8 9 10 Function V Signal PV PC DB DA Description Negative output volta...

Page 12: ...e signal return is isolated from the output terminals V V For PMBus model Serial Clock used in the PMBus interface Note For PMBus model Serial Clock used in the PMBus interface Note For CANBus model D...

Page 13: ...rcing current is 10mA and only for output Note The maximum sourcing current is 10mA and only for output Note The maximum sourcing current is 10mA and only for output Note The maximum sourcing current...

Page 14: ...tration below 5 1 3 SVR Figure 5 1 ON OFF 1 2 3 coarse tune fine tune DIP SW1 5 22 A Have the DIP switch position 3 set as B Connect output of the external DC source to PV and as V signal shown in Fig...

Page 15: ...5 5 E Covered by over temperature protection auto de rating function works under operation either in PC mode or under control by communication protocol T1 Typ Maximum ambient temperature of full load...

Page 16: ...owing equation Maximum output current at parallel operation Rated current per unit Number of unit 0 95 When the total output current is less than 5 of the total rated current or say 5 of Rated current...

Page 17: ...nd mode data Each SHP 10K unit should have their unique and own device address to communicate over the PMBus 7 bit address setting is used to assign advice address shown in the description below A0 A2...

Page 18: ...t reading value format linear N 5 STATUS_MFR_SPECIFIC STATUS_FANS_1_2 READ_VIN READ_VIN READ_VIN READ_IIN READ_IIN READ_IIN READ_VOUT READ_IOUT Read Word Read Word Read Word Read Word Read Word Read W...

Page 19: ...READ_FAN_SPEED_1 READ_FAN_SPEED_2 6 Physical layer specification This protocol follows CAN ISO 11898 with Baud rate of 250Kbps Data Frame This protocol es Extended CAN 29 bit identifier frame format o...

Page 20: ...11 MFR_DATE_B0B5 MFR_SERIAL_B0B5 MFR_SERIAL_B6B11 MFR_MODEL_B6B11 MFR_REVISION_B0B5 MFR_LOCATION_B0B2 MFR_MODEL_B0B5 READ_VIN_TR READ_ IN_ I R READ_ IN_ I S READ_ IN_ I T READ_VOUT READ_IOUT READ_ TEM...

Page 21: ...value is 0x0960 hexadecimal 2400 decimal then VDC_real 2400 0 01 24 00V 6 36 MFR_MODEL_B0B5 0x0082 is the first 6 codes of the manufacturer s model name ASCII MFR_MODEL_B6B11 0x0083 is the last 6 code...

Page 22: ...t7 Bit0 Reserved Bit3 Bit3 Bit3 Bit3 Bit2 Bit2 Bit2 Bit2 Bit1 Bit1 Bit1 Bit1 Bit0 Bit0 Bit0 Bit0 byte4 5 byte3 byte2 byte1 byte0 byte0 Bit 0 3 VOUT Factor The factor of output voltage 0x 0 Output volt...

Page 23: ...l status 0 The output voltage current defined by control over SVR PV PC 1 The output voltage current ON OFF control defined by control over CANBus VOUT_SET IOUT_SET OPERATION Bit 1 2 OPERATION_INIT Pr...

Page 24: ...code 1byte what The function code is used to tell the slave kind of action to perform Data N bytes For data exchange contents and data length are dependent on different function codes Error Check 2by...

Page 25: ...0C3 0x00C4 Note The conversion of setting and reading values is defined as following Actual value Communication reading value Factor F x value Among them Factor needs to refer to the definition of SCA...

Page 26: ...0 0x41 0x50 0x20 0x2D 0x4E 0x2D 0x20 0x32 0x57 0x33 0x20 0x34 0x45 0x35 0x20 0x20 MFR_ID_B0B5 0x0080 0x0082 is the first 6 codes of the manufacturer s name ASCII MFR_ID_B6B11 0x0083 0x0085 is the last...

Page 27: ...te 1 Byte 7 Byte 2 Byte 8 Byte 3 Byte 9 Byte 4 Byte 10 Byte 5 Byte 11 6 48 SCALING_FACTOR 0x00C0 Bit7 Bit7 Bit7 Bit7 Bit6 Bit6 Bit6 Bit6 Bit5 Bit5 Bit5 Bit5 Reserved Reserved FAN_SPEED Factor IOUT Fac...

Page 28: ...DD output voltage status TOO LOW 1 Secondary DD output voltage status NORMAL Bit 2 PFC_OK Primary PFC status 0 Primary PFC OFF or abnormal 1 Primary PFC ON normally Bit 4 ADL_ON Active dummy load cont...

Page 29: ...FFFF 0x7DEC 6 3 7 2 Read Input Register FC 04 The request message specifies the starting register and quantity of registers to be read For example The master requests the content of analog input regis...

Page 30: ...8A 40 110 N A 0 57 6V 24 57 6V 31 2 6V 0 165A 30 153 7A 0 138V 57 5 138V 57 5 23V 0 95 7A 17 4 89 1A 0 260V 108 260V 122 30V 0 50 8A 9 2 47 4A 0 400V 167 400V 213 20V 0 33A 6 30 7A Display value rang...

Page 31: ...7 1 1 Over Temperature Protection OTP and T Alarm 7 1 2 AC Fail 7 4 1 Short Circuit Protection 7 3 1 FAN FAIL T ALARM to GND AUX TTL AC OK to GND AUX TTL FAN FAIL to GND AUX TTL Condition Condition C...

Page 32: ...not replace parts or any form of modification to the product in order to keep the warranty effectively MEAN WELL possesses the right to adjust the content of this manual Please refer to the latest ve...

Page 33: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Reviews: