Technical Manual IP-Router SCN-IP100.01 

 

 

 

MDT technologies GmbH  •  

51766 Engelskirchen  •  Papiermühle 1

 

 

Tel.: +49-2263-

880  •  Fax: +49-2263-4588  • [email protected]  •  www.mdt.de 

13

 

 

4 ETS Connection Manager 

 

If the IP configuration of the KNX IP Router is valid, the router can be used as an interface to KNX/EIB.  
The following configuration is necessary:  
Select the button Settings and the tab Communication in the main window of ETS4. All available 
connections are listed by Configured connections. Select the desired connection.  
To be able to access KNX/EIB, the KNX IP Router requires an second physical address. This second 
physi-cal address is only used for bus access and must be set up separately. 
 

 

Figure 10: Communication Manager  

 
A dummy device may have to be added to the ETS project to reserve this address. 
 
 

 

Summary of Contents for SCN-IP100.01

Page 1: ...MDT technologies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 1 2012 Technical Manual MDT IP Router SCN IP100 01...

Page 2: ...3 1 1 Installation and connection 3 2 1 Coupler function 4 2 2 Bus access function KNXnet IP Tunneling 6 3 ETS Parameter 7 3 1 General 7 3 2 IP Configuration 8 3 3 Routing KNX IP 10 3 4 Routing IP KNX...

Page 3: ...Power over Ethernet IEEE 802 3af 1 1 Installation and connection The KNX IP Router is designed for installation in a rack with a depth of 2 units It contains the following display and control elements...

Page 4: ...mbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 4 2 1 Coupler function The IP Router can operate as a line and or backbone coupler In both cases the LAN IP...

Page 5: ...SCN IP100 01 MDT technologies GmbH 51766 Engelskirchen Papierm hle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 5 Figure 3 KNX IP Router as a backbone coupler Figure 4 KNX IP Router as a...

Page 6: ...coupler x y 0 there must be no KNX IP Router in the topology above it For example if a KNX IP Router has the physical address of 1 1 0 there must be no KNX IP Router with the ad dress 1 0 0 The KNX I...

Page 7: ...ive e g Line TF It is used to search for and recognize a device Monitoring bus voltage failure If a KNX EIB failure is detected it is reported on the IP Return of the bus voltage is also reported Para...

Page 8: ...ion 1 Figure 6 IP configuration 1 IP Routing Multicast Address This address is used for routing telegrams on IP The multicast IP address 224 0 23 12 was reserved KNXnet IP at the IANA Internet Assigne...

Page 9: ...ess of the gateway here Note If the KNX IP Router will only be used in the local LAN the entry of 0 0 0 0 can remain unchanged Example of assigning IP addresses A PC is to be used to access the KNX IP...

Page 10: ...are routed to IP Route All group telegrams of main groups 14 and 15 are routed to IP Group telegrams main groups 16 to 31 Block No group telegrams of these main groups are routed to IP Route An addit...

Page 11: ...is generated for every received physically addressed telegram from KNX EIB Only if routed An acknowledge is only generated for received physically addressed group telegrams from KNX EIB if they are ro...

Page 12: ...disabled or enabled in pairs Physically addressed telegrams Block No physically addressed telegrams are routed to KNX EIB Route All physically addressed telegrams are routed to KNX EIB Filter The phy...

Page 13: ...llowing configuration is necessary Select the button Settings and the tab Communication in the main window of ETS4 All available connections are listed by Configured connections Select the desired con...

Page 14: ...e device Page 3 Figure 2 KNX IP Router as Line Coupler Page 4 Figure 3 KNX IP Router as a backbone coupler Page 5 Figure 4 KNX IP Router as a backbone and line coupler Page 5 Figure 5 General settings...

Page 15: ...can occur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 6 2 Routine disposal Do not throw the waste...

Page 16: ...lectrical isolation between the lines and reduction of the busload by using the filter function The MDT KNX Interfaces are modular installation devices for fixed installation in dry rooms They fit on...

Page 17: ...ore 0 8mm solid core 0 8mm solid core Power Supply via KNX bus 12 to 24VAC DC 12 to 24VAC DC via KNX bus Power consumption 0 3W 0 8W 0 8W 0 3W each line Operation temperature range 0 to 45 C 0 to 45 C...

Reviews: