803 B – 04/11 D – pag. 11/24
Physical data PFS “B”
PFS Unit size
103.1
124.1
147.1
208.2
229.2
249.2
272.2
296.2
Cooling capacity (1)
kW
369
445
521
734
816
895
976
1050
Power input (1)
kW
65
78
90
130
143
155
168
180
COP (1)
5.7
5.7
5.8
5.7
5.7
5.8
5.8
5.8
McQuay Screw compressors
No.
1
1
1
2
2
2
2
2
Refrigerant circuits
No.
1
1
1
1
1
1
1
1
Min % of capacity reduction
%
25,0
25,0
25,0
12,5
12,5
12,5
12,5
12,5
Refrigerant charge HFC 134a
kg
130
165
180
200
215
230
274
290
Oil charge
l
30
30
30
60
60
60
60
60
Evaporator
Evaporators / water volume
No./l
1/78
1/107
1/134
1/184
1/210
1/210
1/281
1/302
Max water operating pressure
bar
10,5
10,5
10,5
10,5
10,5
10,5
10,5
10,5
Condenser
Condensers / water volume
No./l
1/83
1/111
1/133
1/181
1/199
1/243
1/243
1/263
Max water operating pressure
bar
10,5
10,5
10,5
10,5
10,5
10,5
10,5
10,5
Weight and dimensions
Shipping weight
kg
3089
3370
3603
5546
5636
6007
6448
6598
Operating weight
kg
3250
3588
3870
5911
6045
6460
6972
7163
Unit length (2)
mm
3625
3860
3860
4145
4145
4145
4145
4145
Unit width
mm
1551
1551
1551
1743
1743
1808
1910
1910
Unit height
mm
2250
2250
2250
2300
2300
2300
2300
2300
Note: (1)
Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
30/35 °C entering/leaving condenser water temperature.
(2)
Length includes modulating condenser water flow valve.
Electrical data PFS “B”
PFS unit size
103.1
124.1
147.1
208.2
229.2
249.2
272.2
296.2
Standard voltage (1)
400 V – 3Ph – 50 Hz
Nominal unit current (2)
A
112
129
148
224
244
258
277
295
Max unit current (3)
A
137
178
205
302
331
357
385
410
Max unit inrush current (4)
A
367
367
367
535
550
561
575
588
Max unit current for wires sizing (5)
A
142
183
210
307
336
362
390
415
Max short circuit holding current
kA
25
25
25
25
25
25
25
25
Notes: (1)
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2)
Absorbed current referred to nominal condition: 12/7 °C entering/leaving evaporator water temperature; 30/35 °C
entering/leaving condenser water temperature.
(3)
Absorbed current referred to the following conditions: 15/10 °C entering/leaving evaporator water temperature;
45/50°C entering/leaving condenser water temperature.
(4)
Absorbed current of compressor n°1 at 75% + inrush current of the other compressor.
(5)
Compressors FLA (Full Load Ampere).