![MDV MDVi-D100Q4/N1-C Manual Download Page 76](http://html1.mh-extra.com/html/mdv/mdvi-d100q4-n1-c/mdvi-d100q4-n1-c_manual_1757515076.webp)
MHVAC-DTSM-2010-03 Specifications
Medium Static Pressure Duct Type
75
2.Specifications
Sale Model
MDVi-D45T2/CN1
MDVi-D56T2/CN1
Power supply
V-ph-Hz
220~240-1-50
220~240-1-50
Cooling
Capacity kW
4.5 5.6
Input W
110
110
Rated current
A
0.5
0.5
Heating
Capacity kW
5.0
6.3
Input W
110
110
Rated current
A
0.5
0.5
Indoor fan motor
Model
YSK55-4D
YSK55-4D
Type
AC MOTOR
AC MOTOR
Brand
Welling
Welling
Input W
117/110/101
117/110/101
Capacitor uF
3
3
Speed(hi/mi/lo) r/min
900/800/690 900/800/690
Indoor coil
Number of rows
3
3
Tube pitch(a)x row pitch(b)
mm
25.4×22
25.4×22
Fin spacing
mm
1.7
1.7
Fin type (code)
Hydrophilic aluminum
Tube outside dia. and type
mm
Ф
9.53
Ф
9.53
Inner groove tube
Inner groove tube
Coil length x height x width
mm
800x66 x254
800x66 x254
Number of circuits
2
2
Indoor air flow (Hi/Mi/Lo)
m
3
/h 1160/1100/950 1160/1100/950
Indoor external static pressure (Hi)
Pa
40
40
Sound level (sound pressure) dB(A)
45/41/38
45/41/38
Indoor unit
Dimension (W x H x D)
mm
1000×298×800
1000×298×800
Packing (W x H x D)
mm
1205x370x940
1205x370x940
Net/Gross weight
kg
38/45
38/45
Refrigerant Type
R410A
R410A
Design pressure
MPa 4.2/2.0
4.2/2.0
Refrigerant piping
Liquid side/ Gas side
mm
Ф
6.4/
Ф
12.7
Ф
9.5/
Ф
15.9
Connection wiring
Power wiring
Nb×mm
2
3×2.5(L
≤
20m); 3×3.5(L
≤
50m)
Signal wiring
Nb×mm
2
3×1.0
Drainage water pipe dia.
mm
Ф
32
Ф
32
Controller
Wireless remote controller R51(standard)
Operation temp
℃
17
~
30
Notes:
1.
Nominal cooling capacities are based on the following conditions: return air temp.: 27°CDB, 19°CWB, and outdoor
temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2.
Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB,
and equivalent ref. Piping: 8m (horizontal)
Summary of Contents for MDVi-D100Q4/N1-C
Page 11: ...Dimensions MHVAC DTSM 2010 03 Compact Four Way Cassette Type 10 3 Dimensions...
Page 12: ...MHVAC DTSM 2010 03 Service Space Compact Four Way Cassette Type 11 4 Service Space...
Page 15: ...Wiring Diagram MHVAC DTSM 2010 03 Compact Four Way Cassette Type 14 MDVi D45Q4 BN1...
Page 16: ...MHVAC DTSM 2010 03 Wiring Diagram Compact Four Way Cassette Type 15 MDVi D56Q4 BN1...
Page 63: ...Wiring Diagrams MHVAC DTSM 2010 03 Low Static Pressure Duct Type 62 6 Wiring Diagrams...
Page 106: ...MHVAC DTSM 2010 03 Service Space New Middle Static Pressure Duct Type A5 105 4 Service Space...
Page 108: ...MHVAC DTSM 2010 03 Wiring Diagrams New Middle Static Pressure Duct Type A5 107...
Page 110: ...MHVAC DTSM 2010 03 Air Velocity New Middle Static Pressure Duct Type A5 109...
Page 126: ...MHVAC DTSM 2010 03 Accessories New Middle Static Pressure Duct Type A5 125 11 Accessories...
Page 133: ...Service Space MHVAC DTSM 2010 03 Ceiling Floor Type 132 4 Service Space 600mm 600mm...
Page 204: ...MHVAC DTSM 2010 03 Wiring Diagram Exposed Concealed Floor standing Type 213 7 Wiring Diagram...
Page 241: ...Dimension MHVAC DTSM 2010 03 High Static Pressure Duct Type 250 3 Dimension...
Page 244: ...MHVAC DTSM 2010 03 Wiring Diagram High Static Pressure Duct Type 253 6 Wiring Diagram...
Page 258: ...MHVAC DTSM 2010 03 Service Space Console Type 267 4 Service Space...
Page 287: ...Indoor Unit Central Control Monitor System MHVAC DTSM 2010 03 Control System 296 Dimension...