background image

IM620-1

31

Troubleshooting Power Problems

The MCB receives 18 Vac, center-tapped power from transformer T2. It then distributes both 5 Vdc
and 13 Vdc power to various MicroTech components. A problem that exists in any of these
components can affect the MCB and thus the entire control system. Power problems can be caused
by an external short, which can blow a fuse, or a defective component, which can either blow a fuse or
create an excessive load on the power supply. An excessive load can lower the power supply voltages
to unacceptable levels. Use the following procedure to isolate the problem. This procedure may
require two or three spare MCB fuses (see parts list). Refer to the panel wiring diagram or Figures 15
and 17 as you proceed.

1.

 

Verify that circuit breaker CB1 is closed.

2.

 

Remove the MCB Power In connector and check for 9 Vac between the terminals on the plug
corresponding to terminals 2 and 3 on the board (see Figures 2 and 18). Then check for 9 Vac
between the terminals on the plug corresponding to terminals 1 and 3 on the board. (Readings of
9–12 Vac are acceptable.)

a.

 

If 9 Vac is present between both sets of terminals, go to step 3.

b.

 

If 9 Vac is not present between both sets of terminals, check transformers T2 and T1 and all
wiring between the 115 Vac source and the Power In plug.

3.

Remove power from the controller by opening circuit breaker CB1. Check the MCB power supply
input fuses (F1 and F2) with an ohmmeter. See Figure 18. A good fuse has negligible resistance
through it (less than 2 ohms).

a.

 

If either or both fuses are blown, replace them. Go to step 4.

b.

 

If the fuses are intact, the MCB is defective.

4.

Reconnect the Power In plug and disconnect all other connectors  on the MCB. Cycle power to
the controller (close and then open CB1) and check the power fuses.

a.

 

If both fuses are intact, go to step 5.

b.

 

If either fuse blows, the MCB is defective.

5.

Reconnect the analog input ribbon cable. Cycle power and check the power fuses.

a.

 

If both fuses are intact, go to step 7.

b.

 

If either fuse blows, check the ICM Terminal Board, the connecting ribbon cable, and the
field wiring for shorts. Any of these may be defective.

6.

Reconnect the digital input ribbon cable. Cycle power and check the power fuses.

a.

 

If both fuses are intact, go to step 8.

b.

 

If either fuse blows, check the ICM Terminal Board, the connecting ribbon cable, and the
field wiring for shorts. Any of these may be defective.

7.

Reconnect the digital output ribbon cable to t he MCB. Cycle power and check the power fuses.

a.

 

If both fuses are intact, go to step 9.

b.

 

If either fuse blows, check Output Board and the connecting ribbon cable. Either of these
may be defective.

8.

If there are any AOX-4 boards, reconnect the expansion bus ribbon cable to the MCB; otherwise,
go to step 10. Cycle power and check the power fuses.

a.

 

If both fuses are intact, go to step 10.

b.

 

If either fuse blows, check the Analog Output Expansion Modules (if any), the connecting
ribbon cables, and the field wiring for shorts. Any of these may be defective.

9.

With circuit breaker CB1 open, measure the resistance between field terminals “DC-GRD” and “5
Vdc.” It should be greater than 20 ohms.

If the resistance is greater than 20 ohms, go to step 11 if the controller is equipped with at least
one AOX-4 board or a modem. Otherwise, the problem is indeterminate. Obtain factory service.

Summary of Contents for MicroTech MAG

Page 1: ...tion Maintenance Data IM 620 1 Group Controls Part Number 585524Y Date February 1998 1998 McQuay International MicroTech Absorption Gateway for Absorption Chillers MicroTech Absorption Gateway MicroTe...

Page 2: ...unications Trunk 23 Service Information 28 Wiring Diagrams 28 Test Procedures 30 Status LED Diagnostics 30 Troubleshooting Power Problems 31 Troubleshooting Analog Outputs 32 Troubleshooting Output Bo...

Page 3: ...LED Indication 9 Table 4 Amber Status LED Indication 9 Table 5 Program Codes 11 Table 6 Accessory Installation Manuals 11 Table 7 PC Specification 13 Table 8 MAG Panel Environmental Specifications 14...

Page 4: ...stop signals Cooling water inlet outlet temperature Heating cooling simultaneous and abnormality indicators Condensation temperature SVRP and SVRU valves Remote reset setting Cooling main heating mai...

Page 5: ...al device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment Operat...

Page 6: ...his type of configuration is called the Network Connect MAG The base panel is equipped with eight AC power rated relays plus the necessary hardware to support the addition of accessories listed in Tab...

Page 7: ...rocessor Control Board The Microprocessor Control Board MCB is shown in Figure 2 It contains a microprocessor that is preprogrammed with the software required to monitor the data from the absorption c...

Page 8: ...ormation on the Analog Output Expansion Module Power In Connector The MCB receives 18 Vac center tapped power through transformer T2 and the Power In connector This power drives all logic and communic...

Page 9: ...On 1 second Off 1 second Communications exists between the MAG and the absorption chiller On 2 10 second Off 2 10 second Communications does not exist between the MAG and the absorption chiller Hex S...

Page 10: ...using the RS 485 interface standard A twisted shielded pair cable should be connected to port B via terminals B B and GND on terminal block T11 The communications rate is 9600 bps For more informatio...

Page 11: ...VENDOR MDL 280 50 DATE CODE 10 94 MCB part number Program code Ident Table 5 Program Codes MAG Type Program Code Direct Connect 950468 010 Network Connect 950469 010 Accessories The accessories of th...

