24
5-ASSEMBLY
SETTING UP THE CLADDING
The product must be fully tested before the cladding is applied. The company cannot be held liable for any damage to
the cladding should operating anomalies arise, which were not verified before the cladding was applied to the product.
IT IS MANDATORY to check the tightness of all the pipes through which smoke passes (smoke fitting, gaskets and flue
coupling) before setting up the cladding.
READ THE “OPERATION TEST” CHAPTER BEFORE SETTING UP THE PRODUCT CLADDING.
The product and the cladding parts must be fastened together
WITH NO CONTACT MADE WITH THE STEEL STRUCTURE
in order to
prevent heat from being transmitted to the marble and/or stone and to allow for normal thermal expansion. Pay attention to the wood
finishes, such as beams or shelves.
It is recommended to set up the counter hood made of 15 to 20 mm thick fireproof plasterboard with a freestanding frame made of a
galvanised profile to prevent bearing the weight on the cladding components (wooden beams or marble lintels), which do not have a
freestanding structure
in order to intervene easily in case of anomalies and/or future maintenance
. Dry mount the hearth of the
cladding, leaving a 1 cm gap
between the insert and the hearth for insulation.
WOODEN BEAM INSULATION
If you wish to mount a wooden beam, it must be protected with adequate insulation from the hot parts in order to prevent the risk of fire
or damage to the cladding.
STANDARD CLADDING ASSEMBLY.
The installation guide found in each specific cladding must be referred to for the setting up of product specific claddings.
1- INSULATION: APPLIED OR TO BE APPLIED
2 - WOODEN BEAM
3 - MARBLE OR OTHER MATERIAL