![MDV MDVi-D100Q4/N1-C Manual Download Page 284](http://html1.mh-extra.com/html/mdv/mdvi-d100q4-n1-c/mdvi-d100q4-n1-c_manual_1757515284.webp)
MHVAC-DTSM-2010-03
Indoor Unit Central Control Monitor System
Control System
293
1.
The liquid crystal matrix is composed of 4*64 grids, and each grid is composed of two blocks of different
sizes (as shown in the above figure).
2.
The matrix includes horizontal coordinates 00-15 on the upper side and vertical coordinates 00+, 16+, 32+
and 48+ on the left side, which indicate the address of the indoor unit. The sum of the horizontal coordinate
and the vertical coordinate of the grid is the address of the grid. Each grid corresponds to an indoor unit of this
address.
3.
One grid is composed of two blocks of different sizes. The status indication table is as follows:
Status
Object
Constantly on
Slow blink
Fast blink
Big black block
In-service
Selected
Out of service
Small black block
Power on
Fault of indoor unit
Power off
LCD display description
1. Description of the standby page
1)
The LCD displays the standby page, 60 air conditioners are in service, of which 28 are powered on and 32
off.
2)
In the matrix, the big dots of (00, 16+) and (15,32+) are luminous, and the small dots are not luminous. It
indicates the 32 air conditioners with the addresses from 16 to 47 are powered off.
3)
In the matrix, the big and small dots of (09, 48+) and (12, 48+) are not luminous. It indicates the four air
conditioners with the addresses from 57 to 60 are outside the network.
4)
All other big and small dots in the matrix are luminous. It indicates all other air conditioners are in the
network and powered on.
5)
The address of the air conditioner is sum of the coordinates. For example, the address of (09, 48+) is
09+48=57.
6)
The centralized controller keypad is locked, and the centralized controller communicates with the
computer normally.
Summary of Contents for MDVi-D100Q4/N1-C
Page 11: ...Dimensions MHVAC DTSM 2010 03 Compact Four Way Cassette Type 10 3 Dimensions...
Page 12: ...MHVAC DTSM 2010 03 Service Space Compact Four Way Cassette Type 11 4 Service Space...
Page 15: ...Wiring Diagram MHVAC DTSM 2010 03 Compact Four Way Cassette Type 14 MDVi D45Q4 BN1...
Page 16: ...MHVAC DTSM 2010 03 Wiring Diagram Compact Four Way Cassette Type 15 MDVi D56Q4 BN1...
Page 63: ...Wiring Diagrams MHVAC DTSM 2010 03 Low Static Pressure Duct Type 62 6 Wiring Diagrams...
Page 106: ...MHVAC DTSM 2010 03 Service Space New Middle Static Pressure Duct Type A5 105 4 Service Space...
Page 108: ...MHVAC DTSM 2010 03 Wiring Diagrams New Middle Static Pressure Duct Type A5 107...
Page 110: ...MHVAC DTSM 2010 03 Air Velocity New Middle Static Pressure Duct Type A5 109...
Page 126: ...MHVAC DTSM 2010 03 Accessories New Middle Static Pressure Duct Type A5 125 11 Accessories...
Page 133: ...Service Space MHVAC DTSM 2010 03 Ceiling Floor Type 132 4 Service Space 600mm 600mm...
Page 204: ...MHVAC DTSM 2010 03 Wiring Diagram Exposed Concealed Floor standing Type 213 7 Wiring Diagram...
Page 241: ...Dimension MHVAC DTSM 2010 03 High Static Pressure Duct Type 250 3 Dimension...
Page 244: ...MHVAC DTSM 2010 03 Wiring Diagram High Static Pressure Duct Type 253 6 Wiring Diagram...
Page 258: ...MHVAC DTSM 2010 03 Service Space Console Type 267 4 Service Space...
Page 287: ...Indoor Unit Central Control Monitor System MHVAC DTSM 2010 03 Control System 296 Dimension...