Page 12: ...C AC DC G Power LEDs 26 pin Expansion Bus Connector 26 pin Expansion Bus Connector Power Connector a0166 MicroTech Monitoring and Networking Options PC Monitoring A PC personal computer equipped with...

Page 13: ...quired because the MAG can connect directly to the BAS interface If two or more MAG Panels are included the MicroTech Open Protocol Master OPM Panel is required For further information contact your Mc...

Page 14: ...screw By adjusting this screw you can prevent the panel door from swinging open or closed unexpectedly Table 8 MAG Panel Environmental Specifications Panel State Temperature Relative Humidity Operatin...

Page 15: ...r to Figures 7 and 8 Power wiring must be sized to carry at least 5 amps To gain access to the high voltage section remove the deadfront barrier It is attached to the panel with five 5 16 inch hex scr...

Page 16: ...nd MAG 2 It is highly recommended that the installing contractor keep track of the physical order of the controllers on the daisy chained trunk This facilitates troubleshooting any network communicati...

Page 17: ...ble Communications Interface Cable Hot Neutral Hot Neutral Legend Field Wiring Terminal Cable Shielded Twisted and Jacketed Pair with Drain Wire Factory Wiring Field Wiring Line Input Line Input WHT B...

Page 18: ...ions Interface Cable Hot Neutral Legend Field Wiring Terminal Cable Shielded Twisted and Jacketed Pair with Drain Wire Factory Wiring Field Wiring Line Input a0168 PC Connection The PC is connected to...

Page 19: ...connection between the PC and a controller is 50 feet Cable Specification for Direct PC Connection A properly terminated twisted shielded pair cable is required to directly connect a PC to a MicroTech...

Page 20: ...damage The analog output signals voltage mode must be isolated from any ground other than the MicroTech controller chassis ground If it is not ground loop currents could occur which could damage the M...

Page 21: ...24V GND Ribbon Cable Expansion Bus 13 VDC GND DC GND MCB 24V AC 13V DC 13V DC AOX 4 Board Analog Output Device Current Mode 24 VAC Power Analog Output Device Voltage Mode 24 VAC Power To MicroTech Co...

Page 22: ...For more on hex switch settings see Microprocessor Control Board in the Component Data section of this manual The Network Connect MAG Network The Network Connect MAG Network includes a Network Master...

Page 23: ...ock or directly on the port B connector of the level 1 controller With one lead on the control panel chassis ground check for voltage at the and ground terminals There should be no AC or DC voltage se...

Page 24: ...PORT B FUSE BUSSMAN MCR 1 4 FUSE 1 3 2 4 5 3 1 2 4 6 a0114 Network MAG Controller Connection In order for the NMP OPM or other level 1 controller in a network to connect and communicate with level 2...

Page 25: ...on trunk voltages at the field wiring terminals if any or directly on the connector The trunk must not be connected to the controller when you do this If no voltage or improper voltages are found chec...

Page 26: ...to the MAG Panel or connection to port A if an AMP connector was used Check to see if the MAG Panel and the absorption chiller unit controller are energized Direct Connect MAG Controller Connection T...

Page 27: ...ber LED on the MAG controller stays on for 1 second and goes off for 1 second if communications exists see Table 4 Amber Status LED Indication in the Component Data section of this manual If communica...

Page 28: ...shown in Figure 14 Figure 14 Network Connect MAG Schematic Legend Component Designation Description CB1 Circuit Breaker MCB Microprocessor Control Board OB Output Board AOX BRD Auxiliary Output Expan...

Page 29: ...s reproduced here for your convenience The legend is shown in Figure 16 Figure 16 Direct Connect MAG Schematic Legend Component Designation Description CB1 Circuit Breaker MCB Microprocessor Control B...

Page 30: ...described in the Component Data section of this manual see Tables 3 and 4 there is a problem with the MCB Following are troubleshooting procedures for the various symptoms Red LED Remains On If the r...

Page 31: ...ce them Go to step 4 b If the fuses are intact the MCB is defective 4 Reconnect the Power In plug and disconnect all other connectors on the MCB Cycle power to the controller close and then open CB1 a...

Page 32: ...o step 13 b If the resistance does not rise above 5000 ohms the MCB is defective 12 One at a time reconnect the modem and each AOX 4 board as applicable Each time a component is reconnected measure th...

Page 33: ...tput Boards Each output on the output board consists of a solid state relay an LED 5 amp fuse and an MOV metal oxide varistor Normally when the MCB commands an output to energize the solid state relay...

Page 34: ...Restore power by pressing CB1 to the ON position The LED should light regardless of the controller s command a If the output LED illuminates it is likely that the MCB is defective b If the output LED...

Page 35: ...components Output Energized LED not Lit If the LED of a suspect output is not lit but the load connected to it is energized either the solid state relay or the MOV is bad The solid state relay contac...

Page 36: ...re 20 In this circuit a solid state relay behaves like an electromechanical relay If the relay is energized the relay output is hot If the relay is de energized voltage cannot be measured at the relay...

Page 37: ...s program Therefore it is possible to download the proper controller software to a replacement MCB at the building site if a PC equipped with that job s Monitor software is available In addition if t...

Page 38: ...ibbon Cable Assembly 3 AOX 4 to AOX 4 654997B 06 CIC Communications Interface Cable 50 733173B 01 AOX 4 Analog Output Expansion Module 005532370 1 SSR Solid State Relay Kit 005532390 1 Solid State Rel...

Page 39: ...IM620 1 39...

Page 40: ...40 IM620 1...

Page 41: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...

Reviews: