MHVAC-DTSM-2010-03 Specifications
Exposed & Concealed Floor-standing Type
207
Model MDVi-D71Z/N1-F1
MDVi-D71Z/N1-F2
MDVi-D71Z/N1-F3
Power supply
V- Ph-Hz
220-240V, 1Ph, 50Hz
Cooling
Capacity kW
7.1 7.1 7.1
Input W
130
130
130
Rated current
A
0.57
0.57
0.57
Heating
Capacity kW
8.0
8.0
8.0
Input W
130
130
130
Rated current
A
0.57
0.57
0.57
Indoor fan motor
Model
YSK74-4E
YSK74-4E
YSK74-4E
Type
AC
motor
AC motor
AC motor
Brand
Yongan
Yongan
Yongan
Input W
138.5/119/97
138.5/119/97 138.5/119/97
Capacitor
μ
F 3
3
3
Speed (hi/mid/lo)
r/min
1120/1020/880 1120/1020/880 1120/1020/880
Indoor coil
Number of rows
2
2
2
Tube pitch(a)x row pitch(b)
mm
25.4x22
25.4x22
25.4x22
Fin spacing
mm
1.8
1.8
1.8
Fin type
hydrophilic aluminum
Tube outside dia. and type
mm
Ф
9.5
innergroove tube
Ф
9.5
innergroove tube
Ф
9.5
innergroove tube
Coil length x height x width
mm
1068 x 254 x 44
1068 x 254 x 44
1068 x 254 x 44
Number of circuits
4
4
4
Indoor air flow (H/M/L)
m
3
/h 1380/1100/870 1380/1100/870 1380/1100/870
Indoor external static pressure
Pa
12
12
12
Indoor noise level (Hi/Mid/Lo) (Sound pressure) dB(A) 43/41/38 43/41/38 43/41/38
Indoor unit
Dimension (WxHxD)
mm
1500×220×625
1500×220×625
1336×212×545
Packing (WxHxD)
mm
1589X722X312
1679X722X312
1439X639X305
Net/Gross weight
kg
44/50 44/53 36/40
Refrigerant type
R410A
R410A
R410A
Throttle
Electric expansive valve
Design pressure
MPa
4.2/2.0 4.2/2.0 4.2/2.0
Refrigerant piping
Liquid side/ Gas side
mm
Ф
9.5/
Ф
15.9
Ф
9.5/
Ф
15.9
Ф
9.5/
Ф
15.9
Connecting wiring
Power wiring
Nb×mm
2
3×2.5(L
≤
20m)
;
3×3.5(L
≤
50m)
Signal wiring
Nb×mm
2
3×1.0 3×1.0 3×1.0
Drainage water pipe dia.
mm
Ф
25
Ф
25
Ф
25
Controller
Wireless remote controller (R51/E)(standard)
Operation temp
℃
17-30
Notes:
1.
Nominal cooling capacities are based on the following conditions: return air temp.: 27°CDB, 19°CWB, and outdoor
temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2.
Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB,
and equivalent ref. Piping: 8m (horizontal)
Summary of Contents for MDVi-D100Q4/N1-C
Page 11: ...Dimensions MHVAC DTSM 2010 03 Compact Four Way Cassette Type 10 3 Dimensions...
Page 12: ...MHVAC DTSM 2010 03 Service Space Compact Four Way Cassette Type 11 4 Service Space...
Page 15: ...Wiring Diagram MHVAC DTSM 2010 03 Compact Four Way Cassette Type 14 MDVi D45Q4 BN1...
Page 16: ...MHVAC DTSM 2010 03 Wiring Diagram Compact Four Way Cassette Type 15 MDVi D56Q4 BN1...
Page 63: ...Wiring Diagrams MHVAC DTSM 2010 03 Low Static Pressure Duct Type 62 6 Wiring Diagrams...
Page 106: ...MHVAC DTSM 2010 03 Service Space New Middle Static Pressure Duct Type A5 105 4 Service Space...
Page 108: ...MHVAC DTSM 2010 03 Wiring Diagrams New Middle Static Pressure Duct Type A5 107...
Page 110: ...MHVAC DTSM 2010 03 Air Velocity New Middle Static Pressure Duct Type A5 109...
Page 126: ...MHVAC DTSM 2010 03 Accessories New Middle Static Pressure Duct Type A5 125 11 Accessories...
Page 133: ...Service Space MHVAC DTSM 2010 03 Ceiling Floor Type 132 4 Service Space 600mm 600mm...
Page 204: ...MHVAC DTSM 2010 03 Wiring Diagram Exposed Concealed Floor standing Type 213 7 Wiring Diagram...
Page 241: ...Dimension MHVAC DTSM 2010 03 High Static Pressure Duct Type 250 3 Dimension...
Page 244: ...MHVAC DTSM 2010 03 Wiring Diagram High Static Pressure Duct Type 253 6 Wiring Diagram...
Page 258: ...MHVAC DTSM 2010 03 Service Space Console Type 267 4 Service Space...
Page 287: ...Indoor Unit Central Control Monitor System MHVAC DTSM 2010 03 Control System 296 Dimension...